Dorgard Pro is a fire door retainer which holds open fire doors legally,
allowing them to automatically close when a fire alarm is activated.
Dorgard Pro can be acoustically activated or connected to a Transmitter using secure wireless
technology. The radio Transmitter can be directly wired to volt free contacts of a fire alarm relay or
triggered acoustically, processing the sound of the fire alarm and sending a radio signal to Dorgard Pro
allowing them to release the doors.
Part Number Part Name
218-8662 Dorgard Pro Site Survey and Demo Case
360-1551 Dorgard Pro Black
956-8278 Dorgard Pro White
885-3205 Fireco Transmitter
966-2075 Fireco Repeater
System
overview
System
overview

• Overall Height: 205mm
• Casing Height: 150mm
• Width: 195mm
• Depth: 45mm
• Weight: 700g
150mm
205mm
195mm
Dorgard Pro
Page 2
Dorgard Pro is a self contained fire door hold open device which is able to retain a fire
door, at any angle of opening.
Dorgard Pro
Power Two x LR14 C Size batteries
Battery life Five years when radio connected, three years in acoustic
mode
Triggers Fireco Transmitter 885-3205 or acoustically
Radio frequency 433.050 MHz to 434.790 MHz
Applicable door size Up to EN7 160Kg, 1600mm
Fire rating Suitable for timber/composite doorsets up to 120 minutes and
steel doorsets of 240 minutes
Compliant to
EN1155, EN1634, EMC Directive, Radio Equipment Directive,
Critical (Cat A) BS7273-4, when hard wired to a critical
(cat A) system
Radio
Fire
Power
Alert
FR120M
System
overview

Page 3
The Fireco Transmitter is a radio control unit for the Dorgard Pro system. Connecting to
a fire alarm relay or listening to the sound of your fire alarm, it controls and monitors
the system.
Fireco Transmitter
Power 8-30V AC or DC
Battery back-up Two x LR14 C-size batteries, capable of operating system
for 7 days
Triggers Volt free NC/NO/COM or Acoustic
Radio Frequency 433.050 MHz to 434.790 MHz
Range Typically 40-50m
Maximum System Capacity 50 Repeaters and 500 Dorgard Pro
Compliant to EN1155, EMC Directive, Radio Equipment Directive
Operating Temperatures -5 to +70C
• Casing Height: 180mm
• Width: 180mm
• Depth: 48.5mm
• Weight: 532g
180mm !
180mm
!
Radio
Fire
Power
Alert
System
overview

Page 4
System
overview
The Fireco Repeater extends the radio range from the Fireco Transmitter allowing you to
connect more units over a greater distance. Up to 50 Fireco Repeaters may be used in
any installation.
Fireco Repeater
Power 8-30V AC or DC
Battery back-up Two x LR14 C-size batteries, capable of operating system
for 7 days
Triggers Fireco Transmitter
Radio Frequency 433.050 MHz to 434.790 MHz
Range Typically 40-50m
Maximum System Capacity 8 Repeaters and 120 Dorgard Pro
Compliant to EN1155, EMC Directive, Radio Equipment Directive
Operating Temperatures -5 to +70C
• Casing Height: 180mm
• Width: 180mm
• Depth: 48.5mm
• Weight: 532g
!
180mm
180mm
!
Radio
Fire
Power
Alert

1. Switch your Dorgard Pro Demo & Site Survey
Transmitter into survey mode by flicking the switch
on the base of the Survey Transmitter to the right.
2. Press down the plunger on your Demo
Dorgard Pro. This will sync the two units and
enable you to survey a building.
!
3. Place the Survey Transmitter where you are
proposing to install the Fireco Transmitter. This should
be within 2 metres of the fire alarm relay if you are
planning on directly connecting the Transmitter.
If proposing an acoustically activated Transmitter,
place the Survey Transmitter where it is able to hear
the sound of the fire alarm above the background
noise. Do not site Transmitters within 1 metre of power
sources or metal surfaces (including Georgian
wire glass).
https://goo.gl/CMxYW8
Dorgard Pro
!Dorgard Pro
!
1
Page 5
Surveying a
building prior to
installation
Survey

