Distech Controls Allure EC-Smart-Vue Series Manual de usuario

Allure™ EC‑Smart‑Vue Sensor Series
Figure1: (Left image) Allure EC Smart Vue, Allure EC Smart Vue-H/-C/-CH sensors. (Right image) Models equipped with a motion
sensing window in the upper left corner: Allure EC Smart Vue-M/-CM/-HM/-CHM sensors
Product Description
The Allure EC-Smart-Vue Series is designed to interface with Distech Controls’ ECLYPSE™ series BACnet/IP and Wi-Fi Controllers, ECB series BAC-
net® Controllers and ECL series LONWORKS® Controllers.
This line of communicating sensors with backlit display consists of eight models that provide precise environmental zone control. Models are available
with any combination of the following: temperature, humidity, CO2, and motion sensor.
General Installation Requirements
For proper installation and subsequent operation of the device, pay special attention to the following recommendations:
£Upon unpacking, inspect the contents of the carton for shipping damages. Do not install a damaged device.
£Allow for proper clearance around the device’s enclosure and wiring terminals to provide easy access for hardware configuration and maintenance.
£Orient the device with the ventilation slots towards the top to permit proper heat dissipation.
£Ensure proper ventilation of the device and avoid areas where corroding, deteriorating or explosive vapors, fumes or gases may be present.
Any type of modification to any Distech Controls product will void the product’s warranty
Take reasonable precautions to prevent electrostatic discharge to the device when installing, servicing or during operation. Discharge
accumulated static electricity by touching one’s hand to a well-grounded object before working with the device.
General Wiring Recommendations
Risk of Electric Shock: Turn off power before any kind of servicing to avoid electric shock.
£All wiring must comply with electrical wiring diagrams as well as national and local electrical codes.
£Comply with all network and power supply guidelines outlined in the Network Guide.
£Use the screws, wall anchors, and wire nuts included for wall mounting and wiring.
Installation Guide

2 / 16
Mounting Instructions
The Allure Allure EC-Smart-Vue has been specially designed for easy installation. However, certain conditions apply when choosing a suitable location
for the device:
£Install the device in a location of average temperature approximately 5 ft (1.5 m) above the floor
£The device should not be installed on an exterior wall.
£The device should not be installed near a heat source.
£The device should not be installed near an air discharge grill.
£The device should not be installed in a place where it can be affected by the sun.
£Install the device in an area that provides proper device ventilation. Nothing must restrain air circulation to the device.
The Allure Allure EC-Smart-Vue has not been designed for outdoor use.
Mounting hardware with a separate sub-base is provided with the device for installation on dry wall or on an electrical junction box.
Wall Mounting Installation Procedure
The Allure EC-Smart-Vue can be mounted on a dry wall using supplied screws.
1. Remove the security screw from the device (See Device Mounting [pg.3]).
2. Open the device by pressing in the two (2) tabs on the bottom of the device and pulling the bottom side of the front plate out.
3. Set any jumpers (see Connector and Jumper Location, Identification and Configuration [pg.3]).
4. Pull all cables 6” (15cm) out of the wall, and insert them through the central hole of the back plate.
5. Align the back plate with the wall and mark the location of the mounting holes on the wall. Make sure to orient the proper side of the back plate facing
upwards.
6. Remove the back plate and drill holes in the wall if necessary.
7. Install anchors in the wall if necessary.
8. Make sure that the mounting surface is flat and clean.
9. Screw the back plate onto the wall. Do not over tighten.
10. Plug the wire(s) into the connector(s).Gently push excess wiring back into the wall.
11. Reattach the front plate and make sure it clips tightly into place.
12. Install security screw.
Device Dimensions
Model with
motion
sensor
1.15
(28.84)
3.29
(83.57)
4.62
(117.27)
Mounting Base Plate Shown Detached
Unit Legend: inches (mm)
2.36
(60.00)
2.37
(60.30)
0.12
(3.00)
3.31
(84.00)
0.20
(4.98)
1.06
(26.81)
Model without
motion
sensor
Bottom View
Figure2: Front view, bottom view, back plate, and side view for models with and without motion sensor.

