Delta Controls DLC-D312 Guía del usuario

INSTALLATION & APPLICATION GUIDE
Delta Lighting Controller (Douglas Lighting)
DLC-D312/624/936 (Rev 1.5c)
Document Edition 1.2
Product Description
The Delta Douglas Lighting Controller is a Native BACnet
Application Controller that communicates on a BACnet
MS/TP RS-485 LAN. The controller is designed for lighting
applications and can switch from 12 up to 36 Douglas lighting
relay outputs per controller. The controller also supports up to
12 Delta BACstats connected on its LINKnet subnetwork.
Lighting algorithms are written in Delta’s powerful GCL+
programming language. Both firmware and controller
databases are loadable over the network and are backed
up/loaded to/from flash memory.
With its board dimension and capability of switching up to 36
Douglas lighting relays, this controller is ideal to mount in
various Douglas relay enclosures for both new and retrofit
construction projects. The controller also includes a built-in
sequencer for sweeping through and turning all the lighting
relays on or off in a timed sequence. The controller is
completely programmable using GCL+, and BACnet objects
can be created and modified for the lighting application.
Contents
MODEL NUMBERS & ACCESSORIES ................................................2
PACKAGE CONTENTS...........................................................................2
OTHER RELEVANT DOCUMENTS .....................................................2
IMPORTANT INFORMATION..............................................................2
PRODUCT SPECIFICATIONS...............................................................2
BOARD LAYOUT.....................................................................................4
CONTROLLER ADDRESS DIP SWITCHES........................................7
JUMPERS ..................................................................................................7
MOUNTING...............................................................................................8
INPUT & OUTPUT WIRING ................................................................10
POWER ....................................................................................................12
NETWORK CABLING & REQUIREMENTS.....................................12
NETWORK TOPOLOGY ......................................................................13
NETWORK COMMUNICATIONS SETUP ........................................13
APPLICATION NOTES.........................................................................14
CAUTIONS & WARNINGS...................................................................15
COMPLIANCE DECLARATIONS.......................................................15
Document Edition 1.2 Page 1 of 17

Delta Lighting Controller (Douglas Lighting) DLC-D312/624/936 (Rev 1.5c) Installation
& Application Guide
Model Numbers
The Douglas Lighting Controller has the following product numbers: DLC-D312, DLC-
D624, DLC-D936
Accessories
• DNS-24 BACstat II Network Sensor
• RPT-768 Delta Network Repeater for MS/TP
• TRM-768 Delta Network Terminator for MS/TP
Package Contents
• Delta Lighting Controller (Douglas Lighting) Board, DLC-D312/624/936 (Rev 1.5c)
• Stylized Enclosure for quick mounting
• DLC-D312/624/936 (Rev 1.5c) Installation & Application Guide
Other Relevant Documents
• Delta Controls Wiring Guidelines
• ORCAview Operator Guide
• ORCAview Technical Reference Manual (particularly Appendix G)
• Release Notes for V3.30 Firmware/Software
Important Information
The Douglas Lighting Controller (DLC-Dxxx), Rev 1.5c is only compatible
with DSC Firmware 3.30, Release 2 or higher. Loading any other firmware
will result in the controller becoming inoperable.
Ensure that the controller is properly grounded. If not, poor network
communication will result. (See page 9 for more information.)
Page 2 of 17 Document Edition 1.2

Delta Controls
Product Specifications
Power Requirements
• 24 VAC c/w Visual LED status indication.
• 50 VA (including Douglas relays and switches (4 relays/6 switches per output)).
Ambient Ratings
• 32º to 131º F (0º to 55º C).
• 10 to 90% RH (non-condensing).
Communication Ports
Main LAN (NET1) c/w Visual LED Status Indication
• BACnet™ MS/TP @ 9,600 or 19,200 or 38,400 or 76,800 bps (the default).
• Maximum of 99 controllers per MS/TP segment.
SubLAN (NET2) c/w Visual LED Status Indication
• LINKnet @ 76,800 bps.
• Maximum 12 BACstats per lighting controller.
Inputs
DLC-D312
• 3 Binary Inputs (Douglas 2-wire relay switch or Dry Contact inputs (c/w Status Feedback & LED
status indication)).
• 1 Analog Input, c/w Visual LED status indication.
DLC-D624
• 6 Binary Inputs (Douglas 2-wire relay switch or Dry Contact inputs (c/w Status Feedback & LED
status indication)).
• 1 Analog Input, c/w Visual LED status indication.
DLC-D936
• 9 Binary Inputs (Douglas 2-wire relay switch or Dry Contact inputs (c/w Status Feedback & LED
status indication)).
• 1 Analog Input, c/w Visual LED status indication.
Outputs
12, 24 OR 36 Douglas Lighting Relays Outputs (max 4 Relays/6 Switches per Output)
• WR-6161 1 Pole HID Relay 20A 120/277/347
• WR-6162 2 Pole HID Relay 20A 120/277/347
• WR-6161-3 1 Pole HID Relay with aux contact 20A 120/277/347
Document Edition 1.2 Page 3 of 17

