E-Mon Class 3200 Manual de usuario

62-0390-02
INSTALLATION INSTRUCTIONS
Class 3200 Meter
ADVANCED KWH/DEMAND METER
Test Equipment Depot - 800.517.8431 - 99 Washington Street Melrose, MA 02176
TestEquipmentDepot.com

CLASS 3200 METER
62-0390-02 2
Dear Valued Customer,
We are pleased that you chose to buy one of our products, and want you to be just as
pleased with owning it. Before installing your new E-Mon product, please read the
information on the following pages carefully.
We believe that you will find the E-Mon D-Mon meters easy to install and to use for
monitoring and evaluating your electrical usage.
To be sure that you are 100% satisfied with your products, we provide toll-free
technical and sales support Monday through Friday, 8:00 am to 7:30 pm, EST:
If you have questions, we can handle them quickly and effectively with a telephone call.
Please let us try to help you BEFORE you remove your meter. And to help us help you,
we ask that you have all relevant information on hand when you call (model or part
numbers, nature of difficulty, etc.)
Be sure to forward this manual to the owner after installation is complete, so that they
may use it as a reference guide when reading the E-Mon D-Mon meter.
Thank you.

CLASS 3200 METER
3 62-0390-02
TABLE OF CONTENTS
Section 1.0 Introduction 4
Section 2.0 Internal Electronic Assemblies 6
Section 2.1 Main Power Board 6
Section 2.2 Display Board 7
Section 3.0 Meter Technical Specifications 8
Section 4.0 Safety Label Definitions and Information 10
Section 5.0 Precautionary and Safety Information 11
Section 6.0 Meter Installation 12
Section 6.1 Mounting the Class 3200 Meter 12
Section 6.2 Main Power Board Connections 12
Section 6.3 Phasing of Line Voltage 15
Section 6.4 Current Sensor Installation & Wiring 16
Section 6.5 Main Power & Current Sensor Wiring Diagram 18
Section 6.6 Line Voltage/Current Sensor Diagnostics 18
Section 6.7 RS-485 Wiring 19
Section 6.8 RS-232 Communications 22
Section 6.9 Modem Wiring 24
Section 6.10 Modbus RTU Wiring 27
Section 6.11 BACnet MS/TP Wiring 28
Section 6.12 Connecting Class 3200 Meters to USB Key using RS485 28
Section 6.13 Ethernet Communications 29
Section 7.0 Multiple-Load Monitoring 30
Section 8.0 Preventative/Scheduled Maintenance 31
Section 9.0 Lithium Battery Replacement 32
Section 10.0 Class 3200 Meter Operating Modes 34
Section 10.1 Start Up Screens 34
Section 10.2 Normal Mode Display Screens 35
Section 10.3 How to Program the Display Screens 36
Section 11.0 High Voltage Metering 41
Section 12.0 Class 3200 Protocol Definitions 45
Section 13.0 Meter Limited Warranty 51

CLASS 3200 METER
62-0390-02 4
1.0 INTRODUCTION
The E-Mon D-Mon® Class 3200 meter is a 3-element meter with communications. The
device is used to monitor electric power usage of individual loads after the utility meter
and store kW and kVAR data for automatic meter reading. Installation must only be
performed by qualified personnel and in accordance with these instructions and all
applicable local and national electrical codes. E-Mon and its representatives assume
no responsibility for damages or injury resulting from the improper installation of this
meter.
Verify the input voltage rating and configuration on the unit panel label to ensure that it
is suitable for the intended electrical service. Class 3200 meters labeled for 120/208V
service MUST NOT be installed on service feeds of 277/480 volts or 347/600 and vice
versa.
Verify that the Class 3200 meter’s current sensors are sized suitably for the load to be
monitored. Compare the color of the arrows on the current sensors to the chart below
to confirm the correct current sensor is being used.
Sensor Arrow Color Code Sensor Rating
Brown 100 A
Red 200 A
Yellow 400 A
Black 800 A
Blue 1600 A
White/Black 3200 A

CLASS 3200 METER
5 62-0390-02
CAUTION
Internal circuit components are extremely sensitive to electrostatic discharge.
Prior to handling or touching internal circuitry, discharge any static buildup on
your person. To discharge yourself, touch a grounded metal object such as
conduit or an earth-grounded enclosure.
WARNING
Use of this instrument, the E-Mon D-Mon Class 3200 meter, in a manner
inconsistent with this manual or not specified by the manufacturer in writing,
can cause permanent damage to the unit and/or serious injury to the operator.
The protection and safety features provided by this equipment may become
impaired or otherwise compromised.
NOTE: If any trouble arises during the installation or functional verification opera-
tions, do not immediately remove the unit. Before removing the unit, contact
E-Mon’s technical support and/or engineering department at (800) 334-3666.
E-Mon’ s technical department will assist you in detailed troubleshooting of
the Class 3200 meter installation and assist you in getting the unit operating
correctly.

