Huato S400W Series Manual de usuario

User’s Guide
S400W Series Wireless Temperature and
Humidity Data Logger User Manual
S400W
E-mail: [email protected]
Talk to our sales
and shop online at
www.huato.cn

The information contained in this document is believed to be correct, but HUATO accepts no liability for any errors it contains, and reserves
the right to alter specifications without notice.
HUATO HUATO ELECTRIC CO., LTD.
Toll-Free: 0755-29977605
Customer Service: 0755-29977605
Engineering Service: 0755-29977605
Fax: +86-755-29748856
E-mail: [email protected]
Headquarters:
For Other Locations Visit www.huato.cn

Table of
Contents
Table of Contents
Section
..................................................................................................................................
Page
Section 1 Introduction .....................................................................................
1.1 Feature ................................................................................................
1.2 Applications .........................................................................................
1.3 Data Logger Model ..............................................................................
1.4 HE2400&HE2410 wireless base station appearance ..........................
1.5 S400W series wireless logger with LCD display .................................
1.6 1.6 Explanation of S400W Series LCD Symbols .................................
1.7 S400W-ND series wireless temperature and
humidity logger without LCD display ...................................................
1.8 Install the battery ..................................................................
Section 2 Software User's Guide ..............................................................
2.1 Installing the software ..........................................................................
2.2 Setting the RJ45 module of the HE2400 wireless base station ...........
2.3 ToMonitor software use .......................................................................
2.3.1 Open the running software ...............................................................
2.3.2 System Settings ...............................................................................
2.3.4 Communication settings ...................................................................
2.3.5 User Management ............................................................................
2.3.6 Partition management ......................................................................
2.3.7 Equipment management ..................................................................
2.3.8 Real-time curve button .....................................................................
2.3.9 Text display button ...........................................................................
2.3.10 Previous Area / Next Area Button ..................................................
2.3.11 Monitoring list button ......................................................................
2.4 View the exported data .......................................................................
3.1 Attention ..............................................................................................
3.2 FAQ......................................................................................................
1
1
1
2
3
4
4
5
6
6
7
7
8
9
9
10
10
12
12
13
13
13
15
15
15
5
5
Section 3 Attention .........................................................................................

S400 wireless temperature and humidity data logger is a high speed, intelligent
device developed by HUATO which combines the advantages of its relevant
devices. With built-in memory and Zigbee wireless transmission function,
it can record 8192 readings as well as remotely monitoring warehouse,
lab, refrigerator, cold storage room, etc. With its 2.4G transmission ability,
wiring is not required to build a monitoring network, reliable and easy to use.
Widely used in agricultural research, food, medicine, warehouse, cold storage,
refrigerator, machine room, chemical industry, meteorology, environmental protection,
electronics, laboratory and other applications of temperature & humidity monitoring,
typical customers include China National Museum, State Grid Corporation Archives,
Hong Kong Nanyang Tobacco, Shanghai Taste Candy, BGI Research Institute,
Jiangsu Academy of Agricultural Sciences and other well-known entities.
Section 1 Introduction
Section 1.1 - Features
Section 1.2 - Applications
(1)Zigbee to RJ45 DTU technical parameters
• Wireless/wired transmission speed: 115, 200 bps
• Maximum 64 wireless logger terminals.
• Number of supported frequency bands: 15 frequency bands
• Wireless interface: Zigbee ad hoc network, automatically find the best link to transmit data
• Built-in RJ45 interface to transmit received data to server through LAN
• Can be used as a relay/gateway at the same time
• Power supply: DC 12V
(2)Zigbee wireless data logger technical parameters
• Zigbee 2.4G
• LCD screen
• Resolution:0.1%℃/0.1%RH
• LED +buzzer alarm for exceptional data
• 2 in 1 sensor made in Switzerland
• Configurable record interval: 2s - 24h
• Transmission recovery function
• Wireless/wired transmission speed: 115, 200 bps.
• Maximum transmission range: 100-500 meters
1
Introduction
1

Section 1.3 - Data Logger Models
2
Introduction 1
Model
S400W-TH ±0.5℃/±3%RH -20~ 70℃
0~100%RH
-20~ 70℃
0~100%RH
-20~ 70℃
0~100%RH
-40~ 85℃
0~100%RH
-40~ 85℃
0~100%RH
-40~ 85℃
0~100%RH
-40~ 85℃
-40~ 85℃
-40~ 85℃
-40~ 85℃
-200~ 480℃
-40~ 120℃
0~ 20000PPM
-100~ 300℃
±0.5℃/±3%RH
±0.5℃/±3%RH
±0.5℃/±3%RH
±0.3℃/±3%RH
±0.3℃/±3%RH
±0.5℃
±0.5℃
±0.5℃
±0.5℃
±0.5℃
0~20%/±70PPM
+/-5%
±(1-2%FS)
±(1-2%FS)
S400W-EX
S400W-ET
S400W-EK
S400W-DT
S400W-EPT
S400W-DP
S400W-CO2
S400W-TH-ND
S400W-EX-ND
S400W-ET-ND
S400W-EK-ND
S430W-TH
S430W-EX
S400W-T
Sensor type Remark
Internal temperature &
humidity integrated
sensor
External temperature &
humidity integrated
sensor
Single channel external
temperature sensor
External thermocouple
temperature sensor
Dual-channel external
temperature sensor
Single-channel external
temperature sensor
External PT100 pin
sensor
Internal temperature
and humidity
integrated sensor
External temperature
and humidity
integrated sensor
Single-channel external
temperature senso
External thermocouple
temperature sensor
Internal temperature
and humidity
integrated sensor
External temperature
and humidity
integrated sensor
1.5V AA battery * 4,
9VDC, LCD dual figures
1.5V AA battery * 4,
9VDC, LCD dual figures
1.5V AA battery * 4,
9VDC, LCD dual figures
1.5V AA battery * 4,
9VDC, LCD dual figures
1.5V AA battery * 4,
9VDC, LCD dual figures
1.5V AA battery * 4,
9VDC, LCD dual figures
1.5V AA battery * 4,
9VDC, LCD dual figures
1.5V AA battery * 4,
9V DC, no LCD display
1.5V AA battery * 4,
9V DC, no LCD display
1.5V AA battery * 4,
9VDC, LCD single figures
1.5V AA battery * 4,
9VDC, LCD single figures
1.5V AA battery * 4,
9V DC, LCD single
figure, ultra-low
temperature detection
1.5V AA battery * 4,
9V DC, LCD single
figure, ultra-low
temperature detection
Measurement
Accuracy
Measurement
Range