Delta Lighting Controller (Douglas Lighting) DLC-D312/624/936 (Rev 1.5c) Installation
& Application Guide
• WR-6162-3 2 Pole HID Relay with aux contact 20A 120/277/347
• WR-6172 2 Pole HID Relay 20A 120/277/347/480
Sweeper Ports
Sweeper Input Port c/w Visual LED Status Indication
• Master Override or Sweeper Input Port, c/w Command Sequencer.
Sweeper Output Port c/w Visual LED Status Indication
• Connects to another lighting controller’s Sweeper Input Port to continue the sweep
sequence.
On-Board Overrides
• ON scan button provides ALL ON override control.
• OFF scan button provides ALL OFF override control.
Connectors
• Network & Power: Removable screw type terminal connectors.
• Relays: Removable screw type terminal connectors (one terminal per relay).
• Inputs: Removable screw type terminal connectors.
Technology
• 16-bit Processor.
• 2 MB (16 megabit) Flash Memory.
• 512 KB SRAM Memory.
Device Addressing
• Set via DIP switch and jumpers, or Software Setup.
Wiring Class
• Class 2
Size
Controller & Enclosure
• 3.625” x 10.125” x 1.0” (9.2 cm x 25.7 cm x 2.5 cm)
Weight (c/w Enclosure)
• Controller Board = 0.84 lb. (380 g.)
Page 4 of 17 Document Edition 1.2

Delta Controls
Board Layout (DLC-D312/624/936)
DNA
ON
On
12345678
12416 83264
24~ GND + NET1 -
TX
RXPWR SCAN
4-20mA 10k 5V 10V
INTERNAL
EXTERNA
L
INTERNAL
EXTERNA
L
INTERNAL
EXTERNA
L
GND AI1GNDBI2BI3BI4
EXT
AC1
GNDBI5BI6BI7
EXT
AC2
GNDBI8BI9BI10
EXT
AC3
OFF GND ON OFF GND ON
SEQ IN SEQ OUT SERVICE PORT
24~ GND + NET2 -
TX
RX
4.0"
(101mm)
10.2"
(260 mm)
Single Wire Douglas
Relay Outputs
Analog Input
Binary Inputs
NET2
(LINKnet SUB-LAN)
24VAC
Power Out
NET1
(BACnet MS/TP)
24VAC
Power In
On/Off
Sequencer
Input
On/Off
Sequencer
Output
Override Off
Relay Status
LEDs
Override On
Address DIP
Switches
OFF ON
SEQUENCER
1 3 5 7 9 1113 15 1719 21 2325 2729 3133 35
24681012141618202224262830323436
Document Edition 1.2 Page 5 of 17

Delta Lighting Controller (Douglas Lighting) DLC-D312/624/936 (Rev 1.5c) Installation
& Application Guide
Indicators
L
ED Function Description
Scan CPU Scan Indicator Due to memory expansion on this model the
LED no longer indicates the CPU scan rate.
Power CPU Power Indicator This amber LED turns on to indicate that the
controller has 24 VAC applied. If no Control
Power transformer is connected the LED will be
off.
N
etwork
(NET1)
RS-485 Communication Status
Indicators for NET1 (the main
LAN connection)
A Green LED flashes to indicate when the
device is transmitting out the associated port,
and a red LED flashes to indicate when the
device is receiving data through the port.
N
etwork
(NET2)
RS-485 Communication Status
Indicators for NET2 (LINKnet)
A Green LED flashes to indicate when the
device is transmitting out the associated port,
and a red LED flashes to indicate when the
device is receiving data through the port.
Analog Input
(AI1)
Analog Input Status Indicators The corresponding red LED varies with the
Analog Input Voltage. The light will indicate full
red when the Voltage is 0V, and will be off
when the Voltage is 5V.
Binary Inputs
(BI2 – BI10)
Input Status Indicators The corresponding LED will be green if the port
is open contact or the WR850X switch is OFF.
The same LED will be red if the port is closed
contact or the WR850X switch is ON.
Sweep Input
(BI11 (active),
BI12 (value))
Sweep Input Signal Indicators A corresponding red LED will reflect the port
status to match the ON or OFF signal of the
Sweep Input (for spooling to the next controller).
Sweep Output
(BO37)
Sweep Output Signal Indicators A corresponding green LED will turn on
momentarily to match the ON or OFF signal of
the Sweep Output (for spooling to the next
controller).
Binary Outputs
(BO1-BO36)
Output Relay Status Indicators Reflects the status of the Relay.
I.e. Red – ON, Green - OFF
Binary Outputs
(BO38-BO46)
Output Status Indicators Outputs to be used with WR8501 and WR8503
Douglas Switches. The BI points will reflect the
corresponding Output from the BO point,
assuming that there has been no interference of
manual override.
Page 6 of 17 Document Edition 1.2