CLASS 3200 METER
62-0390-02 6
2.0 INTERNAL ELECTRONIC ASSEMBLIES
The units are comprised of two major subassembly boards, the main power board and
the display board. Both circuit boards are mounted inside a UL Type 1 or Type 4X
enclosure.
Fig. 1. Internal Electronic Assemblies.
2.1 Main Power Board
Connections to this board include the MAIN Power Input and current sensors.The
MAIN Power Input terminals are positions one through four on the four position screw
terminal block, TB1. These terminals are covered with a protective shield for safety
purposes. The current sensor assemblies interface to TB2, TB3 and TB4. Each
terminal block corresponds to an input voltage phase; care must be exercised to
ensure that each current sensor is connected to the correct terminal block. One three
terminal screw connector is provided for RS-485 communications.
Fig. 2. Main Power Board Connections.
M33307
MAIN
POWER
BOARD
DISPLAY
BOARD
M33308
RS-485
TB1
POSITIONS
1-4
TB2, TB3,
TB4

CLASS 3200 METER
7 62-0390-02
2.2 Display Board
The display board connects to the main power board via a flex ribbon cable and the
board mounts on the inside of the housing door.
The Class 3200 meter features a 4-line LCD display that indicates multiple meter data
points.
Fig. 3. Display Board.
M33279
DOWN UP SELECT MENU

CLASS 3200 METER
62-0390-02 8
3.0 METER TECHNICAL SPECIFICATIONS
Ordering Information: Define brand, class, input voltage, amperage, protocol, and
sensor type in the format A-BB-CCC-DDDD-E-FFF-GGG, where
A = Brand: E for E-Mon
BB = designates Class: 3200 (32), 3400 (34), or 5000 (50) meter
CCC = input voltage: (208, 480, 600, 120 volt for High Voltage)
DDDD = current rating: (100, 200, 400, 800, 1600, 3200, 25HV)
E = enclosure: J = metal (type 1), R = non-metallic (type 4X), M = MMU
FFF= protocol: RTU = Modbus, BAC = BACnet, EZ7 = proprietary
GGG = Sensors: KIT = split-core, SCS = solid-core, “blank” = none supplied
Input Voltage
Configuration
3-wire (delta) Or 4-wire (wye)
Mains Voltage Input Up To 600 VAC RMS available
Input Power 6 VA maximum rating
Current Sensor
Rating
Up To 3200 amps RMS AC available
Power Factor 0.5 leading or lagging
Line Frequency 50-60 Hz
Metering Accuracy ANSI C12.20
Temperature Range -20C to +50C
Relative Humidity
Range
0-95% non-condensing
Altitude 2000 meters maximum
Voltage Overload +25% continuously: +100% For 20 cycles
Current Sensor
Overload
100% for 1 minute
Pollution Degree Degree 2 in accordance with IEC 664
Installation
(Overvoltage)
Category
Category III
Measurement
Category
Category III
M33191
EXAMPLE: E 32- 208 200 J RTU KIT
E-MON
CLASS 3200 METER
INPUT VOLTAGE (208V)
CURRENT RATING (200A)
ENCLOSURE (METAL - TYPE 1)
PROTOCOL (MODBUS)
SENSORS (SPLIT-CORE)

CLASS 3200 METER
9 62-0390-02
3.0 METER TECHNICAL SPECIFICATIONS
(CONTINUED)
Enclosure Material UL Type 1 or Type 4X
Display Readout LCD
Standard Ranges (4-Wire Wye) 208 VAC: 100, 200, 400, 800,1600, 3200 Amp
(3-Wire Delta) 240 VAC: 100, 200, 400, 800,1600, 3200 Amp
(4-Wire Wye) 480 VAC: 100, 200, 400, 800,1600, 3200 Amp
(3-Wire Delta) 480 VAC: 100, 200, 400, 800,1600, 3200 Amp
(4-Wire Wye) 600 VAC: 100, 200, 400, 800,1600, 3200 Amp
RS-485 Serial
Communications
Cable
Cable: UL-listed/rated/3-conductor,
300 VAC, stranded
conductors, 22-26 AWG.
Input/output Voltage: Ground-isolated +/-5.4Vdc
Cable Connector: Screw terminal termination
Circuit Input Isolation: 5.3kVAC
Max Cable Distance: 4000 feet
Max Network Nodes: 64 cabling nodes (including
master)
Baud Rate: 9600, 19200, 38400, 76800
Recommended
In-Line Fuse
Manufacturer: Littlefuse
Mfg. Part No: KLDR.100
Rating: 100mA, time-delay, 600VAC
cartridge fuse
Battery Cell: Description: Non-rechargeable cell used for
memory retention
Manufacturer: Panasonic
Mfg Part No: CR2032
Working Voltage: 3Vdc
Current Capacity 225 mAHr
Electrolyte: Manganese Dioxide Lithium

CLASS 3200 METER
62-0390-02 10
4.0 SAFETY LABEL DEFINITIONS AND
INFORMATION
The 3200 meter may contain one or more of the following labels. Operator(s) should
familiarize themselves with the meaning of each label to minimize risk.
The presence of this label is a cautionary indicator identifying a
danger risk. The manual should be consulted prior to proceeding.
The presence of this label indicates an electrical shock hazard exists
in the location or area where the label is placed. Prior to proceeding,
the MAINS power must be disconnected and the manual consulted for
safety information.
Tabla de contenidos
Otros manuales de Instrumento de medición de E-Mon
Manuales populares de Instrumento de medición de otras marcas

Endress+Hauser
Endress+Hauser Proline Promag 50 Especificaciones técnicas

Siemens
Siemens SITRANS F Coriolis FCT030 Manual de lista de piezas

KLINGER
KLINGER CMF V Series Manual de usuario

EXFO
EXFO FTB-2 Manual de operación y mantenimiento

Keysight
Keysight M8290A Manual de usuario

ADTEK
ADTEK MW-5 Manual de usuario