Kimo ATE 310 Manual de usuario

ATE 310 transmitters configuration by keypad


Table of contents
1. Introduction..........................................................................................................................................5
1.1. Transmitter description.................................................................................................................5
1.2. Keys description...........................................................................................................................5
2. Modbus................................................................................................................................................6
2.1. Settings........................................................................................................................................6
2.2. Functions......................................................................................................................................6
2.3. Access code to register................................................................................................................6
3. Access to the di erent unctions.........................................................................................................9
4. F 100 : Con igure the transmitter......................................................................................................10
4.1. Access to the serial number : F100...........................................................................................10
4.2. Access to the irmware version : F101.......................................................................................10
4.3. Lock the keyboard : F 140.........................................................................................................10
4.4. Modi y the security code : F141.................................................................................................10
4.5. Con igure the Modbus communication......................................................................................11
4.5.1 Con igure the slave number : F150.....................................................................................11
4.5.2 Con igure the communication speed : F151........................................................................11
4.6. Activate the options....................................................................................................................11
4.7. Activate the digital input : F180..................................................................................................11
4.8. Back to actory settings : F190..................................................................................................12
5. F 200 : Con iguration o the channels and measurement units........................................................13
5.1. Activate a channel......................................................................................................................13
5.2. Assign a measurement unit to a channel...................................................................................13
6. F 300 : analog inputs management..................................................................................................14
6.1. Set the analog inputs.................................................................................................................15
6.2. Set the ranges o analogue outputs...........................................................................................15
6.3. Measurements conversion tables..............................................................................................16
6.4. Set the decimal point position....................................................................................................16
7. F400 : Alarms management..............................................................................................................17
8. F 520 : Measurement setting............................................................................................................19
8.1. Add a coe icient.........................................................................................................................19
8.2. Add an o set..............................................................................................................................19
9. Functions recap and Modbus connections.......................................................................................20
9.1. F 100 : Con igure the transmitter...............................................................................................20
9.2. F 200 : Con igure the channels and the measurement units....................................................20
9.3. F 300 : Manage the analogue inputs.........................................................................................21
9.4. F 400 : Manage the alarms........................................................................................................21
9.5. F 500 : Set the measurement....................................................................................................23


1. Introduction
1.1. Transmitter description
The ATE310 transmitter can be configured with the keyboard. It is possible to set the measurement units, to acti ate or not
a channel,…
Philosophy : the different settings are indicated under a folder and sub folder number form. These digital codes are
explained in details in the user manual.
1.2. Keys description
–Up key : increments a alue or a le el
–Down key : decrements a alue or a le el
–OK key : alidates the entry
–Esc key : cancels the entry or goes back to the pre ious step
Introduction 5
Up key
Down key
OK key
Esc key
10 Pa
Channel 1 indicator light Channel 3 indicator light
Channel 2 indicator light
Front access to the
mini-Din connector for a
connection on PC

2. Modbus
2.1. Settings
•Communication speed : between 2400 and 115200 bauds, 19200 bauds by default
•Data Bits : 8 bits
•Stop bit : 1 bit
•Parity : None
•low control : None
•Transmitter addressing : between 1 and 255 (always answers to requests from address 0)
•Data sending : carried out by words of 2 bytes, in the following order : high weight then low weight
2.2. Functions
•Registers reading : Function 03
•Registers writing : Function 16
•Communication loop test : Function 08
2.3. Access code to register
•Registers type
Type Size Designation ormat
U8 1 byte Unsigned integer 8 bits Byte 1
Example with a 24 (0x18) alue 0x18
Type Size Designation ormat
U16 2 bytes Unsigned integer 16 bits Byte 2 Byte 1
Example with a 300 (0x012C) alue 0x01 0x2C
Type Size Designation ormat
U32 4 bytes Unsigned integer 32 bits Byte 2 Byte 1 Byte 4 Byte 3
Example with a 1 096 861 217 (0x4160C621) alue 0xC6 0x21 0x41 0x60
Type Size Designation ormat
Real 4 bytes Real 32 bits Byte 2 Byte 1 Byte 4 Byte 3
Example with a 153.5 (0x43198000) alue 0x80 0x00 0x43 0x19
Type Size Designation ormat
Enumeration 1 byte See the Enumeration table
page 8
Idem U8
Boolean 1 byte True = 1 ; False = 0 Idem U8
6Modbus

Type Size Designation Example
Serial number 8 bytes Class (1 byte)
Range (1 byte)
Year (2 bytes)
Month (1 byte)
Number (3 bytes)
'3' (0x33)
'F' (0x46)
13 (0x000D)
8 (0x08)
98765 (0x0181CD)
ormat
Byte 2 (range) Byte 1 (class) Byte 4 (year) Byte 3 (year) Byte 6
(number)
Byte 5
(month)
Byte 8
(number)
Byte 7
(number)
0x46 0x33 0x00 0x0D 0xCD 0x08 0x01 0x81
Example with 3 13898765 : 0x0181CD08000D4633
Alarms and relays status – Modbus Code 7000
Encoded on 4 bytes (U32)
Byte 2 Byte 1
b8 – b15 b7 – b4 b3 b2 b1 b0
Unused Unused Unused Channel 3 Channel 2 Channel 1
Alarm status*
(*)1 : the channel is in alarm state / 0 : the channel is not in alarm state
Byte 4 Byte 3
b31 – b28 b27 b26 b25 b24 b23 – b20 b19 b18 b17 b16
Unused Relay 4** Relay 3** Relay 2** Relay 1** Unused Unused Alarm 3*** Alarm 2*** Alarm 1***
(**)1 : the alarm is acti ated / 0 : the alarm is deacti ated
(***)1 : the relay is triggered / 0 : the relay is not triggered
•Values (real) – Modbus code : 7010 (channel 1)
7040 (channel 2)
7070 (channel 3)
•Number of digits after the decimal point (U8) – Modbus code : 7020 (channel 1)
7050 (channel 2)
7080 (channel 3)
•Unit (U8) – Modbus code : 7030 (channel 1)
7060 (channel 2)
7090 (channel 3)
Modbus 7

