SAFETY REQUIREMENTS
•Read the user’s manual carefully prior to the operation and installation of the unit.
•Installation and operation of the unit shall be performed in accordance with the present
user’s manual as well as the provisions of all the applicable local and national construction, electrical
and technical codes and standards.
•The warnings contained in the user’s manual must be considered most seriously since they
contain vital personal safety information.
•Failure to follow the safety regulations may result in an injury or unit damage.
•Read the manual carefully and keep it as long as you use the unit.
•While transferring the unit control the user’s manual must be turned over to the receiving
operator.
UNIT OPERATION SAFETY PRECAUTIONS
Do not carry out the unit maintenance with wet hands.
Do not wash the unit with water. Protect the unit electric parts from water ingress.
Do not block the air intake and exhaust vents during the unit operation.
Disconnect the unit from power supply prior to maintenance.
Do not let children operate the unit.
Do not damage the power cable while operating the unit. Do not put any objects on the power cable.
Keep combustible gases and inflammable products away of the unit.
Do not open the operating unit.
In case of unusual sounds, smoke disconnect the unit from power supply and contact the service
centre.
Do not let air flow from the unit be directed to the open flame devices or candles.
INTRODUCTION
This user’s manual includes technical description, operation, installation and mounting guidelines,
technical data for the air heating unit with electric heater E-HP, hereinafter referred as the unit.

USE
The unit is designed for air heating of medium up to large premises, such as industrial halls, storage
facilities, workshops, sport halls, trade halls, greenhouses, etc. The unit is designed for operation in
moderate and cold climate conditions.
E-HP 9, 12, 15 E-HP 18, 24, 30
UNIT DESIGN
FAN
TERMINAL BOX
EMERGENCY
THERMAL
LOUVRE
SHUTTERS

TECHNICAL PARAMETERS
Model
E-HP 9
E-HP 12
E-HP 15
E-HP 18
E-HP 24
E-HP 30
Supply voltage, 50 Hz [V]
3 ~ 400
Max. fan power [W]
140
253
Fan current [A]
0,61
1,1
Electric heater power [kW]
9
13,0
12
15
18
26,0
24
30
Electric heater current [A]
17,3
21,7
34,6
43,3
Total unit power [kW]
9,14
12,14
15,14
18,25
24,25
30,25
Total unit current [A]
13,6
17,9
22,3
27,1
35,7
44,4
Air capacity [m3/h]
2300
4000
RPM [min-1]
1420
1480
Casing material
Painted steel
Noise level, 5 m, [dB(A)]
55
61
Ingress protection rate
IP 21
Weight[kg]
32
48
Transported air must not contain any flammable or explosive mixtures, evaporation of chemicals,
coarse dust, soot and oil particles, sticky substances, fibrous materials, pathogens or any other
harmful substances.
DESIGN AND OPERATING LOGIC
The unit is designed for indoor air heating by means of the electric heater and uniform air flow
distribution with the fan and louvre shutters.
The special unit design enables quick air heating in large premises due to high-efficient electric
heater and a powerful fan. The electric connections and control connections are performed in a
terminal box at the side unit panel.
UNIT MOUNTING AND SET-UP
THE UNIT INSTALLATION IS ALLOWED BY QUALIFIED PROFESSIONALS AFTER
CAREFUL STUDY OF THE USER’S MANUAL.
While mounting the unit provide the minimum required access to the unit for maintenance and
repair.
The unit is designed for wall mounting or mounting to any other vertical surface or ceiling mounting
with fixing bracket.
While mounting the unit provide free air flow to the unit intake opening. The minimum distance from
the wall or the ceiling to the unit is 300 mm.

WARNING!
REDUCING MINIMUM DISTANCE FROM THE UNIT TO THE WALLS OR CEILING ADVERSELY
AFFECTS AERODYNAMIC AND HEATING CHARACTERISTICS AND THE UNIT SERVICE LIFE.
UNIT INSTALLATION WITH MKP-AOW MOUNTING KIT
The mounting kit MKP-AOW (available upon separate order) is used for ceiling mounting of the unit
with mounting studs or chains.
The unit mounting example with the mounting kit MKP-AOW is shown below.
CONNECTION TO POWER MAINS
DISCONNECT THE UNIT FROM POWER MAINS PRIOR TO ANY ELECTRIC
INSTALLATION OPERATIONS. CONNECT THE UNIT TO A CORRECT INSTALLED SOCKET WITH A
GROUNDED TERMINAL. ANY INTERNAL CONNECTION MODIFICATIONS ARE NOT ALLOWED
AND RESULT IN WARRANTY LOSS.
The unit must be operated only jointly with an automation system that enables the following
functions:
1. Disabling power supply to the heater when the fan is off.
2. Air supply to the electric heating elements for heat removal within 2 minutes after the unit is
off.
3. Maintaining minimum air speed 2 m/s to avoid heating elements overheating.
4. Power supply cut-off in case of overheating of the electric elements by means of the thermal
switches mounted inside of the heater casing
5. Automatic heating capacity control to keep the maximum air temperature downstream of
the electric heater +40 °C to avoid the heater overheating and reducing its service life.

