Cutes Corporation
CT-2000F
Series
AC MOTOR DRIVER
Instruction
Head Office : 2-22, Nan Yuan Road, Chung Li City, Taiwan
TEL: 886 3 4612333 or 886 3 4526161 ext. 275, 266, 512
FAX: 886 3 4526227 or 886 3 4511347
E-mail: [email protected]
URL: www.cutes.com.tw

C.TY TNHH TỰ ĐỘNG HÓA VIỆT TRUNG 02413.281.181-0989.984.666
bsite:www.viet-trung.com.vn Đ/c:194-Nguyễn Trãi-Võ Cường-TP.Bắc Ninh
2

C.TY TNHH TỰ ĐỘNG HÓA VIỆT TRUNG 02413.281.181-0989.984.666
Website:www.viet-trung.com.vn Đ/c:194-Nguyễn Trãi-Võ Cường-TP.Bắc Ninh
3
Introduction / Table of Contents
Introduction
Thank you for choosing the CT-2000 inverter unit, this inverter unit is suitable for operating
squirrel cage induction motors. Please read this instruction manual carefully before actual
usage in order to ensure proper operation and suit your needs.
Table
of
Contents
1. Inspection upon receiving…………………………………………………. 4
2. Installation and Storage…………………………………………………… 4
A. Installation and………………………………………………………….. 4
B. Storage…………………………………………………………………… 4
3. Application notes…………………………………………………………… 5
4. Block diagram and Wiring ………………………………………………… 5
A. Wiring of main and control circuit …………………………………… 5
B. Signal circuit……………………………………………………………. 5
C. Connecting the power supply and the AC motor…………………… 6
D. R.S.T. for Power source reactor……………………………………… 7
E. Standard external connection diagram……………………………… 8
F. Control circuit specification………………………………………….... 9
G. Terminal specifications……………………………………………….. 10
5. Operation Test……………………………………………………………… 11
6. Function Setup and Specification.……………………………………….. 13
A. Keypad operation………………………………………………………. 13
B. Display specification…………………………………………………… 14
C. Keypad specification…………………………………………………… 14
D. Function Code………………………………………………………….. 15
7. Description of alarm display indications ………………………………… 45
8. Troubleshooting……………………………………………………………. 47
9. Maintenance and Inspection……………………………………………… 49
10. Standard Specification…………………………………………………….. 50
A. 200V series……………………………………………………………… 50
B. 400V series……………………………………………………………… 50
C. Standard specification………………………………………………….. 51
D. Outline dimension………………………………………………………. 52
11. Function code Table……..………………………………………………. 53
12. Modbus Address of Display Data….…………………………………… 60
13. Series Communication User Manual..…………………………………. 62
A. The physical link………………………………………………………… 62
B. Data structure in communication……………………………………… 63

C.TY TNHH TỰ ĐỘNG HÓA VIỆT TRUNG 02413.281.181-0989.984.666
Website:www.viet-trung.com.vn Đ/c:194-Nguyễn Trãi-Võ Cường-TP.Bắc Ninh
4
C. Function code in Modbus……………………………………………… 66
D. Error check generation………………………………………………… 67
E. Group & global broadcasting…………………………………………. 69
- 3 -

C.TY TNHH TỰ ĐỘNG HÓA VIỆT TRUNG 02413.281.181-0989.984.666
Website:www.viet-trung.com.vn Đ/c:194-Nguyễn Trãi-Võ Cường-TP.Bắc Ninh
5
Inspection upon receiving / Installation and storage
1.
Inspection
upon
receiving
A. Check that the model, the capacity and power voltage specifications are as
ordered.
B. Check that no damage has occurred during transportation.
C. Check that none of the internal parts have been damaged or have fallen off.
D. Check that none of the connectors have been damaged or have fallen off.
E. Check that there is no loosening of the terminals or screws of each of the parts.
2.
Installation
and
Storage
A. Storage:
If the equipment is not to be installed immediately, it should be stored in a clean and
dry location at ambient temperatures from 20℃to 55℃. The surrounding air must
be free of corrosive contaminants.
B. Installation place:
Places where the peripheral temperature is from -10℃to 40℃, and where the
relative humidity is 90% or less. Avoid installing at places where there is dust, iron
particles, corrosive gas, water spray, direct sunlight or too much vibration. And
places where has good ventilation.
10cm
min.
10cm
min.
10cm
min.
10cm
min.

