KEPCO SUPERtrol II Guía del usuario

990375 05/05/17
Document Revision: 2.A
Web Congurator Template
Revision: 61
APPLICABILITY & EFFECTIVITY
Explains hardware specications, setup instructions and usage.
The instructions are effective for the above as of August 2016.
Multi-Protocol Communication Card (COM CARD)
Start-up Guide
For Interfacing KEP Products: SUPERtrol_II, SUPERtrol_I,
LEVELtrol_II, ES762-ST2
To Building Automation Systems:
BACnet MS/TP, BACnet/IP, Modbus TCP/IP, Metasys N2,
EtherNet/IP, DF1 and LonWorks

KEP Multi-Protocol Communication Card Option Start-up Guide
Page 2
Technical Support
Support Contact Information:
Kessler-Ellis Products
10 Industrial Way East Eatontown,
NJ 07724
Customer Service:
(800) 631 – 2165
(732) 935 – 1320
Email: [email protected]
Website: www.KEP.com

KEP Multi-Protocol Communication Card Option Start-up Guide
Page 3
Quick Start Guide
1. Record the information about the unit. (Section 3.1)
2. Set the device’s Modbus RTU serial settings (i.e. baud rate, parity, stop bits) and Modbus
Node-ID for the device connected to the COM CARD. (Section 3.3)
3. Metasys N2 or Modbus TCP/IP: Set the Node-ID. (Section 3.3.2)
4. Connect COM CARD 4 pin RS-485 port to the Field Protocol cabling, (Section 4.2) for LonWorks
port (Section 4.3)
5. Use a browser to access the embedded tool, which is referred to in this manual as the Web
Congurator, to select the device that will be attached to COM CARD and set the Modbus
Node-ID. Once the device is selected, the COM CARD Automatically builds and loads the
Conguration. (Section 5)
6. BACnet/IP or Modbus TCP/IP (Option 3): Use a browser to access the COM CARD Web
Congurator to change the IP Address. No changes to the conguration are necessary. (Section
5.4)
7. LonWorks (Option 4): The COM CARD must be commissioned on the LonWorks Network. This
needs to be done by the LonWorks administrator using a LonWorks Commissioning tool.
(Section 8)

KEP Multi-Protocol Communication Card Option Start-up Guide
Page 4
TABLE OF CONTENTS
1 CERTIFICATIONS ....................................................................................................................................................... 6
1.1 BTL Mark – BACnet Testing Laboratory .............................................................................................................. 6
1.2 LonMark Certication ............................................................................................................................................ 6
2 INTRODUCTION ......................................................................................................................................................... 7
2.1 COM CARD Gateway ......................................................................................................................................... 7
3 SETUP FOR COM CARD ........................................................................................................................................... 8
3.1 Record Identication Data .................................................................................................................................... 8
3.2 Point Count Capacity and Registers per Device .................................................................................................. 8
3.3 Conguring Device Communications ................................................................................................................... 9
3.3.1 Input COM Settings for all Devices with an Inserted COM CARD ..................................................................... 9
3.3.2 Set Modbus Node-ID for the Device ................................................................................................................... 9
4 INTERFACING COM CARD TO DEVICE ................................................................................................................. 10
4.1 Connection Ports ................................................................................................................................................ 10
4.2 BACnet MS/TP or Metasys N2 (Option 3): Wiring Field Port to RS-485 Network .......................................11
5 USE COM CARD WEB CONFIGURATOR TO SETUP THE GATEWAY ................................................................. 12
5.1 Connect the PC to COM CARD via the Ethernet Port ........................................................................................ 12
5.2 Connecting to COM CARD Web Congurator ..................................................................................................... 13
5.3 Selecting Proles for Device Connected to COM CARD .................................................................................... 13
5.4 BACnet/IP and Modbus TCP/IP: Setting IP Address for Field Network ............................................................... 15
5.5 Select Field Protocol ........................................................................................................................................... 17
5.5.1 BACnet/IP Conguration ................................................................................................................................. 17
5.5.2 BACnet MS/TP Conguration ........................................................................................................................... 18
5.5.3 Metasys N2, Modbus TCP and EtherNet/IP Conguration .............................................................................. 19
5.5.4 DF1 Conguration ........................................................................................................................................... 19
6 BACNET MS/TP AND BACNET/IP: SETTING NODE_OFFSET TO ASSIGN SPECIFIC DEVICE INSTANCES . 20
7 HOW TO START THE INSTALLATION OVER: CLEARING PROFILES .................................................................. 21
8 LONWORKS (Option 4): COMMISSIONING COM CARD ON A LONWORKS NETWORK ................................ 22
8.1 Commissioning COM CARD on a LonWorks Network ........................................................................................ 22
8.1.1 Instructions to Download XIF File from COM CARD Using Browser ................................................................ 22
9 BACNET EXPLORER ............................................................................................................................................... 24
Appendix A. Troubleshooting .................................................................................................................................... 25
Appendix A.1. Lost or Incorrect IP Address ............................................................................................................... 25
Appendix A.2. Viewing Diagnostic information ........................................................................................................... 26
Appendix A.3. Check Wiring and Settings ................................................................................................................. 27
Appendix A.4. LED Diagnostics for Communications Between COM CARD and Device ......................................... 28
Appendix A.5. Take Diagnostic Capture With the FieldServer Toolbox ...................................................................... 29
Appendix A.6. Update Firmware ................................................................................................................................. 32
Appendix A.8. Reading Data Arrays ........................................................................................................................... 33
Appendix B. Vendor Information - KEP ..................................................................................................................... 34
Appendix B.2. SUPERtrol_I Modbus RTU Mappings to BACnet, Metasys N2, EtherNet/IP, DF1,Modbus TCP/IP and
LonWorks ......................................................................................................................................................................... 36
Appendix B.3. LEVELtrol_II Modbus RTU Mappings to BACnet, Metasys N2, EtherNet/IP, DF1, Modbus TCP/IP and
LonWorks ......................................................................................................................................................................... 37
Appendix B.4. ES762-ST2 Modbus RTU Mappings to BACnet, Metasys N2, EtherNet/IP, DF1, Modbus TCP/IP and
LonWorks ...................................................................................................................................................................... 38
Appendix C. Reference ............................................................................................................................................... 40
Appendix C.1. Specications ....................................................................................................................................... 40
Appendix D. Limited 2 Year Warranty ........................................................................................................................ 41

