B
D
CE
AcƟvate the Netbiter
ConnecƟons
Local ConfiguraƟon Technical Data
EC310/EC350
INSTALLATION GUIDE
Local ConfiguraƟon via USB
Connect a USB Micro B cable between a computer and the USB port on the
Netbiter. The USB device driver will create a virtual network interface on the
computer, with an IP address in the range 169.254.200.xxx.
Accessing the local configuraƟon
Enter the IP address 169.254.200.200 in a web browser.
The default username for the local configuraƟon pages is admin.
The password is the AcƟvaƟon Code supplied with the unit.
The Netbiter must be acƟvated to be able to communicate with Netbiter Argos.
This requires the System ID and AcƟvaƟon Code, both of which are provided on a
printed sheet included with the Netbiter.
To open a new account on Netbiter Argos:
1. Go to
www.netbiter.net and click on Create an account.
2. Follow the instrucƟons and log in to the new account.
3. Select the primary use for the unit and click on AcƟvate.
To use an exisƟng Netbiter Argos account:
1. Go to www.netbiter.net and log in to your Argos account.
2. Open the menu Management >> All Systems >> Add system.
Refer to the online help in Argos if needed (see below).
Requirements for Mobile CommunicaƟon
If the SIM card is not a Netbiter SIM card the following informaƟon is needed:
• The phone number for the SIM card
• The access point name (APN)
• The username and password (if required by the operator)
The informaƟon can be entered in two ways:
• In the local configuraƟon pages under Modem seƫngs (see secƟon C)
• In Netbiter Argos on the Mobile network configuraƟon page
The PIN code for the SIM card must be disabled.
Online Help
The help system in Netbiter Argos can be accessed by clicking on the icon in the
top right corner of the web page.
HMS Industrial Networks AB
Box 4126
300 04 Halmstad
Sweden
Phone +46 (0)35 - 17 29 00
Fax +46 (0)35 - 17 29 09
Web www.hms-networks.com
Support www.netbiter.com/support
©2016 HMS Industrial Networks - All rights reserved
HMS reserves the right to make modificaƟons without prior noƟce.
For a Netbiter SIM card the APN seƫngs are pre-configured on
Netbiter Argos and the PIN code is disabled upon delivery.
Package Contents DescripƟon
Netbiter EC310 or EC350
Connectors Connectors for I/O, RS-232 and RS-485 teminals
System ID/AcƟvaƟon code Printed document with installaƟon credenƟals
InstallaƟon Guide This document
Stub antenna NB1005 only
DIN Rail MounƟng Kit NB1005 and NB1007 only
Once the Netbiter is online at Netbiter Argos, check
that the unit is running the latest firmware.
SP1829 3.10 2016-10-03
Field wiring terminals must be connected with minimum wire size 24 AWG
Power Connector
SIM Card Slot (EC350 only)
I/O Terminal Block RS-232RS-485
GPS antenna connector
(EC350 only)
WAN
Pin DescripƟon
Rx Rx Recieve Input RS-232
Tx Tx Transmit Output RS-232
GND Signal ground
Pin DescripƟon
A RS-485 Line A (+)
B RS-485 Line B (-)
COM ISO GND (Isolated ground)
Micro USB
Connector ProtecƟve Earth
(for Ethernet ports)
Pin Label DescripƟon
1 Relay NO Relay Output, NO, Isolated
2 Relay COM Relay Output, COM, Isolated
3 DI1+ Digital input 1 current source
4 DI1- Digital input 1
5 DI2+ Digital input 2 current source
6 DI2- Digital input 2
7 Analog In AI1 Analog Input 1
8 Analog In AI2 Analog Input 2
9 Analog In AI3 Analog Input 3
10 Analog In AI4 Analog Input 4
11 Analog IN COM Analog Ground
I/O Terminal Block
Order Code
EC310: NB1007
EC350: NB1005
EC350 (no antenna): NB1008
Mobile communicaƟon (EC350 only)
5-band 3G/UMTS (WCDMA/FDD):
800/850, 900, 1900, 2100 MHz
Quad-band GSM/GPRS:
850, 900, 1800, 1900 MHz
1 Relay Output
2 Digital Inputs (dry contact type)
4 Analog Inputs
V, mA (all 4 inputs)
Pt100 (2 inputs)
Serial Port #1
RS-232 (Tx, Rx, GND)
Serial Port #2
RS-485
Antenna Connector Mobile (EC350 only)
SMA female
Antenna Connector GPS (EC350 only)
SMA female (acƟve or passive antenna)
USB Interface
Micro USB, USB 2.0
Protocols
Modbus RTU
MounƟng
DIN rail (EN 50022)
Wall mounƟng
Dimensions (H x W x D)
25.6 x 135 x 92 mm
Temperature
OperaƟng: -40 °C to +65 °C
Storage: -45 °C to +85 °C
Humidity range
5–95 % RH, non-condensing
Input Voltage
12–48 VDC
Recommended Power Supply
24 VDC, 25 W, LPS
Power ConsumpƟon, typical
EC310: 2.5 W
EC350: 4.5 W
CerƟficaƟons
EC310: CE, CULUS
EC350: CE, CULUS, FCC, IC, PTCRB
Contains FCC ID: QIPPHS8-P
Contains IC ID: 7380A-PHS8P