C.TY TNHH TỰ ĐỘNG HÓA VIỆT TRUNG 02413.281.181-0989.984.666
Website:www.viet-trung.com.vn Đ/c:194-Nguyễn Trãi-Võ Cường-TP.Bắc Ninh
6
- 4 -

C.TY TNHH TỰ ĐỘNG HÓA VIỆT TRUNG 02413.281.181-0989.984.666
Website:www.viet-trung.com.vn Đ/c:194-Nguyễn Trãi-Võ Cường-TP.Bắc Ninh
7
Block diagram, wiring
3.
Application
notes
A. Concerning the inverter unit:
(1) Do not fit capacitors to the output side of the inverter in order to improve the
power ratio.
(2) In case of fitting MC between inverter and motor to control motor operation,
then the capacity of inverter must be 6 times the capacity of motor.
(3) Run a motor that is within the capacity of the inverter unit, light load current and
no-load current will cause the motor to develop ripple current.
(4) This unit is provided with a current limiting function. The starting torque is
assumed to be from 80% to 100%.
B. Concerning the AC motor
(1) When general-purpose motors are operated at low speeds, there is a reduced
cooling effect, please apply the special purpose motor.
(2) Operation at frequencies exceeding 60 Hz requires caution, as there is the
danger of the mechanical strength failure of the motor.
(3) When motors with brakes are being operated, the power for the brake and
inverter should be taken from the same power supply and the brake operation
must be in phase when the unit is started and stopped.
4.
Block
diagram,
Wiring
A. Wiring of main and control circuit
Wire according to the standard connection diagram. On using the external
sequence control, please use small signal relay or double terminal relay to avoid
relay terminal malfunction.
B. Signal circuit
The signal circuit uses either shielded pairs or twisted pairs, should be wired either
using a wiring duct separated from that for the power circuit, or with the wiring
conduit isolated as much as possible.

C.TY TNHH TỰ ĐỘNG HÓA VIỆT TRUNG 02413.281.181-0989.984.666
Website:www.viet-trung.com.vn Đ/c:194-Nguyễn Trãi-Võ Cường-TP.Bắc Ninh
8
- 5 -

C.TY TNHH TỰ ĐỘNG HÓA VIỆT TRUNG 02413.281.181-0989.984.666
Website:www.viet-trung.com.vn Đ/c:194-Nguyễn Trãi-Võ Cường-TP.Bắc Ninh
9
Block diagram, wiring
C. Connecting the power supply and the AC motor
Connect the main circuit, by wiring according to the main circuit terminal connection
diagram. Care is required not to make a mistake when connecting the input and
output terminals, lest it will cause inverter damage. Specifications of main circuit
path and NFB are as follow:
Voltage (V) Model NFB (A) Wire size for
circuit (mm
2
)
CT-2002-A75 6A 2~5.5
CT-2002-1A5 10A 2~5.5
CT-2002-2A2 15A 3.5~5.5
CT-2002-3A7 20A 5.5
CT-2002-5A5 30A 5.5~8
CT-2002-7A5 40A 5.5~8
220
380
|
440
CT-2002-011 60A 22
CT-2002-015 80A 30
CT-2002-022 120A 38
CT-2002-030 150A 38~100
CT-2002-037 200A 38~100
CT-2002-045 250A 60~100
CT-2002-055 300A 100
CT-2002-075 400A 100~200
CT-2002-093 500A 100~200
CT-2004-A75 5A 2~5.5
CT-2004-1A5 5A 2~5.5
CT-2004-2A2 7.5A 2~5.5
CT-2004-3A7 10A 3.5~5.5
CT-2004-5A5 15A 3.5~5.5
CT-2004-7A5 20A 5.5
CT-2004-011 30A 8~14
CT-2004-015 40A 8~14
CT-2004-022 60A 22
CT-2004-030 80A 22
CT-2004-037 100A 30
CT-2004-045 120A 50
CT-2004-055 150A 38~100
CT-2004-075 200A 38~100
CT-2004-093 250A 60~100
CT-2004-112 300A 100