List of units :
ield Unit Value
None 0
Temperature °C 16
°F 17
Hygrometry
%RH 32
g/kg 33
Kj/KG 34
°C td 35
°F td 36
°C Tw 37
°F Tw 38
Pressure
kPa 50
inWg 51
hPa 52
mbar 53
mmHg 54
mmH2O 55
daPa 56
Pa 57
Air velocity
m/s 64
fpm 65
km/h 66
Combustion ppm 112
“Enumerations” table :
Corresponding values 0 1 2 3 4 5 6 7
Modbus Communication
speed 2400 4800 9600 19200 38400 115200 Unused
Channel x Unit See units list
Channel x Transmitter None Probe 1 Module Unused
Input x Type 4 - 20 mA 0 - 20 mA 0 - 10 V 0 - 5 V 0 – 2.5 V Unused
Alarm x Mode Deacti ated Rising edge Falling edge Monitoring Unused
Alarm x Security Negati e Positi e Unused
8Modbus

3. Access to the different functions
This step is necessary for each configuration of the transmitter.
To ha e an access to the transmitter functions, and for security measures, you need to fill in a security code. By default, this
security code is 0101.
•Verify that the transmitter is powered.
➢Connect the transmitter.
➢Wait the end of the initialization phase.
➢Press OK.
“Code” is displayed with “0000”. The first 0 flashes.
➢Press OK to mo e on the second 0.
It flashes.
➢Press Up key to display 1 then press OK.
The third 0 flashes.
➢Press OK to mo e on the fourth 0.
➢Press Up key to display 1 then press OK.
The following screen appears :
“ 100” corresponds to the configuration folder number. 5 are existing :
• 100 : folder of the de ice configuration. See page 10.
• 200 : folder of the channels and measurement units. See page 13.
• 300 : folder of the analogue inputs. See page 14.
• 400 : folder of the alarms. See page 17.
• 500 : folder of the channel configuration, the integration and autozero. See page 19.
To select the required configuration folder :
“F 100” is displayed and 1 is blinking.
➢Press Up key until the required folder number displays (F 100, F 200, F 300 or F 500).
➢Press OK.
9Access to the different functions
Code
0101
F 100

4. F 100 : Configure the transmitter
This folder enables to configure the following parameters of the transmitter : security code, modbus, options and factory
configuration.
It also enables an access to the serial number and the firmware ersion of the transmitter.
4.1. Access to the serial number : F100
The serial number enables to obtain acti ation codes for the options.
F 100 is displayed (see previous page .
➢Press OK.
“F 100” displays on the screen with the serial number of the transmitter which is scrolling below.
4.2. Access to the irmware version : F101
The F100 folder is displayed.
➢Press Up key.
“F 101” displays on the screen with the version number of the firmware below. (Ex : 1.00
4.3. Lock the keyboard : F 140
For more security and a oid any handling mistake, it is possible to lock the transmitter keys.
The sub folder F101 is displayed on the screen.
➢Press Up key.
“F 140” displays on the screen with “0” meaning that the locking is deactivated.
➢Press OK.
“0” flashes.
➢Press Up or Down key, “1” is flashing then press OK.
“LOCK” displays for a few seconds then the transmitter returns to the measured values.
All the keys are inactive.
To reactivate them :
➢Press 10 seconds OK key.
“LOCK” displays for a few seconds then the transmitter returns to the display of measured values and the keys
are active again.
4.4. Modi y the security code : F141
It is possible to modify the security code.
The sub folder F140 is displayed on the screen.
➢Press Up key.
“F 141” is displayed on the screen and the security code is displayed below.
➢Press OK.
The first zero flashes.
➢Press Up or Down key to modify the digit then press OK.
The second digit flashes.
➢Press Up or Down key to modify the digit then press OK.
The third digit flashes.
➢Press Up or Down key to modify the digit then press OK.
The fourth digit flashes.
➢Press Up or Down key to modify the digit then press OK.
“OK ?” is displayed on the screen.
➢Press OK key to alidate the code modification or on Esc to cancel.
The transmitter returns to the display of the F141 folder with the new code indicated below.
10 F 100 : Configure the trans itter
Tabla de contenidos
Otros manuales de Transmisor de Kimo

Kimo
Kimo Class 200 Manual de usuario

Kimo
Kimo CPE 311-S Manual de usuario

Kimo
Kimo C310 Manual de usuario

Kimo
Kimo 210-R Series Manual de usuario

Kimo
Kimo Class 300 Manual de usuario

Kimo
Kimo CP 111 Manual de instrucciones

Kimo
Kimo CA 310 Manual de usuario

Kimo
Kimo TG 100 Manual de instrucciones

Kimo
Kimo HM 50 Manual de instrucciones

Kimo
Kimo CPE 300 Manual de usuario
Manuales populares de Transmisor de otras marcas

Dejero
Dejero EnGo 3x Manual de usuario

Rosemount
Rosemount 4600 Manual de usuario

Speaka Professional
Speaka Professional 2342740 Manual de usuario

trubomat
trubomat GAB 1000 Manual de usuario

Teledyne Analytical Instruments
Teledyne Analytical Instruments LXT-380 Manual de usuario

Rondish
Rondish UT-11 Manual de usuario