[email protected]CURRENT TRANSFORMER BASICS
To ensure safety and maintain UL listings, use only CTs provided by DENT
Instruments.
▪Do not use on services greater than 600VAC
▪CTs are 333.3 mV (1/3 V) output voltage, or DENT RōCoil
▪Select CTs of appropriate current range for the circuit (5-120% of CT
rating recommended)
▪Ensure arrow points towards load (or as instructed by CT label)
▪Place CT on rst conductor of voltage reference. Example: for L1-L2
circuits without neutral, place CT on L1
▪Observe wiring color and polarity: For millivolt CTs, the white wire is (+)
and the black wire is (-). For RōCoils, the white is (+), brown is (-), and the
bare, shield wire connects to the terminal marked “S”
POWERSCOUT 12
1. Alarm Output
2. Ethernet
3. USB
4. RS-485
5. 12V Out (2W)
6. Mounting Hole
7. Display
8. Navigation Buttons
9. Voltage Connection
10. 1” EMT Conduit
Connection (x5)
11. Pulse Inputs (4 total)
12. CT Inputs (12 total)
13. High Voltage Cover
(IP30)
14. Mounting Plate
15. ABS Plastic Enclosure
14
15
11
12
Pictured with High Voltage TouchSāf Cover removed.
10
7
8
9
1 2 3 4 5 6 13
10
13
14
15
16
1. Pulse Input 1
2. Pulse Input 2
3. Ethernet
4. USB
5. 12V Out (2W)
6. RS-485
7. Alarm Output
8. CT Inputs (24 or 48)
9. Display
10. Navigation Buttons
11. Voltage Input 1
12. Voltage Input 2
13. Mounting Plate
(Optional)
14. High Voltage Cover
(IP30)
15. 1” EMT Conduit
Connection (x6)
16. ABS Plastic Enclosure
POWERSCOUT 24/48
1 2 3 4 5 6 8
11 12
10
9
7
Pictured on
Mounting Plate
with High Voltage
TouchSāf Cover
removed.
Top edge
detail
Rev060120
WARNING
▪RISK OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH. CAREFULLY READ AND
FOLLOW INSTRUCTIONS.
▪THIS METER MAY CONTAIN LIFE THREATENING VOLTAGES. RISK OF ELECTRIC
SHOCK. QUALIFIED PERSONNEL ONLY. USER MUST DISCONNECT ALL HIGH VOLTAGE
WIRING BEFORE SERVICING THE METER WITH THE HIGH VOLTAGE COVER REMOVED.
▪TO AVOID FIRE, SHOCK, OR DEATH, TURN OFF ALL POWER SUPPLYING EQUIPMENT
BEFORE WORKING ON OR INSIDE THE EQUIPMENT. USE PROPERLY RATED VOLTAGE
SENSING DEVICE TO CONFIRM POWER IS OFF.
▪FOLLOW SAFE ELECTRICAL WORK PRACTICES. FOLLOW ALL APPLICABLE LOCAL
ELECTRICAL CODES.
▪THIS EQUIPMENT MUST BE INSTALLED AND SERVICED BY QUALIFIED ELECTRICAL
PERSONNEL WITH THE REQUISITE KNOWLEDGE, TRAINING, AND EXPERIENCE
RELATED TO THE INSTALLATION AND OPERATION OF THIS EQUIPMENT.
▪PRODUCT MAY USE MULTIPLE VOLTAGE/POWER SOURCES. BE SURE ALL SOURCES
OF POWER HAVE BEEN DISCONNECTED BEFORE SERVICING.
▪DO NOT DEPEND ON THIS PRODUCT FOR VOLTAGE INDICATION.
DO NOT EXCEED 346V Line-to-Neutral or 600V Line-to-Line. This meter is equipped to
monitor loads up to 346V L-N. Exceeding this voltage will cause damage to the meter
and danger to the user. Always use a Potential Transformer (PT) for voltages in excess
of 346V L-N or 600V L-L. The PowerScout HD is a 600 Volt Over Voltage Category III
device.
SAFETY SYMBOLS
Denotes caution. See full Operator’s Guide for description of the meanings.
Equipment protected throughout by double insulation or reinforced insulation.
DENOTES HIGH VOLTAGE. RISK OF ELECTRIC SHOCK. LIFE THREATENING VOLTAGES
MAY BE PRESENT. QUALIFIED PERSONNEL ONLY.
Contains additional information pertinent to the current subject.
i
1. Connect a powered, or unpowered, PowerScout meter to a USB port of your computer
with a USB A to USB B cable (provided). [Note: The PC will power the meter for setup even
without AC mains power connected.]
2. Launch the ViewPoint HD application and, when prompted, click “Connect over USB”
3. The meter will now be communicating with the PC
4. Use ViewPoint HD to congure the meter and view real-time data to verify the installation is
wired correctly
SETUP THE METER WITH A PC
The meter can also be setup without using ViewPoint HD and instead using a web
browser. Plug in the USB cable and set the browser to 169.254.1.5.
i
USB-B
USB-A
NAVIGATING THE METER’S DISPLAY
VIEW COMMUNICATIONS
REAL-TIME VALUES
VIEW METER SETUP
VERIFY INSTALLATION
LOG IN / OUT
ABOUT METER
VIEW COMMUNICATIONS
REAL-TIME VALUES
VIEW METER SETUP
VERIFY INSTALLATION
LOG IN / OUT
ABOUT METER
PROTOCOL: BACNET
BAUD RATE: 9600
BITS: 8N1
ELEMENT A CHANNELS
V 100 101 99.9
A 23.2 22.9 22.0
KW 2.0 2.0 2.0
ELEMENT A CHANNELS
KVA 100 110 111
KVAR 100 -110 123
KWH 1234 *** 100
USING THE LCD SCREEN
Use the arrow keys to move from one menu display to the next. The ENTER button is used to make
a change. Note that changes to the meter conguration are limited to the communication interface
when using the LCD. If additional changes (such as CT type) are required, they must be made using
either ViewPoint HD software or web server interface.