KEP Multi-Protocol Communication Card Option Start-up Guide
Page 5
NOTES

KEP Multi-Protocol Communication Card Option Start-up Guide
Page 6
1 CERTIFICATIONS
1.1 BTL Mark – BACnet Testing Laboratory
1.2 LonMark Certication
The BTL Mark on the COM CARD is a symbol that indicates that a product has
passed a series of rigorous tests conducted by an independent laboratory which
veries that the product correctly implements the BACnet features claimed
in the listing. The mark is a symbol of a high-quality BACnet product.
Go to http://www.BACnetInternational.net/btl/ for more information about the
BACnet Testing Laboratory. Click here for BACnet PIC Statement.
LonMark International is the recognized authority for certication, education,
and promotion of interoperability standards for the benet of manufacturers,
integrators and end users. LonMark International has developed extensive
product certication standards and tests to provide the integrator and user with
condence that products from multiple manufacturers utilizing LonMark de-
vices work together.

KEP Multi-Protocol Communication Card Option Start-up Guide
Page 7
2 INTRODUCTION
2.1 PCOM CARD
The COM CARD option is an internal, high performance Building Automation multi-protocol gate-
way that is precongured to automatically communicate between KEP’s products (hereafter called
“device”) connected to the COM CARD and automatically congures them for BACnet®1MS/TP, BAC-
net/IP, Metasys®2N2 by JCI, Modbus TCP/IP, EtherNet/IP, DF1 or LonWorks®3.
It is not necessary to download any conguration les to support the required applications.
The COM CARD is pre-loaded with tested Proles/Congurations for the supported devices.
1BACnet is a registered trademark of ASHRAE
2Metasys is a registered trademark of Johnson Controls Inc.
3LonWorks is a registered trademark of Echelon Corporation

KEP Multi-Protocol Communication Card Option Start-up Guide
Page 8
3 SETUP FOR COM CARD
3.1 Record Identication Data
3.2 Point Count Capacity and Registers per Device
Each unit has a unique part number located on the side or the back of the unit. This number
should be recorded, as it may be required for technical support.
Record Your Model Number Below: Example: ST2 O 1 3 BAC/IP P
MODEL NO. __________________________________________________________________
• Option 3 units have the following 2 ports: Ethernet + RS-485
• Option 4 units have the following 2 ports: LonWorks + Ethernet
The total number of Registers presented by the device attached to the COM CARD cannot
exceed:
Model Protocols Supported
Option 3 (Specify Protocol) BACnet IP, BACnet MS/TP, Modbus TCP/IP, Meyasys
N2, AB DF1, AB Ethernet/IP
Option 4 (LonWorks) LonWorks
COM CARD Option Part Numbers
Part number Total Registers
Option 3 1,500
Option 4 1,500
Figure 2: Supported Point Count Capacity
Devices Registers Per Device
SUPERtrol_II 116
SUPERtrol_I 64
LEVELtrol_II 40
ES762-ST2 126
Figure 3: Registers per Device

KEP Multi-Protocol Communication Card Option Start-up Guide
Page 9
3.3 Conguring Device Communications
3.3.1 Input COM Settings for all Devices with an Inserted COM CARD
3.3.2 Set Modbus Node-ID for the Device
• Set Modbus Node-ID for the device the COM CARD is plugged into. The Modbus Node-ID needs to
be uniquely assigned between 1 and 255.
oThe Modbus Node-ID that is assigned for the device needs to be documented
The Modbus Node-ID assigned is used for designating the Device Instance for BAC-
net/IP and BACnet MS/TP (Section 6)
• The Metasys N2 and Modbus TCP/IP eld protocol Node-IDs are automatically set to be the
same value as the Node-ID of the Modbus RTU device.
•Set the serial device that the COM CARD is plugged into to have the same Baud Rate,
Data Bits, Stop Bits, and Parity settings as the COM CARD.
•Figure 4 species the device serial port settings required to communicate with the COM CARD.
Port Setting Device
Protocol Modbus RTU
Baud Rate 9600
Parity None
Data Bits 8
Stop Bits 1
Figure 4: COM Settings

Quad Digital Input
(ES762 only) RS-485
Ethernet
RS-232
KEP Multi-Protocol Communication Card Option Start-up Guide
Page 10
4 INTERFACING COM CARD TO DEVICE
4.1 Connection Ports
Otros manuales para SUPERtrol II
1
Este manual sirve para los siguientes modelos
3
Tabla de contenidos
Manuales populares de Hardware de computadora de otras marcas

EMC2
EMC2 VNX Series Manual del propietario

Panasonic
Panasonic DV0PM20105 Manual de usuario

Mitsubishi Electric
Mitsubishi Electric Q81BD-J61BT11 Manual de usuario

Gigabyte
Gigabyte B660M DS3H AX DDR4 Manual de usuario

Raidon
Raidon iT2300 Manual de usuario

National Instruments
National Instruments PXI-8186 Manual de usuario