INSIGHT VECTOR TR12 Manual de usuario

Insight Control TRI2 Installation Manual
www.insightcontrol.net.au
1300 665 831
Model: V-TRI2
Installation Manual

Insight Control TRI2 Installation Manual
READ AND UNDERSTAND THE INSTRUCTIONS CONTAINED HEREINAFTER BEFORE ATTEMPTING TO
UNPACK, ASSEMBLE, INSTALL, OPERATE, OR MAINTAIN THIS EQUIPMENT.
HAZARDOUS VOLTAGES ARE PRESENT THAT CAN CAUSE DEATH OR SEVERE PERSONAL INJURY. FOLLOW
PROPER INSTALLATION, OPERATION, AND MAINTENANCE PROCEDURES TO AVOID THESE VOLTAGES.
All possible contingencies that may arise during installation, operation, or maintenance, and all details and
variations of this equipment do not purport to be covered by these instructions. If further information is
required by the purchaser regarding an installation, application, or maintenance activity, please contact an
Insight Control representative or the installing contractor.
SAVE THIS MANUAL FOR FUTURE REFERENCE
Document: V-TRI2 Installation Manual
Revision: R01
Date: 20212201
Phone: 1300 665 831
Website: www.insightcontrol.net.au
Address: D3 / 5 Grevillea Place
Brisbane Airport QLD 4008

Insight Control TRI2 Installation Manual
About................................................................................................................................................................. 4
VECTOR TRI2 Controller................................................................................................................................. 4
Control Usage................................................................................................................................................ 4
Touchscreen Touchpad ................................................................................................................................. 4
System overview................................................................................................................................................ 5
System components ...................................................................................................................................... 5
Operating Instructions................................................................................................................................... 5
Typical system installation................................................................................................................................. 6
Technical notes.............................................................................................................................................. 6
Motorised Dampers....................................................................................................................................... 6
Component Positioning................................................................................................................................. 6
Touchpad................................................................................................................................................... 6
Room Sensor.............................................................................................................................................. 6
Motorised Dampers................................................................................................................................... 6
Commissioning .............................................................................................................................................. 6
Connection Diagram.......................................................................................................................................... 7
Terminals....................................................................................................................................................... 7
Troubleshooting ................................................................................................................................................ 7
Specifications..................................................................................................................................................... 8
Electrical Requirements................................................................................................................................. 8
Environmental Requirements........................................................................................................................ 8
Positioning..................................................................................................................................................... 8

Insight Control TRI2 Installation Manual
VECTOR TRI2 Controller
TRI2 operates independently of the air conditioning plant to provide temperature-based zoning control for
one zone. Features include:
• Integrated sensor or optional remote room sensor (not included)
Select the integrated sensor or the optional remote room sensor
• 24 VAC power supply
Offers substantial savings in installation costs compared to 240VAC systems
• Digital Display
Tell at a glance if the zone is open for cooling or heating.
• Quick & Easy Wiring
• BMS Integration
•Adjustable Minimum Ventilation setting
Restricts the damper from fully closing to maintain a minimum airflow.
Control Usage
TRI2 is a variable air volume zone controller suitable for use with any centralised conditioning source (e.g.
reverse cycle systems) Zoning kits comprise of one of each of the following components.
• TRI2 Controller (V-TRI2) - integrated sensor and supply air sensor
• Motorised Damper (MDB-XXX-IC) XXX = the size of the damper.
• Transformer (TFORM-24)
Touchscreen Touchpad
The TRI2 touchscreen controller compares the temperature of the air being supplied with the temperature
of the zone and modulates the damper in a direction that will benefit the zone. Zone motors connect to
and receive power from the touchpad via the Innocab cable system. Terminal connections are provided for
the 24VAC power supply, the supply air sensor, and optional external room sensor. TRI2 is equipped with
minimum ventilation calibration which adjusts a virtual stopper on the motor so that the motor is held
open a set percentage only when the zone is ON. Turning the zone OFF will override minimum ventilation
and fully close the motor.