3 / 16
Device Mounting
Security
Screw
Wall
Anchors
Figure3: Mounting anAllure EC-Smart-VueSensor
Connector and Jumper Location, Identification and Configuration
Allure EC-Smart-Vue sensors have the following onsite configurable jumpers.
ON
EOL
OFF
Front Cover, Interior View
BAC
LON
Local Area Network Type
Jumper
BACnet LONWORKS
3.5 mm (1/8”) Local
Area Network
Access Jack
Pass-Through Subnetwork RJ-45 Connectors
D
E
J11
J6
J18
PIR
LED
PIR LED
Motion Detection
Models Only
DisabledEnabled
Subnetwork End of Line
Enabled Disabled
Figure4: Connector and Jumper Locations
About an Allure EC-Smart-Vue Sensor Equipped with a CO₂ Sensor
The Allure EC-Smart-Vue C/-CM/-CH/-CHM sensors are factory calibrated to accurately read CO2 concentration levels at sea level. When these Allure
EC-Smart-Vue sensors are used in locations where the elevation is greater than 500ft (152m) above sea level, you must set the Elevation input of the
corresponding ComSensor block in EC-
gfx
Program to the current location’s elevation to obtain the most accurate readings.
For more information, refer to the ComSensor block section in the EC-
gfx
Program User Guide
Under normal conditions, an Allure EC-Smart-Vue sensor with CO2 sensor will typically reach its operational
accuracy after 25 hours of continuous operation on the condition that it was exposed to ambient air reference levels
of 400 ppm ±10 ppm CO2.

4 / 16
Supported Quantity
The Allure EC-Smart Vue sensor connects to the controller’s Subnet Port. Other expansion modules may also be connected to this port in a daisy-
chained fashion (see the controller’s datasheet for compatibility information and supported quantities).
Each controller supports a maximum number of Allure EC-Smart Vue sensors. The Subnet ID of all Allure EC-Smart Vue sensors must be set to be
within the shown addressing range.
Series Maximum Number of Allure EC‑Smart‑Vue sensors1Permitted Subnet ID Addressing
Range
ECB‑VAV
ECL‑VAV
ECY-VAV
ECY-VAV-PoE
ECY-303
Up to 421 to 4
ECB-VAV-O
ECL-VAV-O
ECB-VAVS
ECL-VAVS
ECB-VVTS
ECL-VVTS
ECB-VAV-N
ECL-VAV-N
ECB‑PTU Series
ECL‑PTU Series
ECB‑103
ECL‑103
ECB‑203
ECL‑203
ECY-TU/PTU
4 1 to 4
ECB‑300
ECL‑300
ECB‑400 Series
ECL‑400 Series
ECB‑600 Series
ECL‑600 Series
ECY-S1000 Series
12 1 to 12
Table1: Number of Allure EC-Smart-Vue sensors supported by controller model
1. A controller can support a maximum of two (2) Allure EC-Smart Vue sensor models equipped with a CO2sensor. Any remaining connectedAllure EC-Smart Vue sensor models must be without a
CO2sensor.
2. See the room device calculator spreadsheet available for download from our website to know the permitted quantities according to the controller model: VAV Smart Room Control Device
Calculator.xlsm.
About the Subnetwork Bus
The ECB-600 and ECL-600 controllers use the Subnetwork bus to support the ECx-400 Series I/O Extension Modules through the controllers Subnet+
and Subnet- terminals with 2-wire shielded cable.
The ECB-600 and ECL-600 controllers also use the Subnetwork bus to support one or more Allure Series(s) using standard structural (Cat 5e) cabling.

