Specifications subject to change without notice. | INST APD0127 E140404 | USA 150619 | Page 4of 4
12700 Stowe Drive, Suite 100, Poway, CA 92064 | Ph: (858) 578.7887 & (888) GO.INTEC | relevantsolutions.com/inteccontrols
MS – Installation
INSTALLATION INSTRUCTIONS FOR DUCT SMOKE DETECTOR
REMOTE ACCESSORIES
áNOTE: For proper installation, testing, operation and maintenance of a duct smoke detector, please refer to the detector installation guide. The following wiring diagrams
are applicable only to compatible, current limited, UL Listed remote accessories of named products. Use of any other devices may result in damage to the duct smoke
detector, potential injury, and will void any applicable warranties.
SL-2000 Series Duct Smoke Detectors
áNOTE: For remote accessories with a Trouble LED (yellow), a jumper wire must be placed between Terminals 20 and 15. The Trouble LED will illuminate when the
detector cover is removed, or if the smoke detector head is removed and the cover replaced. Trouble contacts CANNOT be connected to a Fire Alarm Control Panel when
using this option without the use of a slave relay.
áNOTE: If duct smoke detectors are interconnected for common functions, please refer to unit installation guide for proper connection of remote alarm functions.
RED
AL ARM
LED
RED
BL ACK
STRO BE
AND/OR
HO RN
RED
BL ACK
YELLOW
TROUBL E
LED
JUMPER
RED
BL ACK
YELLOW
TROUBL E
LED
BL ACK
BL ACK
KEY OR
PUSH BUTTON
“TEST / RESET”
SWITCH
RED
AL ARM
LED
RED
BL ACK
STRO BE
AND/OR
HO RN
GREEN
PILOT
LED
BL ACK
REDRED
BL ACK
YELLOW
TROUBL E
LED
JUMPER
RED
BL ACK
YELLOW
TROUBL E
LED
BL ACK
BL ACK
KEY OR
PUSH BUTTON
EST / RESET”
SWITCH
1
20
TEST / RESET TROUBLE
RED
AL ARM
LED
RED
BL ACK
STRO BE
AND/OR
HO RN
GREEN
PILOT
LED
BL ACK
RED
RED
BL ACK
YELLOW
TROUBL E
LED
JUMPER
RED
BL ACK
YELLOW
TROUBL E
LED
BL ACK
BL ACK
KEY OR
PUSH BUTTON
“TEST / RESET”
SWITCH
4
19
20
15
JUMPER
SM-501 Series Duct Smoke Detectors
áNOTE: For remote accessories with a Trouble LED (yellow), a jumper wire must be placed between Terminals 14 and 18. The Trouble LED will illuminate when the
smoke detector head is removed. Trouble contacts CANNOT be connected to a Fire Alarm Control Panel when using this option without the use of a slave relay.
áNOTE: If duct smoke detectors are interconnected for common functions, please refer to unit installation guide for proper connection of remote alarm functions.
RED
AL ARM
LED
RED
BL ACK
STRO BE
AND/OR
HO RN
GREEN
PILOT
LED
BL ACK
REDRED
BL ACK
YELLOW
TROUBL E
LED
JUMPER
RED
BL ACK
YELLOW
TROUBL E
LED
BL ACK
BL ACK
KEY OR
PUSH BUTTON
“TEST / RESET”
SWITCH
RED
AL ARM
LED
RED
BL ACK
STRO BE
AND/OR
HO RN
RED
BL ACK
YELLOW
TROUBL E
LED
JUMPER
RED
BL ACK
YELLOW
TROUBL E
LED
BL ACK
BL ACK
KEY OR
PUSH BUTTON
“TEST / RESET”
SWITCH
RED
AL ARM
LED
RED
BL ACK
STRO BE
AND/OR
HO RN
GREEN
PILOT
LED
BL ACK
REDRED
BL ACK
YELLOW
TROUBL E
LED
JUMPER
RED
BL ACK
YELLOW
TROUBL E
LED
BL ACK
BL ACK
KEY OR
PUSH BUTTON
EST / RESET”
SWITCH
21
20
TEST / RESET TROUBLE
RED
AL ARM
LED
RED
BL ACK
STRO BE
AND/OR
HO RN
GREEN
PILOT
LED
BL ACK
RED
RED
BL ACK
YELLOW
TROUBL E
LED
JUMPER
RED
BL ACK
YELLOW
TROUBL E
LED
BL ACK
BL ACK
KEY OR
PUSH BUTTON
“TEST / RESET”
SWITCH
A COPY OF THESE INSTRUCTIONS SHOULD BE LEFT WITH THE EQUIPMENT UNTIL INSTALLATION BY ALL TRADES IS FULLY
COMPLETE. FOLLOWING FINAL INSPECTION, A COPY SHOULD BE LEFT WITH THE OWNER/USER.