Insight Control TRI2 Installation Manual
System components
1. TFORM-24 - 24volt Transformer
2. V-TRI2 –TRI2 Controller
3. MDB-XXX-IC –Belimo 24V 0-10V Motorised Damper barrel, where XXX is the size in millimetres
Operating Instructions
Press the button to turn the zone On and Off. Adjust the temperature by pressing for cooler &
for warmer. The setpoint range is from 20-25°C with a factory default of 22.5°C. Leave the controller in
“Auto”mode to work automatically off setpoint for heating or cooling based on return and supply air
temperature.
2
3
1

Insight Control TRI2 Installation Manual
Technical notes
A maximum number of 2 motors is allowed per output. In the event of power loss and restore to the
controller (i.e. blackout), the controller will drive the damper fully open before returning to the state (on or
off) and position it was in prior to the loss of power.
Motorised Dampers
Belimo 24V 0-10V Motorised damper connects to the touchpad. The TRI 2 version is suitable for use with
MDB-XXX-IC 4Nm motorised dampers only. The motorised dampers may be connected in parallel with a
maximum of two motors per zone output.
Component Positioning
Touchpad
The Touchpad should be mounted in a central position within the air-conditioned space. Designed to be
flush mounted to a cavity wall, the touchpad can be surface mounted using a 15mm mounting block if
necessary. If using the integrated sensor see also - positioning the room sensor. Due to the microprocessor-
based design, consideration must be given to sources of EMI (Electro Magnetic Interference) when
positioning the touchpad. The minimum recommended distance from the touchpad to any 240VAC cabling
is 300mm.
Room Sensor
The integrated room sensor should be mounted approximately 1.5 meters from floor level in the return air
path. Most importantly, the room/return air sensor should always be protected from direct sources of heat
such as direct sunlight and office equipment. The integrated room sensor may be replaced with an Insight
Control room sensor (C-RS-10K-TL) if required. The supply air sensor should be mounted inside the supply
air duct upstream from the damper. There should be no electric duct heaters in this supply duct branch.
Motorised Dampers
The Motorised Dampers may be mounted at the take-off point of the rigid duct, or inline in the flexible
duct. Mechanical Stops MUST NOT be used on the Motorised Barrel Damper.
Commissioning
Check that all wiring has been terminated as per wiring instruction on the connection diagram page. Check
Motor rotation set to turn clock wise on normal operation, flick switch on top of belimo as required.
Setpoint should be set to optimal temperature setting for zone being controlled for correct operation of the
system.

Insight Control TRI2 Installation Manual
Terminals
The following table lists some commonly reported fault conditions and suggested corrective action. Further
assistance may be obtained from Insight Control support on 1300 665 831 if needed.
Symptom
Suggested remedial action
Motor drives the wrong way
Check Actuator wiring.
Motor drives one way only
Check cable ends to ensure all connections are terminated
properly. Check cable for broken wire.
Intermittent erratic controller
behaviour
Ensure the touchpad is the minimum recommended distance
from any EMI source. Relocate if necessary.
10K NTC
Supply Air
Sensor
V+ 24 VAC Supply
GND 24 VAC Neutral
1 Wire 1 from Actuator
2 Wire 2 from Actuator
3 Wire 3 from Actuator
8 10K Sensor Wire 1
GND 10K Sensor Wire 2
Vector TRI2
TFORM-24
Belimo Actuator
24V 0-10V
1 2 3

Insight Control TRI2 Installation Manual
Electrical Requirements
Power input to ZONE-IT
24 VAC ± 10%
Line frequency
50 Hz
Environmental Requirements
Operating temperature
0°C to 50°C
Altitude
0 to 2000m
Operating relative humidity
10% to 80%
Positioning
Avoid static electricity hazards
Avoid electromagnetic radiation sources
Avoid dust contamination
Avoid highly corrosive environments
Phone: 1300 665 831
Email: sales@insightcontrol.net.au
Website: www.insightcontrol.net.au
Address: D3 / 5 Grevillea Place
Brisbane Airport QLD 4008
Este manual sirve para los siguientes modelos
1
Tabla de contenidos
Manuales populares de Pantalla táctil de otras marcas

Elecro Engineering
Elecro Engineering Poolsmart Plus Instrucciones de instalación

Johnson Controls
Johnson Controls IQ4 HUB Manual de usuario

Elo TouchSystems
Elo TouchSystems ET2270L Manual de usuario

Elo TouchSystems
Elo TouchSystems ET1002L Manual de usuario

Elo TouchSystems
Elo TouchSystems 3201L Manual de usuario

Duratec
Duratec S15 Manual de usuario