5 / 16
Subnetwork Bus Total Length
The total maximum length of all Subnetwork buses, including both the length of the Allure Series Communicating Sensor Subnetwork bus and the
ECx-400 Series Subnetwork bus is 300 m (1000 ft). The maximum length of the Allure Series Communicating Sensor Subnetwork bus is 200 m (650 ft).
The maximum length of the ECx-400 Series Subnetwork bus is 300 m (1000 ft).
Sub-Network Bus Total Length: 300 m (1 000 ft) Maximum
Sub-Network Bus: 200 m
(650 ft) Maximum
Allure EC-Smart-Vue
Sub-Network Bus: 300 m
(1 000 ft) Maximum
ECx-400
Typical Compatible
Controller Extension I/O Modules
ECx-400
Sub-Network Bus - Cat 5e Cable
with RJ-45 Connectors
Allure EC-Smart-Vue
Sub-Network Bus
ECx-400
2-Wire Shielded Cable
Figure5: Subnetwork Bus Overview Showing the Allure EC-Smart-VueSubnetwork Bus and the ECx-400 Series Subnetwork Bus.
A controller can support a maximum of two Allure EC-Smart-Vue sensor models equipped with a CO2 sensor; the remaining connected models must be
without a CO2 sensor. See Table 1 for the quantity of room devices supported by each controller model.
For instance, if the controller model supports a subnetwork with 12 Allure EC-Smart-Vue sensors in total, then 10 sensor models must be without a CO2
sensor and the other two can be equipped with a CO2 sensor. To ensure proper operation, it is recommended to distribute the sensors throughout the
length of the subnetwork.
Cat 5e Cable with RJ-45 Connectors
Sub-Network Bus Total Length: 1 000 ft (300 m) Maximum
10x...2x...
Bus: 600 ft (180 m) Maximum
Allure EC-Smart-Vue
Sensor Sub-network
ECB-600 ECL-600or
Typical
Controller
ECx-400
Sub-Network Bus
Figure6: Allure EC-Smart-Vue Sensor Subnetwork Length and Distribution
For ECB/ECL-PTU Series controllers, the maximum length between two consecutive devices on the sub-network bus
is 100 feet (30 m).

6 / 16
Subnetwork Bus Topology and EOL Terminations
Only a daisy chain topology is acceptable for the room device subnetwork bus. T connections are not allowed.
Some controller models support the connection of other devices to the Subnet Port as part of the Smart Room Control solution (see the controller’s
datasheet for more information).
For non ECB-600 or ECL-600 Series controllers, only the EOL terminations of the last subnetwork bus device are set to ON. All other subnetwork bus
devices must have their EOL terminations set to OFF. The controller must be the first device on the Cat 5e Cable Subnetwork bus as its internal EOL ter-
mination is permanently enabled.
See Table 1 for the number of Allure EC-Smart-Vue sensors that a given controller model can support.
Typical Room Devices
Cat 5e Cable Subnetwork Bus
EOL set to ON
at the last
sensor at the
end of the Bus
ON
EOL
OFF
Controller Series:
· ECB-VAV-O
· ECB-VAVS
· ECB-VVTS
· ECB-VAV-N
· ECB-103
· ECB-203 Series
· ECB-300 Series
· ECB-400 Series
Back of Allure
EC-Smart-Vue
· ECL-VAV-O
· ECL-VAVS
· ECL-VVTS
· ECL-VAV-N
· ECL-103
· ECL-203 Series
· ECL-300 Series
· ECL-400 Series
Figure7: Setting the EOL Terminations on the Allure EC-Smart-Vue Sensor for non ECB-600 or ECL-600 series, non-Smart Room Con-
trol controllers
Typical Room Devices
Cat 5e Cable Subnetwork Bus
EOL set to ON
at the last
sensor at the
end of the Bus
ON
EOL
OFF
Controller Series:
· ECB-VAV
· ECL-VAV
· ECLYPSE (ECY-VAV, ECY-S1000)
· ECB-PTU Series
· ECL-PTU Series
Back of Allure
EC-Smart-Vue
ECx Subnet
Adapter
Figure8: Setting the EOL Terminations on the Allure EC-Smart-Vue Sensor for Smart Room Control-compatible controllers
When one or more Allure EC-Smart-Vue sensors are installed with an ECB-600 or ECL-600 (without an ECx-4xx IO Extension Module), only the EOL
terminations on the ECB-600 / ECL-600 and the last Allure EC-Smart-Vue sensor are set to ON. All other Allure EC-Smart-Vue sensors must have their
EOL terminations set to OFF.

