4.0 Calibration
The calibration of the controller is carried out on pages accessed by pressing & holding in the RIGHT ARROW
Button for 5seconds. The first calibration page will appear. You can move through the calibration pages by
pressing the RETURN ARROW button & then the RIGHT ARROW button to move on. Continuing this process
will move you through the pages with out making any changes. If changes are made the inputted value is
recorded once the enter button has been pressed. The enter button is the return arrow located at the bottom
right corner of the facia. To get out of calibration pages press the RETURN ARROW button twice & return to
the main page.
4.1 Setting Low Pressure Shutdown
Press & hold the RIGHT ARROW button for 5seconds to enter calibration pages. Low pressure on will now be
displayed.
The Cursor will be flashing under the first digit of the LOW PRESSURE ON setting. Simply type in the
appropriate pressure you want the low pressure shutdown to operate at, example 200kPa Press 2, press 0,
press 0 & then press Return Arrow button.
Press the RIGHT ARROW Button to move onto the next Page
4.2 Setting Low Pressure Time Delay
Low pressure time delay will now be displayed.
The Cursor will be flashing under the first digit of the LOW PRESSURE TIME DELAY setting. Simply type in
the appropriate delay time you want after the low pressure set point has been reached, example 45sec Press
0, press 0, press 4, Press 5, & then press Return Arrow button.
Press the RIGHT ARROW Button to move onto the next Page
4.3 Setting High Pressure Shutdown
High pressure on will now be displayed.
The Cursor will be flashing under the first digit of the HIGH PRESSURE ON setting. Simply type in the
appropriate pressure you want the High pressure shutdown to operate at, example 800kPa Press 8, press 0,
press 0 & then press Return Arrow button.
Press the RIGHT ARROW Button to move onto the next Page
4.4 Setting High Pressure Time Delay
High pressure time delay will now be displayed.
The Cursor will be flashing under the first digit of the HIGH PRESSURE TIME DELAY setting. Simply type in
the appropriate delay time you want after the High pressure set point has been reached, example 45sec Press
0, press 0, press 4, Press 5, & then press Return Arrow button.
Press the RIGHT ARROW Button to move onto the next Page
4.5 Duty Pump Start Pressure
Duty pressure on will now be displayed.
The Cursor will be flashing under the first digit of the DUTY PRESSURE ON setting. Simply type in the
appropriate pressure you want the Pump start pressure to operate at, example 400kPa Press 4, press 0, press
0 & then press Return Arrow button.
Press the RIGHT ARROW Button to move onto the next Page
4.6 Duty Pump Off Pressure
Duty pressure off will now be displayed.
The Cursor will be flashing under the first digit of the DUTY PRESSURE OFF setting. Simply type in the
appropriate pressure you want the Pump stop pressure to operate at, example 500kPa Press 5, press 0, press
0 & then press Return Arrow button.
Press the RIGHT ARROW Button to move onto the next Page
4.7 Standby Pump Start Pressure
Duty pressure on will now be displayed.
The Cursor will be flashing under the first digit of the STANDBY PRESSURE ON setting. Simply type in the
appropriate pressure you want the Pump start pressure to operate at, example 400kPa Press 4, press 0, press
0 & then press Return Arrow button.
Press the RIGHT ARROW Button to move onto the next Page
4.8 Standby Pump Off Pressure
Duty pressure off will now be displayed.
The Cursor will be flashing under the first digit of the STANDBY PRESSURE OFF setting. Simply type in the
appropriate pressure you want the Pump stop pressure to operate at, example 500kPa Press 5, press 0, press
0 & then press Return Arrow button.
Press the RIGHT ARROW Button to move onto the next Page