Summary of installation steps:
1. Decide here to place all system components. Consult component specific HEA manuals for individual
components (J Controller, Water Meter, Manifold, Pump Heads Blend Tank).
2. Install and leak check all plumbing including the manifold supply, ater meter, injection point fittings
and blend tank.
3. Install the manifold and pump heads.
4. Mount controller and make connections bet een the controller, ater meter and manifold(s).
5. Po er on and configure J controller.
This manual covers steps 4 and 5 and assumes steps 1-3 are complete. Consult the J Series Installation
Guidelines (http:// .heanderson.com/Install-Guidelines.pdf) and individual component manuals for prior
steps.
Do all iring before connecting po er. Use a surge suppressor on the incoming AC po er line. Plug in the
po er cord and atch the LCD display. If it does not come on, unplug the po er and check the iring.
This unit as ordered ith the follo ing capacities or settings:
MODEL NO. _____________ SERIAL NO. ______________
Customer Requested _____ Default _____
Soft are Version ____________
K Factor [Pulses per Gallon]____________
Maximum Flo ____________
Pumper Models:
PUMPER #1________
PUMPER #2________
PUMPER #3________
PUMPER #4________
PUMPER #5________
PUMPER #6________
PUMPER #7________
PUMPER #8________
GPS=Gallons Per Stroke
GPS #1________
GPS #2________
GPS #3________
GPS #4________
GPS #5________
GPS #6________
GPS #7________
GPS #8________
Once settings have been properly entered into the controller, the ratios for each output can be vie ed
on the controller’s display. To manually calculate the injection ratio for each pumper use the formulas
belo . With the above settings, pumpers ill have the follo ing chemical to ater feed ratio capacities (At
dial setting 10).
BASE #1 = (GPS #1 x N) ÷ 80 = _______ N=3785(gal.)
H8 1:______ (BASE #1) H4, P4 1:______ (BASE #1 x 2)
H2, P2 1:______ (BASE #1 x 4) H1, P1, A10 1:______ (BASE #1 x 8)
A3 1:______ (BASE #1 x 26.7)
BASE #2 = (GPS #2 x N) ÷ 80 = _______
H8 1:______ (BASE #1) H4, P4 1:______ (BASE #1 x 2)
H2, P2 1:______ (BASE #1 x 4) H1, P1, A10 1:______ (BASE #1 x 8)
A3 1:______ (BASE #1 x 26.7)
BASE #3 = (GPS #3 x N) ÷ 80 = _______
H8 1:______ (BASE #1) H4, P4 1:______ (BASE #1 x 2)
H2, P2 1:______ (BASE #1 x 4) H1, P1, A10 1:______ (BASE #1 x 8)
A3 1:______ (BASE #1 x 26.7)
BASE #4 = (GPS #4 x N) ÷ 80 = _______
H8 1:______ (BASE #1) H4, P4 1:______ (BASE #1 x 2)
H2, P2 1:______ (BASE #1 x 4) H1, P1, A10 1:______ (BASE #1 x 8)
A3 1:______ (BASE #1 x 26.7)
If more than one pumper is used to pump the same chemical, divide the ratio (BASE) by the number
of pumpers used for that chemical. The J+ Advanced can operate up to 8 manifolds. Repeat the above
formulas for BASE #5,6,7 and 8 if in use.