7 / 16
ON
EOL
OFF
EOL OFF
EOL ON
Controller:
ECB-600
ECL-600
Cat 5e Cable Subnetwork Bus
Inside
Controller Back of
Allure EC-Smart-Vue
Sensor
EOL set to ON
at the last
sensor at the
end of the Bus
For the controller, set the
Subnetwork EOL to ON
Figure9: Setting the EOL Terminations on the Allure EC-Smart-VueSensor for ECB-600 or ECL-600 Seriescontrollers
When ECx-400 Series I/O Extension Modules are installed with an ECB-600 or ECL-600 Series controller and with Allure Series Communicating Sen-
sors, only the EOL terminations on the last I/O Extension Module and the last Allure Series Communicating Sensor are set to ON. The ECB-600 /
ECL-600 and all other I/O Extension Modules and Allure Series Communicating Sensor s must have their EOL terminations set to OFF.
EOL OFF
ON
EOL
OFF
EOL ON
Typical Compatible
Controller I/O Extension Modules
ECx-4xx
ECx-4xx
I/O Extension Modules 2 - Wire Shielded
- Last daisy-chained I/O Extension Module:
EOL Jumper is ON
- All other I/O Extension Modules:
EOL Jumpers are OFF
- Last daisy-chained Communicating Sensor:
EOL Jumper is ON
- All other Communicating Sensors:
EOL Jumpers are OFF
Communicating Sensor Sub-Network Bus
- Cat 5e Cable with RJ-45 Connectors
Figure10: Setting the EOL Terminations on the ECx-400 SeriesSubnetwork Bus when Allure EC-Smart-VueSensors are used
ECx-400 Series devices and Allure EC-Smart-Vue sensors are factory-set with the EOL set to OFF by default.
If inserting multiple wires in the terminals, ensure to properly twist wires together prior to inserting them into the terminal connectors.
For more information and detailed explanations on network topology and wire length restrictions, refer to the Network Guide, which can be downloaded
from our website
www.distech-controls.com
.

8 / 16
Setting the Communicating Sensor Subnet ID
Controllers can be commissioned with an Allure EC-Smart-Vue sensor.
The default Subnet ID for an Allure EC-Smart-Vue Series Communicating Sensor is 1. To commission an ECB Series controller, the sensor’s Subnet ID
must be set to 1. If the sensor’s Subnet ID has been set to another value (for example, the display flashes error code 1 with the Bell icon when the sen-
sor is connected to a controller for commissioning), change the Subnet ID to 1 as follows:
1. Connect an an Allure EC-Smart-Vue Series Communicating Sensor to the controller with a Cat 5e patch cable. Wait for the Bell icon and the number
1 to flash on the display.
2. Press and hold the Menu button for 5 seconds to enter the password menu. 10000 is shown on the display.
OR
Screen Timeout: 15 seconds
3. Press the down button to set the number to 9995 (this is the default password).
OR
Screen Timeout: 15 seconds
4. Press the Menu button to submit the password. Upon submitting the password, the GEN CFG menu appears on the display.
OR
Screen Timeout: 30 seconds
5. Press the down button once to enter the GEN CFG submenu.
6. Press the Menu button several times until SUBNET ID appears on the display. The current controller’s Subnet ID is shown.
OR
Screen Timeout: 30 seconds
7. Use the up and down buttons to set the controller’s Subnet ID to 1.
Tip
: Hold down either the up or down button to fast-advance the display
value.
8. Press the Menu button once.
9. Press and hold the Menu button for 5 seconds to exit the configuration menu.
The an Allure EC-Smart-Vue Series Communicating Sensor can now be used to go from one ECB series controller to the next for commissioning pur-
poses.
Commissioning Controllers
For ECB series controllers: to commission a controller with a MAC Address DIP switch located on the faceplate or under the cover in the case of an
ECB-VAV Series controller, first set the DIP switch to 0 (all off). When using an Allure EC-Smart-Vue sensor for commissioning a controller (before code
is downloaded to the controller from EC-
gfx
Program), connect an Allure EC-Smart-Vue sensor to the controller with its Subnet ID set to 1. (see Setting
the Allure EC-Smart-Vue Sensor Subnet ID).

