Technical Specifications
Thank you for choosing ENDA ET1412 temperature controller.
Please read this document carefully before using this product. The guarantee will be
invalidated if the device is damaged by not following instructions detailed in the
manual. The company shall not be responsible for any damage or losses however
caused, which may be experienced as a result of the installation or use of this product.
Connection Diagram
ENDA ET1412 is intended for installation in control panels. Make sure that the device is used
only for intended purpose. The electrical connections must be carried out by a qualified staff
and must be according to the relevant locally applicable regulations. During an installation, all of
the cables that are connected to the device must be free of electrical power. The device must be
protected against inadmissible humidity, vibrations, severe soiling and make sure that the
operation temperature is not exceeded. The cables should not be close to the power cables or
components.
1/2
SÝSEL MÜHENDÝSLÝK ELEKTRONÝK SAN. VE TÝC. A.Þ.
Yukarý Dudullu Barbaros Cad. Kutup Sok. No:20 34775 - ÜMRANÝYE/ÝSTANBUL/TÜRKÝYE
Tel : +90 216 499 46 64 Pbx. Fax : +90 216 365 74 01
url : www.enda.com.tr
Panel cut-out
Dimensions
Note :
1) Panel thickness
should be maximum
7 mm.
2) If there is no 60mm
free space at the back
side of the device, it
ET1412-E-07
71mm
29mm
Flush mounting
clamp
For removing mounting clamps:
Push the flush-mounting
clamp in direction 1as shown
in the figure below. Then, pull
out the clamp in direction 2.
1
ENDA ET1412 DIGITAL THERMOSTAT
* 35x 77mm sized.
* On-Off control.
* Contact output for alarm.
* Single contact output for selectable heating
or cooling control.
* Single NTC probe input..
* Offset value can be entered for NTC probe.
* In the case of probe failure, output state can be
selected on, off or periodical running.
* Upper and lower limits of the set point can be
adjusted.
* Selectable independent, deviation or band alarm.
* Temperature unit can be selected °C or °F.
* CE marked according to European Norms.
Order Code : ET1412-NTC- 1
230VAC.......230V AC
24................24V AC/DC
12................12V AC/DC
Supply Voltage
OUTPUTS
Output
Alarm
Life expectancy for relay
Relay: 250V AC, 8A (for resistive load), NO+NC;
1/2 HP 240V AC CosF= 0.4 (for inductive load)
1/2 HP 240V AC CosF= 0.4 (for inductive load)
Relay: 250V AC, 8A (for resistive load), NO+NC;
Mechanical 30.000.000; Electrical 100.000 operation.
Holding screw
0.4-0.5Nm.
Equipment is protected throughout
by DOUBLE INSULATION
7
8
SUPPLY:
NOTE:
184-253V AC
50/60Hz 3VA
Line
Neutral
230V AC
Supply
Switch
Note:
Cable size: 1,5mm²
Fuse
F 100 mA
250V AC
Fuse should
be connected
1) Mains supply cords shall meet the requirements of
IEC 60227 or IEC 60245.
2) In accordance with the safety regulations, the power
supply switch shall bring the identification of the
relevant instrument and it should be easily
accessible by the operator.
ENVIRONMENTAL CONDITIONS
Height Maximum 2000m
80%, up to 31°C decreasing linearly 50% at 40°C
Ambient/storage temperature
Max. relative humidity
0 ... +50°C/-25 ... +70°C (with no icing)
Rated pollution degree According to EN 60529 Front panel : Ip65
Rare panel : IP20
Do not use the device in locations subject to corrosive and flammable gasses.
Supply voltage 230V AC +10% -20%, 50/60Hz or 12/24V AC/DC ±10%, 50/60Hz.
Power consumption Max. 3VA
2.5mm² screw-terminal connections.
(±1%-1sec)
4 digits, 12.5mm, 7 segment yellow LED
Wiring
Scale
Sensitivity/Accuracy
Time Accuracy
Indicator
EMC
Safety requirements
The device is designed to operate in controlled electromagnetic environment)
EN 61326-1: 1997, A1: 1998, A2: 2001 (Performance criterion B is satisfied for EMC tests.
EN 61010-1: 2001 (Pollution degree 2, overvoltage category II)
ELECTRICAL CHARACTERISTICS
-60.0 ... +150.0°C (-76.0 ... +302.0°F)
0.1°C / ±1°C
CONTROL
Control type Single-setpoint control
On-Off control
Control algorithm
Hysteresis Adjustable between 0.1 ... 20.0°C.
HOUSING
Housing type Suitable for flush-panel mounting.
Dimensions W77xH35xD71mm
Weight Approx. 215g (A )fter packing
Enclosure material Self extinguishing plastics
While cleaning the device, solvents (thinner, benzine, acid etc.) or corrosive materials must not be used.
Flush mounting
clamp
Depth
Panel
2
71mm 5mm
SET
SET
ENDA
OUT
°F
°C
ALR
ET1412
77mm
35mm
SET
SET
ENDA
OUT
°F
°C
ALR
ET1412
Rubber
packing
SN: XXXXXXXXX
1 2 3 4 5 6 7 8 9 10 11 12
ET1412-NTC-230VAC
DIGITAL THERMOSTAT
ENDA INDUSTRIALELECTRONICS
230V AC +10% -20%
50/60Hz 3VA
OUTPUT
250V AC 8A
RESISTIVE LOAD
NTC
SENSOR
SN: XXXXXXXXX
1 2 3 4 5 6 7 8 9 10 11 12
ET1412-NTC-230VAC
DIGITAL THERMOSTAT
ENDA INDUSTRIAL ELECTRONICS
230V AC +10% -20%
50/60Hz 3VA
OUTPUT
250V AC 8A
RESISTIVE LOAD
NTC
SENSOR
ALARM
250V AC 8A
RESISTIVE LOAD