Datcon DT1361 Manual de usuario

DT1361
Intrinsically Safe NAMUR / Contact Isolators
Operating Instructions

DT1361
2 20171206-V0
Contents
1. About this document.....................................................4
1.1. Function ................................................................................... 4
1.2. Target group............................................................................. 4
1.3. Symbolism used....................................................................... 4
2. For your safety...............................................................5
2.1. Authorized personnel ............................................................... 5
2.2. Appropriate use........................................................................ 5
2.3. Warning about misuse ............................................................. 5
2.4. General safety instructions....................................................... 5
2.5. EU conformity........................................................................... 5
2.6. Safety information for Ex areas................................................ 6
2.7. Environmental instructions....................................................... 6
3. Product description.......................................................7
3.1. Delivery configuration............................................................... 7
3.2. Principle of operation ............................................................... 7
3.3. Adjustment ............................................................................... 8
3.4. Indicators.................................................................................. 9
3.5. Storage and transport .............................................................. 9
4. Setting-up the operating modes.................................10
4.1. Open the instrument housing ................................................. 10
4.2. Setting up operating modes ................................................... 11
4.3. Close the instrument housing................................................. 12
5. Mounting.......................................................................13
5.1. General instructions ............................................................... 13
5.2. Main dimensions of the instrument ........................................ 13
5.3. Mounting procedure ............................................................... 14
6. Connecting ...................................................................15
6.1. Preparing the connection ....................................................... 15
6.2. Connecting the detector or the contact to the input. .............. 16
6.3. Connecting the relay contacts and the power supply............. 17
6.4. Put the instrument under supply voltage................................ 17

DT1361
20171206-V0 3
7. Fault rectification.........................................................18
7.1. Fault finding............................................................................ 18
7.2. Repairing................................................................................ 18
8. Dismounting.................................................................19
8.1. Dismounting procedure .......................................................... 19
8.2. Disposal ................................................................................. 20
9. Appendix.......................................................................21
9.1. Technical specification ........................................................... 21
9.2. Application example ............................................................... 23
9.3. ATEX Certification.................................................................. 24

DT1361
4 20171206-V0
1. About this document
1.1. Function
This operating instructions manual has all the information
you need for quick set-up and safe operation of DT1361.
Please read this manual before you start setup.
1.2. Target group
This operating instructions manual is directed to trained
personnel. The contents of this manual should be made
available to these personnel and put into practice by them.
1.3. Symbolism used
Information, tip, note
This symbol indicates helpful additional information.
Caution, warning, danger
This symbol informs you of a dangerous situation that could
occur. Ignoring this cautionary note can impair the person
and/or the instrument.
Ex applications
This symbol indicates special instructions for Ex
applications.
•List
The dot set in front indicates a list with no implied sequence.
→Action
This arrow indicates a single action.
1
Sequence
Numbers set in front indicate successive steps in a
procedure.

DT1361
20171206-V0 5
2. For your safety
2.1. Authorized personnel
All operations described in this operating instructions
manual must be carried out only by trained and authorized
specialist personnel. For safety and warranty reasons, any
internal work on the instruments must be carried out only by
DATCON personnel (except setting DIL switches).
2.2. Appropriate use
The DT1361 is a two channel intrinsically safe NAMUR /
contact isolator. Detailed information on the application
range is available in chapter 3. Product description.
2.3. Warning about misuse
Inappropriate or incorrect use of the instrument can give rise
to application-specific hazards, or damage to system
components through incorrect mounting or adjustment.
2.4. General safety instructions
The DT1361 is a high-tech instrument requiring the strict
observance of standard regulations and guidelines.
The user must take note of the safety instructions in this
operating instructions manual, the country-specific
installation standards as well as all prevailing safety
regulations and accident prevention rules.
2.5. EU conformity
The DT1361 is in conformity with the provisions of the
following standards:
MSZ EN 60079-0:2013 (ATEX)
MSZ EN 60079-0:2013/A11:2014 (ATEX)
MSZ EN 60079-11:2012 (ATEX)
MSZ EN 61326-1:2013 (EMC)
MSZ EN 55011:2016 (EMC)
MSZ EN 55011:2016/A1:2017 (EMC)
MSZ EN 61010-1:2011 (LVD)
MSZ EN 50581:2011 (RoHS 2)

DT1361
6 20171206-V0
2.6. Safety information for Ex areas
Please note the Ex-specific safety information for installation
and operation in Ex areas.
2.7. Environmental instructions
Protection of the environment is one of our most important
duties.
Please take note of the instructions written in the following
chapters:
•Chapter 3.5. Storage and transport
•Chapter 8.2. Disposal

DT1361
20171206-V0 7
3. Product description
3.1. Delivery configuration
Delivered items The scope of delivery encompasses:
•DT1361
•documentation:
this operating instructions manual
certification
warranty
3.2. Principle of operation
Area of application The DT1361 Intrinsically Safe NAMUR / Contact Isolator
is a single channel unit enable one safe area load to be
controlled by a proximity detector or a switch, located in a
potentially explosive area of zone 0 or zone 1.
The instrument galvanic isolates the input, the output and
the power supply. The safe output is a SPDT relay contact.
The DT1361 has a built-in mode-control switch for phase-
reverse control (allows an alarm condition to be signaled for
either state of the sensors), for on / off switch line
monitoring (wire short, wire open). The line fault detection
opens the output in the event of short or open-circuit lines:
intended for use primarily with proximity detectors. It can
also be used with switches made to resemble them
electrically by adding two resistors, or disabling by a switch
if not required.

DT1361
8 20171206-V0
Operating principle
The instrument is powered from a 19-29 VDC supply
through a DC-DC converter. The output supplies the input
circuit. The isolation and intrinsically-safe segregation are
provided by a high isolation relay. The input circuit provides
a 8.2 VDC supply voltage for the sensor through a 1 kohm
resistor. A multilevel comparator detects the current
consumption of the sensor (according with NAMUR
standard).
The levels are as follows:
> 2.1 mA ON (near) state
< 1.2 mA OFF (far) state
< 0.15 mA open circuit (wire broken) state
> 6 mA short circuit (wire short) state
The output relay is controlled by the comparator output in
conjunction of the states of mode switch.
Power supply The instrument works from a 19-29 VDC supply voltage.
The power consumption is 0.6 W.
3.3. Adjustment
The DT1361 operating modes can be set-up with the
internal three element DIL switch.

DT1361
20171206-V0 9
3.4. Indicators
The following figure shows the indicators on the instruments
front:
1. “power” green indicator, indicates the power-on state of
the instrument.
2. red indicator, indicates the line fault state
3. yellow indicator, indicates the output active state
3.5. Storage and transport
This instrument should be stored and transport in places
whose climatic conditions are in accordance with chapter
9.1 Technical specification, as described under the title:
Environmental conditions.
The packaging of DT1361 consist of environment-friendly,
recyclable cardboard is used to protect the instrument
against the impacts of normal stresses occurring during
transportation. The corrugated cardboard box is made from
environment-friendly, recyclable paper. The inner protective
material is polyfoam and nylon, which should be disposed of
via specialized recycling companies.

DT1361
10 20171206-V0
4. Setting-up the operating modes
The operating modes can be set-up with the internal DIL
switch (SW1). To reach the DIL switch the instrument
housing shall be open.
4.1. Open the instrument housing
The following figure shows how to open the instrument
housing:
Open the instrument
housing
Put the instrument on a clean surface prevent to get in any
alien material into the housing.