9 / 16
For controllers embedding a pre-loaded application, commissioning can be used to perform application selection if needed. Pre-loaded applications are
factory-loaded programs that enable the controller to control a typical equipment. See the Pre-Loaded Application User Guide for more information.
For ECB Series controllers only, during commissioning, the Allure EC-Smart-Vue sensor is used to set the controller’s BACnet® MAC Address. Set the
connected ECB Series controller’s MAC Address as follows:
Set the connected controller’s MAC Address as follows:
1. Connect an Allure EC-Smart-Vue Series Communicating Sensor to the controller with a Cat 5e patch cable. Wait for the display to show the room
temperature.
2. Press and hold the Menu button for 5 seconds to enter the password menu. 10000 is shown on the display.
OR
Screen Timeout: 15 seconds
3. Use the down button to set the number to 9995 (this is the default password).
OR
Screen Timeout: 15 seconds
4. Press the Menu button to submit the password. Upon submitting the password, the GEN CFG menu appears on the display.
OR
Screen Timeout: 30 seconds
5. Press the down button once to enter the GEN CFG submenu. The MAC ADDRESS menu is shown with the current controller’s BACnet MAC Ad-
dress.
OR
Screen Timeout: 30 seconds
6. Use the up and down buttons to set the controller’s MAC Address. Only addresses from 1 to 127 are recommended to be used.
7. Press the Menu button once to apply the value.
8. Press and hold the Menu button for 5 seconds to exit the configuration menu.
Once the controller’s network is operational, the controller can be programmed with EC-
gfx
Program. For each Allure EC-Smart-Vue Series Communicat-
ing Sensor, set its Subnet ID number to the block number of its associated ComSensor block in EC-
gfx
Program. This is done in the sensor’s GEN CFG
menu under SUBNET ID.

10 / 16
Setting the BAUD Rate (optional – ECB series controllers only)
By default, the BAUD rate for the controller is set to automatically detect the current communication BAUD rate of the connected BACnet MS/TP network
(AUTO). This is the preferred setting for a controller. However, at least one controller on the BACnet MS/TP network data bus must have its BAUD rate
set. The preference is to set the building controller’s BAUD rate (if present). Otherwise, set the BAUD rate on one controller that will set the BAUD rate
for all other controllers (to act as the master for setting the BAUD rate).
When the BAUD rate is set to AUTO, the controller cannot initiate any communication until it has detected the baud
rate of the BACnet MS/TP network. If all controllers on the BACnet MS/TP network are set to AUTO, then all
controllers will not communicate.
Set the connected controller’s BAUD rate as follows:
1. Connect an Allure EC-Smart-Vue Series Communicating Sensor sensor to the controller with a Cat 5e patch cable. Wait for the display to show the
room temperature.
2. Press and hold the Menu button for 5 seconds to enter the password menu. 10000 is shown on the display.
OR
Screen Timeout: 15 seconds
3. Use the down button to set the number to 9995 (this is the default password).
OR
Screen Timeout: 15 seconds
4. Press the Menu button to submit the password. Upon submitting the password, the GEN CFG menu appears on the display.
OR
Screen Timeout: 30 seconds
5. Press the down button once to enter the GEN CFG submenu.
6. Use the Menu button several times until BAUD RATE appears on the display. The current controller’s BAUD rate is shown.
OR
Screen Timeout: 30 seconds
7. Use the up and down buttons to set the controller’s Baud rate. The AUTO setting detects and uses the current baud rate being used by the
BACnet MS/TP network.
8. Press the Menu button once to apply the value.
9. Press and hold the Menu button for 5 seconds to exit the configuration menu.
Este manual sirve para los siguientes modelos
28
Tabla de contenidos
Otros manuales de Accesorios de Distech Controls

Distech Controls
Distech Controls Allure EC-Sensor Series Manual

Distech Controls
Distech Controls UNIWAVE Manual de usuario

Distech Controls
Distech Controls GS-AQR Manual

Distech Controls
Distech Controls EC-Multi-Sensor Series Manual

Distech Controls
Distech Controls Allure UNITOUCH Manual

Distech Controls
Distech Controls Allure EC-Smart-Air Series Manual de usuario

Distech Controls
Distech Controls HS-THX Manual de usuario

Distech Controls
Distech Controls EC-Multi-Sensor-BLE Manual de usuario