CHANNEL SAFETY SYSTEMS t: 0845 884 7000 | w: www.channelsafety.co.uk
INSTRUCTION MANUAL - Issue 1 - 02/2014 | 8
Communication
Go on to the diagnostic mode to check the quality of the signal strength. Relocate if required.
Clear conguration
Should you wish to clear the conguration data to allow the units to be reused or relocated:
Master unit, MCP or Slave unit
• Open the MCP/Slave unit
• Press & hold the CONFIG button, the unit will bleep. Press & hold the VALID button. The unit will give a series of long bleeps followed by a series of short
bleeps followed by one long bleep. The unit is now decommissioned.
Smoke Detector
• The smoke detectors do not need to be‘de programmed’, simply de powering them using the battery isolate tag and then logging them on to a new
system carries out this function.
Operation
Manual Alarm
The general alarm is activated when one of the MCP’s is activated.
Resetting
Insert the black key in the MCP and turn 1/4 counter-clockwise to restore the normal position.
Testing
• Insert the key in the hole on the front face of the MCP.
• The MCP activates the alarm mode.
• Reset the MCP by turning 1/4 counter-clockwise
• Do not turn the key more than 1/4. Remove the key by turning clockwise.
Manual call point
Resetting
Once one of the MCP has been activated, reset it with the black key, turn the key 1/4 clockwise (remove key by turning clockwise) The alarm will silence in
about 15 seconds.
Internal LEDs
Amber LED: sends the alarm signal to the combined master unit
Red LED: the alarm is accepted by the master unit
Maintenance
We advise you to keep the equipment clean and to ensure that the installation is in a dry and ventilated area.
9V 6 LR 61 battery test
The system will automatically test the batteries every 12 hours.
Manual test
• Press the transparent switch on the master unit
• The indicators illuminate and will indicate the battery voltage
• The master unit emits a‘beep’at the same time as the indicators turns on to check that the loudspeaker works
Indication
The colour mode indicates the battery voltage:
As a precautionary measure, change the battery when the indicator is red. Always replace the batteries with the same type as originally supplied.
CONNECTION CONTINUED...
COLOUR VOLTAGE
Green 9 - 8 V
Orange 8 - 7.5 V
Red 7.5 - 7 V