AVAILABLE ACCESSORIES FOR USE WITH
DUCT SMOKE DETECTORS
REMOTE ACCESSORIES
Remote AlarmMS-RA
MS-RA/R
MS-RA/P/R
MS-RA/P
MS-RH
MS-RH/KA/P/R
MS-RH/P/A
MS-RH/KA/P/A/T
MS-RA/P/T
MS-RA/FT/P
MS-KA/P/R/T
MS-RD
MS-F/T
SHP24-1575R
SHP24-1575O
SHP24-1575W
Remote Alarm, push button Test/Reset Switch
Remote Alarm, Pilot, push-button Test/Reset Switch
Remote Alarm, Pilot
Remote Alarm Horn
Remote Alarm, Pilot, Horn, key-operated Test/Reset Switch
Remote Alarm, Pilot, Horn
Remote Alarm, Trouble, Pilot, Horn, key-operated Test/Reset Switch
Remote Pilot, Trouble
Remote Pilot, Trouble, push-button Test/Reset Switch
Remote Pilot, Trouble, key-operated Test/Reset Switch
Remote Alarm
Remote Trouble
Horn/Strobe, red housing, clear cover
Horn/Strobe, white housing, opaque cover
Horn/Strobe, white housing, clear cover
SMOKE TEST GAS
TG-1000 Solo Aerosol Test Gas with Spray Nozzle
TG-2000 Solo Aerosol Test Gas with Nozzle for SL- Series Test Port
SAMPLING TUBES (RW- AND SM- SERIES) NOTCHED SAMPLING TUBES (SL- SERIES)
STS-1.0 For duct widths of 6” TO 1.0’ STN-1.0 For duct widths of 6” TO 1.0’
STS-2.5 For duct widths of 1.0’ TO 2.5’ STN-2.5 For duct widths of 1.0’ TO 2.5’
STS-5.0 For duct widths of 2.5’ TO 5.0’ STN-5.0 For duct widths of 2.5’ TO 5.0’
STS-10.0 For duct widths of 5.0’ TO 10.0’ STN-10.0 For duct widths of 5.0’ TO 10.0’
WEATHERPROOF ENCLOSURES
WP-1 Weatherproof Enclosure for RW- and SM- Series Detectors
WP-2000 Weatherproof Enclosure for SL- Series Detectors
POWER SUPPLIES
T-PB 202-1 24VAC @ 4.0A Class I Power Supply
T-PB 202-0 24VAC @ 4.0A Class I Power Supply
T-PB 303-1 24VAC @ 3.0A Class II Power Supply
T-PB 303-0 24VAC @ 3.0A Class II Power Supply
NOTICE: The information contained in this document is the most current available at the time of shipment of accompanying product, and is subject to change without notice. Future references should always be made to the most current
revision of this document. The information contained in all this document should be considered before installing or using the product. Any example applications shown are subject to the most current enforced local/national codes,
standards, approvals, certifications, and/or the authority having jurisdiction. All of these resources, as well as the specific manufacturer of any shown or mentioned related equipment, should be consulted prior to any implementation.
MS SERIES REMOTE ACCESSORIES
Power Requirements: Alarm LED 15mA @ 24VDC
Trouble LED 15mA @ 24VDC
Pilot LED 15mA @ 24VDC
Alarm Horn 20mA @ 24VDC
Sound Pressure: 78db @ 10 ft
Dimensions: Single Gang 4½” (114.3mm)H x 2¾” (69.85mm)W
Double Gang 4½” (114.3mm)H x 4½” (114.3mm)W
Wiring: LEDs/Horn 6” 24AWG Pigtails
Switches 6” 22AWG Pigtails
Approvals: UL Listed for use with duct smoke detectors including all
RW- Series, SM- Series and SL- Series duct smoke detectors
UL URRQ.S7425
CSFM 7300-1004:107
MEA 73-92-E Vol.25
RED
AL ARM
LED
RED
BL ACK
STRO BE
AND/OR
HO RN
GREEN
PILOT
LED
BL ACK
REDRED
BL ACK
YELLOW
TROUBL E
LED
JUMPER
RED
BL ACK
YELLOW
TROUBL E
LED
BL ACK
BL ACK
KEY OR
PUSH BUTTON
“TEST / RESET”
SWITCH
GREEN
PILOT
LED
BL ACK
REDRED
BL ACK
YELLOW
TROUBL E
LED
JUMPER
RED
BL ACK
YELLOW
TROUBL E
LED
BL ACK
BL ACK
KEY OR
PUSH BUTTON
“TEST / RESET”
SWITCH
11
19
ALARM
BUZZER
BUZZER
DETECTOR PCB HAS NO
WHITE STRIPE ON LEFT EDGE
PCB HAS WHITE STRIPE
ON LEFT EDGE
HS-100 Series Duct Smoke Detectors
áNOTE: If duct smoke detectors are interconnected for common functions, please refer to unit installation guide for proper connection of remote alarm functions.
RED
AL ARM
LED
RED
BL ACK
STRO BE
AND/OR
HO RN
GREEN
PILOT
LED
BL ACK
REDRED
BL ACK
YELLOW
TROUBL E
LED
JUMPER
RED
BL ACK
YELLOW
TROUBL E
LED
BL ACK
BL ACK
KEY OR
PUSH BUTTON
“TEST / RESET”
SWITCH
RED
AL ARM
LED
RED
BL ACK
STRO BE
AND/OR
HO RN
RED
BL ACK
YELLOW
TROUBL E
LED
JUMPER
RED
BL ACK
YELLOW
TROUBL E
LED
BL ACK
BL ACK
KEY OR
PUSH BUTTON
“TEST / RESET”
SWITCH
RED
AL ARM
LED
RED
BL ACK
STRO BE
AND/OR
HO RN
GREEN
PILOT
LED
BL ACK
REDRED
BL ACK
YELLOW
TROUBL E
LED
JUMPER
RED
BL ACK
YELLOW
TROUBL E
LED
BL ACK
BL ACK
KEY OR
PUSH BUTTON
EST / RESET”
SWITCH
15
7
TEST / RESET TROUBLE
RED
AL ARM
LED
RED
BL ACK
STRO BE
AND/OR
HO RN
GREEN
PILOT
LED
BL ACK
RED
RED
BL ACK
YELLOW
TROUBL E
LED
JUMPER
RED
BL ACK
YELLOW
TROUBL E
LED
BL ACK
BL ACK
KEY OR
PUSH BUTTON
“TEST / RESET”
SWITCH