7. Assess a position for the required Fireco Repeater
to be installed, i.e. not within 1 metre of a power source
or metal surface (including Georgian wire-glass).
8. Move your Fireco Survey Transmitter to this new
position and repeat the first steps of the survey until you
have a positive radio range reading at each door you
require to be held open with Dorgard Pro.
Repeat this process for all of the doors you wish to cover. If at
a door position the Dorgard Pro gives a red LED indicating it is
no longer in range of the Survey Transmitter, the installation will
require a Fireco Repeater to be located at the end of the range.
4. Place the Survey Dorgard Pro at the position a
Dorgard Pro is to be fitted. Ensure you hold it at
the bottom of the fire door with the rubber foot
touching the floor. Press the plunger down to get a
radio reading. If the Dorgard Pro is in range of the
Survey Transmitter the top LED of the Dorgard Pro
will flash green for 4 seconds. If the Survey Dorgard
Pro is no longer in range it will flash the top LED
red for 4 seconds.
6. To identify a suitable location for the new Repeater bring
the Survey Dorgard Pro closer to the Survey Transmitter
until you are again in range (confirmed by getting a green
light on the top LED of the Survey Dorgard Pro after you
press the plunger down).
!Dorgard Pro
!Dorgard Pro
!Dorgard Pro
!Dorgard Pro
!Dorgard Pro
!Dorgard Pro
!Dorgard Pro
Dorgard Pro
!
!Dorgard Pro
Dorgard Pro
!
!Do
Page 6
Survey

Option 3. Connect to another source such as the
auxiliary power from the fire panel. The power
supply must be between 8v and 30v (AC or DC).
Connect the green two way terminal block into the
two way green connector located at the base of the
Transmitter or Repeater.
The Transmitter or Repeater will beep twice and
the power LED on the label will show a green
light to say it has been successfully powered. The
Transmitter will carry out its channel scan indicated
by a flashing amber radio LED.
Power
Dorgard Pro
Dorgard Pro is supplied with two C-size batteries. To replace the batteries,
unscrew the battery compartment on the top face of Dorgard Pro using
an PZ2 screwdriver. Lift the battery shaft out and insert two new batteries
positive up.
Transmitter & Repeater
Provided
• EZ6016 24V 1A DC Power Supply with 2-way terminal block
• EC7922 Power cable C7 with stripped ends
• EC5217 UK plug adaptor
• EC2083 EU Plug adaptor
• EC0000 AU Plug adaptor
The Transmitter and Repeater require 8-30V AC or DC.
Connecting to power
https://goo.gl/XQyoHw
Page 7
Installation
Option 1. Using the supplied power supply EZ6016
connect either the UK, EU or AU plug adaptor by slotting
one into the fixing point.
Option 2. Fit the C7 power cable EC7922 into the Power
Supply EZ6016 at the base of the unit and connect to a
non-switched fused 1A spur.
8-30V ac/dc
https://goo.gl/V2HjZd

The Transmitter is factory set to be triggered
acoustically by the sound of the fire alarm. The
resistor factory fitting across the green three way
terminal block denotes the Transmitter is in Acoustic
Mode.
Remove green three way terminal block from the base of
the Transmitter.
Remove resistor from the green three way terminal block.
Wire the COM NC NO from the volt free contacts of the
fire alarm relay into the green three way terminal block.
Connect the green three way terminal block into the
corresponding green three way connector on the base of
the Transmitter.
Connecting
Transmitter to fire
alarm CIE relay
C NO NC
FIRE ALARM
C NO NC
https://goo.gl/vL546L
https://goo.gl/RmafKZ
Page 8
Installation
Setting up an
acoustically-activated
Transmitter