The unit with a selected control system is rated for connection to three-phase ac 400 V / 50 Hz power
mains. Connection to power mains of the unit with any control system must be performed with
insulated, durable and heat-resistant conductors (cables, wires).
The external power input 400 V / 50 Hz must be equipped with an automatic circuit breaker built into
the stationary wiring to disconnect all the power mains phases. The circuit breaker QF position must
ensure free access for quick power-off of the unit. The circuit breaker trip current must be in
compliance with the current consumption of a specific E-HP model.
The recommended circuit breaker trip current and the cable cross sections for various Е-HP models
are given un the table below. However, the conductor selection shall be based on the maximum
permissible wire heating depending on the wire type, its insulation, length and installation method
(i.e. overhead, in channels or inside the walls)
Terminal block x1 (in the control circuit):
RT1 –temperature sensor;
TK1 –self-resettable thermal switch (normally closed contact), response temperature +50 °C;
TK2 –manually resettable thermal switch (normally closed contact), response temperature +90 °C;
Connect the thermal switch contacts in series to the circuit of the starter (contactor) actuating coil
that starts the unit or the heater. In case of overheating one of the contacts gets broken and
switches the starter actuating coil off to cut power off and stop the motor.
Terminal block x2 (heaters):
L1, L2, L3 –phases (for Е-HP 9,12,15);
1L1, 1L2, 1L3, 2L1, 2L2, 2L3 –phases (for Е-HP 18,24,30);
N –neutral;
PE –protecting grounding.
Unit name
Rated circuit breaker trip current [A]
Numberof conductorsand crosssection[mm
2
]
Е-HP -9
20
5х2,5
Е-HP-12
25
5х2,5
Е-HP -15
31,5
5х4,0
Е-HP -18
40
5х6,0
Е-HP -24
50
5х10,0
Е-HP -30
63
5х10,0

Terminal block x3 (fan):
L –phase; N –neutral.The fan, the heaters, the thermal switch and the temperature sensor are
mounted on side of the unit, refer to the wiring diagram

UNIT WIRING DIAGRAM
The emergency thermal switches are actuated in case of unscheduled power outage or wrong
selected control system.
The automatically resettable thermal switch with response temperature +50 °C resets to operating
condition after the heater cooling.
Reset of the manually resettable thermal switch with response temperature +90 °C is as follows:
Disconnect the unit from power mains.
Let the heater fully cool down.
Remove the emergency thermal switch cap.
Press the Reset button using a rod of non-conducting material. Troubleshoot the unit overheating
and make steps to prevent it.

MAINTENANCE
Regular routine maintenance is required. The unit must be cleaned of dust once in year by means of
air blushing. Disconnect the unit from power mains prior to the unit cleaning.

DE
SICHERHEITSANFORDERUNGEN
•Lesen Sie die Bedienungsanleitung sorgfältig durch, bevor Sie das Gerät in Betrieb und
Installation installieren.
•Die Installation und der Betrieb des Geräts erfolgen in Übereinstimmung mit dem
vorliegenden Benutzerhandbuch sowie den Bestimmungen aller anwendbaren lokalen und
nationalen Bau-, elektro- und technischen Codes und Normen.
•Die im Benutzerhandbuch enthaltenen Warnungen sind am schwerwiegendsten zu betrachten, da
sie wichtige persönliche Sicherheitsinformationen enthalten.
•Die Nichtbeachtung der Sicherheitsvorschriften kann zu einer Verletzung oder einer
Beschädigung der Einheit führen.
•Lesen Sie das Handbuch sorgfältig durch und bewahren Sie es auf, solange Sie das Gerät
verwenden.
•Bei der Übertragung der Gerätesteuerung muss die Bedienungsanleitung an den
empfangenden Bediener übergeben werden.
UNIT OPERATION SICHERHEIT PRECAUTIONS
Führen Sie die Wartung des Geräts nicht mit nassen Händen durch.
Waschen Sie das Gerät nicht mit Wasser. Schützen Sie die elektrischen Teile des Geräts vor dem
Eindringen von Wasser.
Blockieren Sie die Lufteinlass- und Abluftöffnungen während des Betriebs nicht.
Trennen Sie das Gerät vor der Wartung von der Stromversorgung.
Lassen Sie Kinder das Gerät nicht bedienen.
Beschädigen Sie das Netzkabel nicht, während Sie das Gerät bedienen. Legen Sie keine Gegenstände
auf das Netzkabel.
Brennbare Gase und brennbare Produkte vom Gerät fernhalten.
Öffnen Sie die Bedieneinheit nicht.
Bei ungewöhnlichen Geräuschen trennt Rauch das Gerät von der Stromversorgung und kontaktiert
das Servicecenter..
Lassen Sie den Luftstrom aus dem Gerät nicht auf die offenen Flammengeräte oder Kerzen lenken.
Este manual sirve para los siguientes modelos
6
Tabla de contenidos
Idiomas:
Otros manuales de Calentador de dalap
Manuales populares de Calentador de otras marcas

Empire Heating Systems
Empire Heating Systems WCC65 Manual de usuario

Wetekom
Wetekom 92 86 43 Manual de usuario

Desa
Desa SPC170-F Manual de usuario

Watlow
Watlow Watrod Electric Tubular Heaters Manual de usuario

Haverland
Haverland ECO-DRY GPS Series Manual de lista de piezas

Stelpro
Stelpro ASILVC2060 Series Manual de usuario