Installation Instructions 810375-03
Operating Terminal and Display Unit URB 1
URB 1

2
Contents
Usage for the intended purpose ......................................................................................8
Safety note ......................................................................................................................8
Explanatory Notes
Scope of supply ..............................................................................................................8
System description ......................................................................................................8, 9
Function ..........................................................................................................................9
Technical data ...............................................................................................................10
Wiring
Wiring diagram ........................................................................................................ 4, 12
Basic Settings
CAN bus ...................................................................................................................... 13
Node ID for GESTRA bus-based devices URB 1 ....................................................... 13
Factory set default values ............................................................................................ 13
Adjusting display brightness ................................................................................. 14, 15
Changing factory set node ID of URB 1 / adjusting & changing node ID of URB 1 . 16–18
Possibilities to display bus devices ............................................................................. 18
Setting / changing node IDs of bus-based equipment.......................................... 19–22
Visual display / parameterisation of bus-based equipment ................................. 23–28
0 %/100 % calibration for capacitance level monitoring system .......................... 29–31
Calibrating feedback potentiometer of an external control valve ......................... 32–35
Establishing switchpoints and proportional coefficient XP.................................... 36–39
Adjusting sensitivity of response ........................................................................... 40, 41
Setting relay delay times ....................................................................................... 42–44
Adjusting conductivity controller ........................................................................... 45–57
Adjusting LIN (linear) temperature compensation ................................................ 58–60
Adjusting NORM (standard curve) temperature compensation ........................... 61–65
Enabling AUTO temperature compensation ............................................................ 66, 67
Disabling temperature compensation ................................................................... 68, 69
Installation
URB 1 ...........................................................................................................................10
Example of installation ................................................................................................ 79
Important Notes
Page

3
Manual operation via external control valve ............................................................... 70
Stand-by operation with the steam boiler disconnected............................................. 71
Operation
Contents
Page
Systematic malfunction analysis for troubleshooting .................................................. 72
Fault finding list ...................................................................................................... 73, 74
System Malfunctions
Establishing / changing node ID ................................................................................. 75
Factory set node IDs .............................................................................................. 75, 76
Table: standard curves ................................................................................................ 77
Declaration of conformity............................................................................................. 78
Annex

4
Wiring Diagram
Fig. 2
Fig.1 Terminating resistor 120 Ω,
Paired cable
*) CEP = central earthable point
Operating
terminal
URB 1
Conductivity
controller
LRR 1-40
Conductivity
electrode
LRG 16-40
Terminating resistor
120 Ω
Voltage supply CAN data line
Terminating resistor
120 Ω
Electrode
NRG . . .
Level switch
NRS
CEP*)

5
Functional Elements
Fig. 3 1 2 3 4 5
6

6
Functional Elements
Fig. 4
A
B
A
7

7
Program button for switching between operating mode and parameterisation mode
Increase button
Decrease button
Enter button
Manual / automatic button
Illuminated LCD display, resolution 128 x 64 pixels
Code switch for baud rate setting
Fixing screws for panel mounting
Five-pole connector
Key
6
5
4
3
2
1
7
A
B

8
The URB 1 is a user-friendly operating terminal and display unit for GESTRA CAN
bus systems using the CANopen protocol.The equipment makes retrieving and
processing standard functions of associated system components very easy.
In addition, the URB 1 simplifies the parameterisation procedure: The switchpoints,
proportional band and response sensitivity can be adjusted by means of the keypad
regardless of the actual level. The energizing and de-energizing times of the relays
can be set individually for their respective switchpoints.
The following tables specifiy the GESTRA systems that can be displayed by the
URB 1.
Important Notes
Safety Note
Use operating terminal and display unit URB 1 only for operating and viewing
GESTRA CAN bus systems.
The equipment must only be installed by qualified staff.
Qualified staff are those persons who – through adequate training in electrical
engineering, the use and application of safety equipment in accordance with
regulations concerning electrical safety systems, and first aid & accident prevention –
have achieved a recognised level of competence appropriate to the installation and
commissioning of this device.
Usage for the intended purpose
Use operating terminal & display unit URB 1 only in conjunction with GESTRA
Spector bus systems (CANopen).
Explanatory Notes
Scope of supply
URB 1
1 Operating terminal and display unit URB 1 (in plastic case)
2 Fixing screws for panel mounting
1 Installation manual
System description

9
Function
Explanatory Notes – continued –
System description – continued –
The URB 1 communicates with other GESTRA system components via a designated
CAN bus using the CANopen protocol to DIN ISO 11898.
The URB 1 can also be used to operate and display further system components
during operation.
■Capacitance level switch type NRS 2-40 CANopen
■Level controller type NRR 2-40 CANopen
■Conductivity level switch type NRS 1-42 CANopen
■Low-level alarm to TRD 604/EN type NRS 1-40 CANopen
■High-level alarm to TRD 604/EN type NRS 1-41 CANopen
■Conductivity controller and limiter to TRD 604/EN type NRS 1-41 CANopen
Standard display information
Level Conductivity
NRS 1-40 NRS 1-41 NRS 1-42
NRS 2-40 NRR 2-40
LRR 1-40
Actual value (bar chart) ●● ●
Actual value (numerical value) ●● ●
Switchpoint (symbol) ●●● ●
High level alarm (electrode HW) ●●● ●
Low level alarm (electrode LW) ●●● ●
Manual/automatic operation ●● ●
Stand-by mode ●
Unit [µS/cm] or [ppm] ●
Low level limit ●
High level limit ●
Alarm (warning triangle) ●●
Further display information Level Conductivity
NRS 1-40 NRS 1-41 NRS 1-42
NRS 2-40 NRR 2-40
LRR 1-40
Actual value (continuous) ●● ●
Switchpoints ●●● ●
Setpoint ●●
Deviation ●●
Valve position ●●
Intermittent blowdown ●
Intermittent blowdown interval ●
Purging pulse 24 h ●
Current CAN bus addresses ●●●●● ●

10
Technical data
Type approval no.
TÜV · 98-399 (level)
TÜV · WÜL · 02-007 (conductivity)
Input
Power supply: 18 V – 36 V DC
Interface for CAN bus using CANopen protocol to DIN ISO 11898
Output
Interface for CAN bus using CANopen protocol to DIN ISO 11898
Indicators and adjustors
1 illuminated display, resolution: 128 x 64 pixels
5 push buttons
1 three-pole code switch for baud rate setting
Supply voltage
18 V – 36 V DC
Protection
Front panel: IP 54 to DIN EN 60529
Back: IP 00 to DIN EN 60529
Admissible ambient temperature
0°C – 55 °C
Case material
Front face: Aluminium with polyester membrane
Casing: Noryl GFN 2 SE 1, glass-fibre reinforced
Weight
Approx. 0.3 kg
Installation
URB 1
Tool
Panel mounting
1. Provide panel cut-out, dimensions: 92+0.8 x 92+0.8.
2. Install URB 1 using the fixing clips supplied with the equipment.
■Screwdriver (5.5/100)
Explanatory Notes – continued –