1PREFACE
This manual is for project developers, users and assemblers who utilize
the ACCON-NetLink-USB compact.
It shows the user the handling of the ACCON-NetLink-USB compact and
explains signaling functions. All necessary data for assembling should be
provided to the assembler. © 2015 - 2016
DELTA LOGIC
Automatisierungstechnik GmbH
Stuttgarter Strasse 3
73525 Schwaebisch Gmuend
Germany
Phone sales: +49-(0)7171-916-120
Phone support: +49-(0)7171-916-112
Fax sales: +49-(0)7171-916-220
Fax support: +49-(0)7171-916-212
E-Mail sales: sales@deltalogic.de
E-Mail support: support@deltalogic.de
Web site: www.deltalogic.de
All rights reserved. No part of this work is allowed to be copied, reproduced, conferred,
processed and stored into electronic media or translated into any other language without a
written permission of the author. STEP®, TIA®, TIA Portal®, S7-200®, S7-300®, S7-400®, HMI®,
STEP® and SIMATIC® are registered trademarks of Siemens AG, ACCON® and DELTALOGIC®
are registered trademarks of DELTA LOGIC Automatisierungstechnik GmbH.
Note:
We have checked the content of this manual for conformity with the hardware and software
described. Nevertheless, because deviations cannot be ruled out, we cannot accept any
liability for complete conformity. The data in this manual have been checked regularly and
any necessary corrections will be included in subsequent editions. We always welcome
suggestions for improvement.
Last update 2016-09-27. All technical changes reserved.

ACCON-NetLink-USB compact 2
TBALE OF CONTENTS
1PREFACE ................................................................ 1
2TECHNICAL DESCRIPTION .................................... 3
3SCOPE OF DELIVERY ............................................. 4
4DEVICE DESCRIPTION ........................................... 5
5REQUIREMENTS FOR OPERATING ........................ 7
6COMMISSIONING .................................................. 8
7BUS SETTINGS.....................................................10
8TROUBLE SHOOTING...........................................19
9FREQUENTLY ASKED QUESTIONS ...................... 20
10 TECHNICAL DATA ................................................22

ACCON-NetLink-USB compact 3
2TECHNICAL DESCRIPTION
ACCON-NetLink-USB compact is the compact communication and
programming adaptor between PC and S7 controllers. The electronics of
the ACCON-NetLink-USB compact is placed in the box of a PROFIBUS
connector what makes the adaptor very small and handy.
As all-rounder, the ACCON-NetLink-USB compact can be connected to
the PLC via MPI, PROFIBUS and PPI. The ACCON-NetLink-USB compact
independently detects the current bus settings of the PLC.
The communication of the ACCON-NetLink-USB compact and the PC is
effected via USB. The device supports the parametrization of DP-Slaves
via DP-V1 (class 2). A driver for SIMATIC applications (ACCON-S7-NET) is
included. The ACCON-NetLink-USB compact gets its power supply via
the USB cable.
Features:
•Automatic bus profile detection
•Full PROFIBUS speed 12 Mbps
•USB 2.0 up to 480 Mbps (Highspeed)
•Extended diagnostics options
•MPI, PROFIBUS and PPI is supported
•Supports slave parametrization via DP-V1 (class 2)
•Supports all established SIMATIC Engineering Tools
•Power supply via USB
•Plug with PG socket
•Can be used up to 60 °C

ACCON-NetLink-USB compact 4
3SCOPE OF DELIVERY
•ACCON-NetLink-USB compact
•DELTA LOGIC Automatisierungstechnik-DVD including ACCON-S7-
NET driver

ACCON-NetLink-USB compact 5
4DEVICE DESCRIPTION
Figure 1: ACCON-NetLink-USB compact
1. USB plug type A to connect the device to usual PCs or USB hubs.
2. Status LEDs
3. Bus plug with PG socket, switchable terminator and a 1.2 m
connection cable.
2
1
3