Section 1.4 - HE2400 & HE2410 DTU appearance
Introduction
1
3
Ethernet interface (RJ45)
DC 12V DC 12V
Antenna Antenna
USB interface
12
3
12
3
HE2410HE2400

Section 1.5 - S400W series wireless logger with LCD display
Section 1.6 - Explanation of S400W Series LCD Symbols
Introduction 1
4
Battery power Temperature display area
Humidity display area
DC power
Logging
Celsius / Fahrenheit
Humidity unit
Signal quality
Wireless
LCD display area Wall mounting panel
Rear cover screw position
USB and DC power connector
LED indicator: temperature and humidity alarm, flashing light and sound alarm

Section 1.7 - S400W-ND series wireless temperature and humidity
logger without LCD display
Section 1.8 - Install the battery
5
Installation and Instruction 2
LED Indicator Wall Mounting Board
Rear cover screw positionUSB and DC power connectors
Use a screwdriver to loosen the fixing screws from the back cover, and install four 1.5V AA
batteries into the battery compartment according to the directions

Section 2 Software User's Guide
2.1 Installing the software
2.2 Setting the RJ45 module of the HE2400 wireless base station
6
Installation and Instruction
2
Plug the HE2400 into a 12V power supply, plug in the ethernet cable, open Lanconfig program in the
folder, and a pop-up interface will be shown as below:
(1) Click [Search Modules] to search for devices. The names and IP addresses of all the DTU connected to
the LAN will be displayed in the right of the window.
Note: LanConfig software uses UDP broadcast protocol for module search, please make sure that the
software is not blocked by firewall or antivirus software.
(2) Select the serial number of the found HE2400 DTU and double-click to obtain the attributes.
(3) Name: instrument name, can be modified according to actual needs. (Note: The factory setting is the
instrument’s serial number)
(4) Work Model: Set to TCP Client mode.
(5) Baud Rate: set to 115, 200
(6) DHCP Mode: select Disable to turn it off. It is recommended to choose a fixed IP address to ensure
network stability.
(1)Put the Monitor software CD into the CD-ROM drive, and install ToMonitor_V8 software to the computer
hard disk.(Note: It is recommended NOT to install it on the drive C to prevent the d losing data caused by
operating system crashing).
(2)Open the installation folder and find the ToMonitor icon.
(3)This instrument may use HE2400 or HE2410 DTU to upload data. In case of HE2410, you need to
install the driver. Find the USB_Driver directory on the CD-ROM and click the Setup.exe program.
A dialog box pops up and click the "INSTALL" button. It will take a while, to install the driver to the
computer. Driver is not needed for HE2400.

2.3 ToMonitor software guide
Installation and Instruction 2
7
Double-click the program icon and click [Login] button to enter the login interface
as below. The initial user name and password are both “admin” (case insensitive).
2.3.1 Run the software
Power on the instrument, connect the control computer to HE2400 through ethernet
or to HE2410 through USB interface.
(7) Address: IP address / Subnet mask / Gateway IP gateway, modify the IP information according to
current LAN configuration, the IP address will be assigned to HE2400 DTU (Note: This IP address
should not conflict with any IP address of other instruments)
(8) Object IP: this IP address is the fixed IP address of the control computer.
(9) Object Port: default is 4588, which should be consistent with the TCP listening port of ToMonitor software.
(10) Click [Apply Changes] to submit the changes, a " Device Information Changed Successfully " dialog
box will pop up, and finally click Confirm.
Este manual sirve para los siguientes modelos
15
Tabla de contenidos
Otros manuales de Registrador de datos de Huato

Huato
Huato S1500 Series Manual de usuario

Huato
Huato S500 Series Manual de usuario

Huato
Huato S100 Series Manual de usuario

Huato
Huato HE173 Manual de usuario

Huato
Huato HE17 Series Manual de usuario

Huato
Huato S500 Series Manual de usuario

Huato
Huato S220-T8 Series Manual de usuario

Huato
Huato S1500 Series Guía de inicio rápido

Huato
Huato S300-E Manual de usuario