CTI GG-6 Manual de usuario

866-394-5861
sales@CTiengineering.com
www.CTiengineering.com
GG6-GE-DOC1-2 Page 1
GG-6 GATEWAY MODULE MANUAL
Introduction
This manual is for the GG6-GE and GG6-GR Gateway Modules. It includes Installation, Set-up,
Configuration and Troubleshooting instructions for all of the different variants.
NOTE
If your Gateway Module is already installed in the GG-6, skip to the GENERAL SET-UP section below.
Installation
1. Remove the Unitronix EX-A2X Expansion Adapter, and the upper right backboard screw from the
GG-6.

866-394-5861
sales@CTiengineering.com
www.CTiengineering.com
GG6-GE-DOC1-2 Page 2
2. Place the GG-6 Gateway where the Expansion
Adapter was located and loosely attach the upper
right screw.
3. Re-install the Expansion Adapter, tighten all
screws, and re-connect the power and
communication cables.

866-394-5861
sales@CTiengineering.com
www.CTiengineering.com
GG6-GE-DOC1-2 Page 3
4. Cut the zip ties along the Expansion Adapter communication cable, and install the new
communication/power cable alongside the Expansion Adapter cable.

866-394-5861
sales@CTiengineering.com
www.CTiengineering.com
GG6-GE-DOC1-2 Page 4
5. Run the power cable (Orange, White/Orange pair) up to the top connector on the GG-6 PLC.
6. Double up the Orange wire with the Red wire in the first terminal position on the PLC. Double up
the White/Orange wire with the Black wire in the second terminal position.

866-394-5861
sales@CTiengineering.com
www.CTiengineering.com
GG6-GE-DOC1-2 Page 5
7. Plug the Blue, White/Blue pair of wires with the RJ-11 connector into Port 2 (the RS-485 port) on the
PLC.
8. Reinstall any zip ties that were removed.

866-394-5861
sales@CTiengineering.com
www.CTiengineering.com
GG6-GE-DOC1-2 Page 6
General Set Up
Power up the GG-6 and check the GG-6 MODBUS Configuration (see GG-6 Manual for menu navigation):
ID (64 to 127): 64
Master/Slave: Slave
Display: Main
Download and install the ICC Configuration Studio SW ver 2.0.3.7 on a PC, running Win 7 or higher. The
computer will need a spare USB Port. The program can be found on the CTI website at
https://www.ctiengineering.com/Downloads. Scroll down to the Tools section at the bottom of the
page and download ICC Configuration Studio V2.0.3.7 Installer. Un-Zip the file and install the
program.
Run the ICC Configuration Studio program. Do not upgrade to a newer version of ICC Configuration
Studio.
Connect the GG-6 Gateway Module to the computer using the mini-USB cable.
Check for data activity in Database.
Once connected, the Online Devices should show one new device under the Device Configurations.
Select the Online Devices, and select the Discovered Devices tab. Double click on the ETH-1000 (for the
GG6-GE-x) or the XLTR-1000 (for the GG6-GR-x), and select the Project tab.
Right click on ETH-1000 or XLTR-1000 and select Upload Configuration.
CAUTION
Do not change any parameters, other than directed, within the GG-6 Gateway Module or you may
compromise the performance and safety of the GG-6.

866-394-5861
sales@CTiengineering.com
www.CTiengineering.com
GG6-GE-DOC1-2 Page 7
GG6-GE-E Configuration
Select the Ethernet tab on the uploaded ETH-1000 configuration.
From this tab the IP Settings can be changed from Static to DHCP. In the Static mode, the IP Address,
the Subnet Mask and the Default Gateway can be set.
Select the EtherNet/IP Server tab on the uploaded ETH-1000 configuration.
From this tab the Device Name and Connection Timeout Options can be set.
Do not change anything on or below the Class 1 I/O Messaging tab.
Once all of the changes have been made, right click on uploaded ETH-1000 configuration and select
Download Configuration. Answer Yes to overwriting the configuration. Remove the mini-USB cable and
close the program.

866-394-5861
sales@CTiengineering.com
www.CTiengineering.com
GG6-GE-DOC1-2 Page 8
GG6-GE-M Configuration
Select the Ethernet tab on the uploaded ETH-1000 configuration.
From this tab the IP Settings can be changed from Static to DHCP. In the Static mode, the IP Address,
the Subnet Mask and the Default Gateway can be set.
Select the Modbus/TCP Server tab on the uploaded ETH-1000 configuration.
From this tab the Timeout and Connection Timeout Options can be set.
Do not change anything below the Node tab.
Once all of the changes have been made, right click on uploaded ETH-1000 configuration and select
Download Configuration. Answer Yes to overwriting the configuration. Remove the mini-USB cable and
close the program.

866-394-5861
sales@CTiengineering.com
www.CTiengineering.com
GG6-GE-DOC1-2 Page 9
GG6-GE-B Configuration
Select the Ethernet tab on the uploaded ETH-1000 configuration.
From this tab the IP Settings can be changed from Static to DHCP. In the Static mode, the IP Address,
the Subnet Mask and the Default Gateway can be set.
Select the BACnet/IP Server tab on the uploaded ETH-1000 configuration.
From this tab the UDP Port, APDU Timeout and the Number of APDU Retries can be set.
Select the Device Object tab under the Node tab on the uploaded ETH-1000 configuration.
From this tab the Device Name and the Instance Number can be changed.
Do not change anything below the Device Object tab.
Once all of the changes have been made, right click on uploaded ETH-1000 configuration and select
Download Configuration. Answer Yes to overwriting the configuration. Remove the mini-USB cable and
close the program.

866-394-5861
sales@CTiengineering.com
www.CTiengineering.com
GG6-GE-DOC1-2 Page 10
GG6-GR-M Configuration
Select the Modbus RTU Slave tab on the uploaded XLTR-1000 configuration.
From this tab the Baud Rate, Parity, Timeout and Response Delay can be set to match the RS-485
network.
Select the Node tab on the on the uploaded XLTR-1000 configuration.
From this tab the Modbus Address can be set.
Do not change anything below the Node tab.
Once all of the changes have been made, right click on uploaded XLTR-1000 configuration and select
Download Configuration. Answer Yes to overwriting the configuration. Remove the mini-USB cable and
close the program.
Otros manuales para GG-6
1
Este manual sirve para los siguientes modelos
2
Tabla de contenidos
Manuales populares de Puerta de otras marcas

LST
LST M500RFE-AS Manual de usuario

Kinnex
Kinnex Media Gateway Manual de usuario

2N Telekomunikace
2N Telekomunikace 2N StarGate Manual de usuario

Mitsubishi Heavy Industries
Mitsubishi Heavy Industries Superlink SC-WBGW256 Manual de usuario

ZyXEL Communications
ZyXEL Communications ZYWALL2 ET 2WE Manual de usuario

Telsey
Telsey CPVA 500 - SIP Manual de usuario