GridSense Powermonic PM35 Manual de usuario

Configuring PowerMonic
Remote Communications
30 July 2012

Configuring PowerMonic Remote Communications page 1
Contents
1.0Introduction ...................................................................................................................... 2
2.0Step 1: Software Upgrade................................................................................................ 2
3.0Step 2: Update USB Driver............................................................................................... 2
4.0Step 3: Update Firmware.................................................................................................. 4
5.0Step 4: Establish Remote Communication in PowerView ................................................ 6
6.0Step 5: Establish Ethernet Connection............................................................................. 7
7.0Step 6: Upgrade Comms Module................................................................................... 10
8.0Step 7: Validate Comms Module.................................................................................... 11
9.0Step 8: 3G Setup............................................................................................................ 12
10.0Technical Support.................................................................................................... 12

Configuring PowerMonic Remote Communications page 2
1.0 Introduction
Remote Configuration is applicable for PowerMonic 35 and 45. It enables users
to remotely access PowerMonic data. Thus, saving time, money and manpower
while speeding up data analysis via PowerMonic Software.
Please note the remote communication configuration kit will come with the
following:
Network cable
Cross – over Ethernet cable
PowerView release 4.6.3.
2.0 Step 1: Software Upgrade
Uninstall old version PowerView if PowerView is installed on PC and install
PowerView 4.6.3. The new release is bundled with PowerMonic Firmware loader
and the PM Sync software. Please refer to the PM Sync Technical Manual for
PM Sync user instructions.
Please access Gridsense website to download Power view 4.6.3.
The user will need additional files, download the following folders to PC
Desktop:
PV4setup_4_6_3.zip
Firmware file
Utilities file
Manuals
Download all relevant files to the user’s preferred location.
3.0 Step 2: Update USB Driver
Connect the PowerMonic to PC via USB cable and disconnect the AC Power
from PowerMonic. Upgrade PowerMonic USB Driver is old PowerMonic USB
Driver is installed. Installation steps will depend on the user’s operating system:

Configuring PowerMonic Remote Communications page 3
a) Windows 7
Right click on My Computer and click on Properties. Click on the
Hardware tab and click on Device Manager. Expand Other Device
selection and right click on PowerMonic (Note: It may appear as Unknown
Device for some users). Select Update Driver and follow the instruction as
guided by the Hardware Wizard. It is recommended that users select the
option to Search Automatically. Should you select Browse, the file will
automatically point to the driver location. The driver file is located in
C:\Program Files\GridSense\PowerMonic\Drivers
Figure 1: Update USB driver
b) Windows XP
The driver is automatically updated when PowerView version 4.6.3 is
installed.

Configuring PowerMonic Remote Communications
page 4
4.0 Step 3: Update Firmware
Please ensure all other PowerMonic application is closed prior to updating the
firmware. Launch the Firmware Loader application by clicking on the desktop
shortcut or through Start →Gridsense →PowerMonic →Firmware Loader.
A prompt window will pop-up requiring the user to close all other PowerMonic
application. Please close any PowerMonic software and click ok. PowerMonic
Firmware Loader Tool 2.2.2.0 window will appear.
Under the heading Connection, click on Open USB. The user will now be able
to click File Selection under the heading Firmware Selection.
Select firmware revision from save file on Desktop PC
For PM35: Select from Firmware File →PM35_v453_hw3.PX2
For PM45: Select from Firmware File →PM45_v453_hw3.PX2
Figure 2: Firmware loader
Details for the Installed PowerMonic Firmware version and Selected file
Firmware version will appear. If the both the installed and selected firmware

Configuring PowerMonic Remote Communications
page 5
match to version 4.6.3, the user has a version applicable for remote
communication. Close the Firmware Loader and progress to step 4. However, if
the files are not equal, click on Start under Firmware Upgrade. Firmware
upgrade will commence, users can view the progress under the progress and
status bar.
Figure 3: Firmware loader progress bar
Once the upgrade process is complete, PowerMonic will restart and dialog box
Firmware Loader 2 will pop-up. Please follow the instruction as requested. Re-
click on Open USB and Installed Version. The status should now say USB
Connection Success as shown in Figure 4.

Configuring PowerMonic Remote Communications
page 6
Figure 4: Firmware upload completed
Exit the Firmware loader program and progress to Step 4.
5.0 Step 4: Establish Remote Communication in PowerView
Launch Power View 4.6.2 and click Connect to PowerMonic. Select Direct
Cable Connection when the PowerMonic Connection Mode window
launches. The PowerMonic Operation window will appear, click on the
Comms Module Config tab and click on Default. The Ethernet and 3G details
will establish automatically. See Figure 5 below.

Configuring PowerMonic Remote Communications
page 7
Figure 5: PowerView comms module config
Disconnect USB cable to PowerMonic and remove the Sierra 3G modem if it
has been installed on CommsModule. Please note that the default static IP
address for the Comms Module is 10.10.20.100.
6.0 Step 5: Establish Ethernet Connection
Please note that step 5 is necessary for remote communication setup prior to
establishing the 3G connection and it only has to be performed once. Make the
physical connection between the network cable to the Comms Module PCB. To
do so, the user has to disassemble the PowerMonic top plate prior to
connecting the network cable. Instructions are as follows:

Configuring PowerMonic Remote Communications
page 8
a) Remove the top plate by unscrewing the 4 screws as indicated
a) The user is now ready to install the network cable. Align the darker edge of
the cable ribbon to the white dot imprinted on the PCB board.
Figure 7: Installing Network Cable
Figure 6: Disassemble top plate

Configuring PowerMonic Remote Communications page 9
Next, connect the cross-over Ethernet cable from the CommsModule to users’ PC.
Windows XP
To establish the Ethernet connection to Comms Module, click on Start Control
→Panel Network →Connection. Right click on Local Area Connection and
select Properties. Select Internet Protocol (TCP/IP) and click on Properties.
Under the General tab, select the option Use the Following Address and change
PC’s IP address to 10.10.20.123 and Subnet Mask to 255.255.0.0. The user
must have administrative rights to modify or establish network connection.
Windows 7
To establish the Ethernet connection to Comms Module, click Start →Control
Panel →Network and Sharing Center →Local Area Connection →
Properties →Select Internet Protocol Version 4 (TCP/IPv4) →Click Use the
following IP address. Use the following address: IP address 10.10.20.123 and
Subnet Mask 255.255.0.0. The user must have administrative rights to modify
or establish network connection.
Figure 8: Establishing Ethernet connection
Este manual sirve para los siguientes modelos
1
Tabla de contenidos
Manuales populares de Sistema de conferencias de otras marcas

Kramer
Kramer VIA GO Manual de usuario

AVT
AVT MAGIC AC1 Go Manual de usuario

ProSoft Technology
ProSoft Technology AN-X4-AB-DHRIO Manual de usuario

Sony
Sony PCS-I150 Manual de usuario

Middle Atlantic Products
Middle Atlantic Products VTC Series Manual de usuario

Prentke Romich Company
Prentke Romich Company Vanguard Plus Guía