Delta Controls
Controller Address DIP switches
Each individual DIP switch represents a unique value, which forms the device address
when added together.
Jumpers
5V 10V4-20mA 10K
ANALOG INPUT 1
The input type is selected by placing the jumper in the
correct location on the Input Type Selector Block. The
diagram to the left shows the factory default selection of 10
KΩ.
4-20mA For sensors that use a 4 to 20 mA signal.
10K For 10 KΩThermistor temperature sensors, as
well as Dry Contact binary inputs.
5V For sensors that use a 0 to 5 VDC signal.
10V For sensors that use a 0 to 10 VDC signal.
BINARY INPUTS (BI2 – BI10)
The binary inputs can be selected to use either an internal or
external power source by placing the jumper in the correct
locations. The diagram to the left shows the factory default
selection of Internal Power Source. For each group of 3
BI’s, there is an associated jumper to select the power
source.
Internal 24 VAC Power is provided internally from within
the board right to the output terminals. No external
transformer is required. Note that the power supply
should be sized appropriately to handle the
additional loading.
External Power needs to be provided externally to the
board from a nearby transformer appropriately
connected to the output wiring.
DEVICE TYPE
Note that the Douglas Lighting Controller does not have a
Device Type jumper. It is fixed as a Subnet level device.
As a result, the Douglas Lighting Controller may only be
EXT
AC1
BI4 BI2 GNDBI3
Internal
External
24VAC
Document Edition 1.2 Page 7 of 17

Delta Lighting Controller (Douglas Lighting) DLC-D312/624/936 (Rev 1.5c) Installation
& Application Guide
installed at the Subnet level, and the DIP or MAC address is
always mapped into the Subnet portion of its address,
inheriting other portions of its BACnet address when DNA
is enabled.
DNA
DERIVED NETWORK ADDRESSING (DNA)
Derived Network Addressing (DNA), which works in
conjunction with the Device Type setting and refers to the
ability of inheriting portions of its address from higher-up
devices on a BACnet MS/TP network, may be enabled or
disabled via jumper setting.
EnabledWith the jumper in place, the controller
automatically obtains portions of its overall BACnet
device address (as related to Area and System) from
higher-up devices on the network. This is the
preferred method of addressing the controller in a
system of Delta devices.
Disabled With the jumper removed, the device does
not obtain any portions of its address from higher-up
devices. Instead, default numbers are assumed (for
Area and System), which may be modified via
software. This method of addressing is most useful
in OEM or multi-vendor installations where Delta
products do not exist higher-up in the network
architecture, or where device address ranges are pre-
assigned for the installation.
NOTE: Whether or not Derived Network Addressing is
enabled, the Addressing DIP switches are always used to set
the device MAC address.
Mounting
The Douglas Lighting Controller is designed for mounting quickly and easily in a number
of locations, usually within one of several sizes of Douglas relay enclosures. Ensure the
controller itself is a safe distance away or in some other way protected from relief valves
and other water sources.
Page 8 of 17 Document Edition 1.2

Delta Controls
Document Edition 1.2 Page 9 of 17

Input & Output Wiring
Input and output wiring on the Delta Douglas Lighting Controllers should be
straightforward, as shown below. Refer to separate documentation for additional details.
Relay Wiring Details
Each relay control coming from the red terminal on the Douglas Relay will be connected to
the corresponding BO on the relay ports.
Document Edition 1.2 Page 10 of 17
Este manual sirve para los siguientes modelos
2
Tabla de contenidos
Otros manuales de Controladores de Delta Controls

Delta Controls
Delta Controls Red5-PLUS/EDGE-6 Series Manual de usuario

Delta Controls
Delta Controls DRP-T0B Manual de usuario

Delta Controls
Delta Controls DLC-G1212 Guía del usuario

Delta Controls
Delta Controls eZFC-424R4-24 Guía del usuario

Delta Controls
Delta Controls eZV-440 Guía del usuario

Delta Controls
Delta Controls Red5-PLUS/EDGE-11 Series Manual de usuario

Delta Controls
Delta Controls DSC-1280 Manual de usuario