Standard Specifications for VG-VL-VLG Series: Gas, #2 Oil, Gas/Oil Configuration
Burner
Model
Gas
Input
MBtu/
hr
#2 Oil
Input
US
GPH
BHP
@80%
Eff.
Furnace
Pressure
(“W.C.)
Blower
Motor
HP1
Blower
Motor
HP2
Remote
Oil Pump
Motor HP3
Standard
Gas Train
Pipe Size
(in.)
Min. Gas
Pressure
(“w.c.)
Blower Motor
Volt/PH 60 Hz.
V-13-1 1,300 9.3 31 0.4 1/2 3/4 1/2 1 8.6/9.25115/230/1
V-15-1 1,500 10.7 36 0.5 1/2 3/4 1/2 1 11.4/11.75115/230/1
V-17-1 1,700 12.1 40 0.7 1/2 3/4 1/2 1 14.3/14.75115/230/1
V-20-1 2,000 14.3 48 0.9 3/4 1 1/2 1 19.7/20.25115/230/1
V-21-1 2,100 15.0 50 1.0 3/4 1 1/2 1 21.5/22.15115/230/1
V-25-1 2,500 17.9 60 1.2 3/4 1 1/2 1 1/2 9.6/10.45115/230/1
V-30-1 3,000 21.4 71 1.4 3/4 1 1/2 2 8.7 115/230/1
V-34-1 3,400 24.3 81 1.8 3/4 1 1/2 2 10.3 115/230/1
V-35-2 3,500 25.0 83 1.9 1 1 1/2 1/2 2 8.1 115/230/1
V-40-2 4,000 28.6 95 1.2 1 1 1/2 1/2 2 10.4 115/230/1
V-42-2 4,200 30.0 100 1.3 1 1/242 1/2 2 11.5 208/230/460/3
V-45-2 4,500 32.1 107 1.4 2 2 1/2 2 10.8 208/230/460/3
V-50-2 5,000 35.7 119 1.8 2 3 3/4 2 13.6 208/230/460/3
V-54-2 5,400 38.6 129 2.1 3 3 3/4 2 19.2 208/230/460/3
V-55-2 5,500 39.3 131 2.2 3 3 3/4 2 19.7 208/230/460/3
V-60-3 6,000 42.9 143 2.7 5 - 3/4 2 17.6 208/230/460/3
V-63-3 6,300 45.0 150 1.8 5 - 3/4 2 19.4 208/230/460/3
V-70-3 7,000 50.0 167 2.2 5 - 3/4 2 1/2 15.8 208/230/460/3
V-80-3 8,000 57.1 190 2.8 5 - 1 2 1/2 15.1 208/230/460/3
V-84-3 8,400 60.0 200 3.1 7 1/2 - 1 2 1/2 15.5 460/3
V-90-3 9,000 64.3 214 3.5 7 1/2 - 1 1/2 2 1/2 17.4 460/3
V-100-3 10,000 71.4 238 2.7 10 - 1 1/2 2 1/2 20.5 460/3
V-105-3 10,500 75.0 250 2.8 10 - 1 1/2 2 1/2 44.7 460/3
V-110-3 11,000 78.6 262 3.0 10 - 1 1/2 2 1/2 48.7 460/3
V-120-4 12,000 85.7 286 3.6 15 - 1 1/2 2 1/2 34.2 460/3
V-126-4 12,600 90.0 300 4.3 15 - 1 1/2 2 49.1 460/3
V-147-4 14,700 105.0 350 4.3 15 - 1 1/2 2 2.5 PSI 460/3
V-168-4 16,800 120.0 400 1.0 15 - 1 1/2 2 3.1 PSI 460/3
Input is based on fuel BTU content, listed furnace pressure and altitude of 2,000 feet or less. If altitude >2,000 feet and <8,000
feet, derate capacity 4% per 1,000 feet over 2,000. Consult factory for higher altitudes. If furnace pressure exceeds listed value,
derate capacity 5% for every 0.5 “w.c. of pressure in excess of stated. Consult factory if derate exceeds 20%. Gas input is based
on natural gas with 1,000 BTU/cu. ft., 0.60 gravity. For total pressure at manifold, add furnace pressure. Oil input based on
140,000 BTU/gal. Consult factory for 50 Hz. applications.
1Motor ratings for gas only or gas/oil burners using a remote oil pump
2Motor ratings for oil only and gas/oil burners using a direct drive oil pump
3Remote oil pump is optional for frame size 1 and 2 but standard for frame sizes 3 and 4. All pump motors are 115/230/1
41 1/2 HP blower motor voltage is 115/230/1
5Low/High and Full Modulation minimum gas pressure
6Lower gas supply pressure configurations available for New York City requirements