ACCON-NetLink-USB compact 6
Starting the ACCON-NetLink-USB compact
During the first seconds after starting the Power LED is blue. After 25
seconds the boot procedure is already finished and the Device is ready.
LED display
STATUS LED POWER LED ACTIVE
LED BUS LED
Ready to operate BLUE
Trying to log in on the
device at the bus BLUE BLINKING
ORANGE
Device is logged in on
the bus BLUE GREEN
Data exchange with a
controller BLUE BLINKING
GREEN
Table 1: Status LEDs
POWER LED ACTIVE
LED BUS LED
Transmitting firmware
update
BLINKING
BLUE BLINKING
RED
Table 2: Firmware update

ACCON-NetLink-USB compact 7
5REQUIREMENTS FOR OPERATING
Hardware requirements
Siemens S7-200-, S7-300 and S7-400 automation devices or compatible
to S7. The used PCs must have a working USB interface. You can also
use standard USB cards which support both Highspeed 480 Mbps and
Fullspeed 12 Mbps. But to achieve a good performance you should use
USB 2.0 interfaces.
Software requirements
To use the ACCON-S7-NET drivers you need a PC including Windows XP,
2003R2, 7, 2008R2, 8.1, 2012R2, 10. On this PC the SIMATIC Device
Drivers (PG/PC-Interface) have to be installed. The SIMATIC Device
Drivers will be installed with e. g. STEP 7, STEP 7 lite or STEP 7-
Micro/Win. By installing ACCON-S7-NET more interfaces will be added
to the PG/PC-Interface.
Assembly
Installation and assembly have to be carried out according to VDE 0100
/ IEC 364. As the ACCON-NetLink-USB compact is an IP30 module it has
to be built into a switchboard.
For secure operating please keep the maximum environmental
temperature of 60 °C in mind.

ACCON-NetLink-USB compact 8
6COMMISSIONING
Connection to the PC
Put one end of the USB cable into the USB socket of your ACCON-
NetLink-USB compact and the other end into a USB port of your PC.
Connection to the automation device
Connect the 9-pin SUB-D plug to the MPI or PROFIBUS interface of your
S7 controller.
Installation of the USB driver
When connecting an ACCON-NetLink-USB compact to the PC for the
first time, the operating system tries to install a suitable device driver.
This could take a while and continues as follows:
For the installation under Windows you need to be logged in as
administrator!
The operating system starts an installation wizard.
1. Lay in the delivered DELTA LOGIC Automatisierungstechnik-DVD
and select the folder:
S7-Adapter\ACCON-NetLink\USBDriver
Then click on »Next«.
2. Now the driver search starts.
3. If found, the installation can be started with a click on »Next«.
4. After a successful installation click on »Finish« to complete the
setup.
The ACCON-NetLink-USB compact has been installed successfully and
can be used now. If there are several ACCON-NetLink-USB compact
devices available it is recommendable to copy the USB drivers to your
hard disk. As for every ACCON-NetLink-USB compact a single driver
entity is installed. Therefore the driver data is needed every time when
installing an ACCON-NetLink-USB compact. Remember that you cannot
use more than one ACCON-NetLink-USB compact on a single PC,
simultaneously.

ACCON-NetLink-USB compact 9
Latest driver and firmware versions can be found on our web site at
www.deltalogic.de in the section »Downloads«.
Installation Software
The driver ACCON-S7-NET can be installed by executing the file
»SetupAcconS7Net.exe« from the DELTA LOGIC
Automatisierungstechnik-DVD (<DVD-drive>\S7-Adapter).
Set PG/PC Interface
1. Open the SIMATIC PG/PC Interface.
The following points have to be in the dialog »Set PG/PC Interface«:
- ACCON-S7-NET NLUSB(MPI)
- ACCON-S7-NET NLUSB(PPI)
- ACCON-S7-NET NLUSB(PROFIBUS)
Figure 2: Set PG/PC Interface