Campbell CS15-L Manual de usuario

CS15-L Current Transformer
Revision: 10/08
Copyright © 2001-2008
Campbell Scientific, Inc.

Warranty and Assistance
The CS15-L CURRENT TRANSFORMER is warranted by CAMPBELL
SCIENTIFIC, INC. to be free from defects in materials and workmanship
under normal use and service for twelve (12) months from date of shipment
unless specified otherwise. Batteries have no warranty. CAMPBELL
SCIENTIFIC, INC.'s obligation under this warranty is limited to repairing or
replacing (at CAMPBELL SCIENTIFIC, INC.'s option) defective products.
The customer shall assume all costs of removing, reinstalling, and shipping
defective products to CAMPBELL SCIENTIFIC, INC. CAMPBELL
SCIENTIFIC, INC. will return such products by surface carrier prepaid. This
warranty shall not apply to any CAMPBELL SCIENTIFIC, INC. products
which have been subjected to modification, misuse, neglect, accidents of
nature, or shipping damage. This warranty is in lieu of all other warranties,
expressed or implied, including warranties of merchantability or fitness for a
particular purpose. CAMPBELL SCIENTIFIC, INC. is not liable for special,
indirect, incidental, or consequential damages.
Products may not be returned without prior authorization. The following
contact information is for US and International customers residing in countries
served by Campbell Scientific, Inc. directly. Affiliate companies handle
repairs for customers within their territories. Please visit
www.campbellsci.com to determine which Campbell Scientific company
serves your country. To obtain a Returned Materials Authorization (RMA),
contact CAMPBELL SCIENTIFIC, INC., phone (435) 753-2342. After an
applications engineer determines the nature of the problem, an RMA number
will be issued. Please write this number clearly on the outside of the shipping
container. CAMPBELL SCIENTIFIC's shipping address is:
CAMPBELL SCIENTIFIC, INC.
RMA#_____
815 West 1800 North
Logan, Utah 84321-1784
CAMPBELL SCIENTIFIC, INC. does not accept collect calls.

CS15-L Table of Contents
PDF viewers note: These page numbers refer to the printed version of this document. Use
the Adobe Acrobat® bookmarks tab for links to specific sections.
1. General Description.....................................................1
2. Specifications ..............................................................1
3. Installation....................................................................2
4. Wiring............................................................................ 2
5. Measurement Instruction ............................................2
5.1 Sample Program........................................................................................2
Figure
1. CS15-L Current Transformer .....................................................................1
i

This is a blank page.

CS15-L Current Transformer
1. General Description
The CS15-L uses a modified CR Magnetic’s CR8459 Current Transformer to
measure the approximate current over a range of 0 to 125 A. The CS15-L
outputs a millivolt signal allowing it to be directly connected to the CR2XX
dataloggers. The CS15-L is recommended for measurements that do not
require high accuracy.
FIGURE 1. CS15-L Current Transformer
2. Specifications
Example Applications:
•Motor or generator load conditions
•Efficiency studies
•Intermittent fault detection
•Rough submetering
Manufacturer’s Specifications
Frequency: 50 and 60 Hz
Insulation Resistance: 100 M ohm @ 500 VDC
High Potential: 2000 volts
Rated Current: 125 A
Storage Temperature: -25ºC to 70ºC
Operating Temperature: -25ºC to 55ºC
Case Material: Polypropylene Resin
Construction: Epoxy Encapsulated
Accuracy with 10 ohm
burden max. (resistive): typically ±5 percent of actual value with
provided multiplier
Dimensions: Outer diameter: 1.89” (4.8 cm)
Inner diameter: 0.75” (1.9 cm)
Depth: 0.67” (1.7 cm)
1

CS15-L Current Transformer
3. Installation
Mount the AC load wire through the hole of the CS15-L.
4. Wiring
The CS15-L uses a single-ended analog channel.
Red ---------------- Ex
White -------------- Single-Ended Channel
Black -------------- AG
Clear--------------- AG
5. Measurement Instruction
In the CR2XX datalogger the VoltSE instruction is used.
SCWIN users: This manual was written primarily for those
whose needs are not met by SCWin. Your procedure is much
simpler: just add the CS15-L (it’s in the Miscellaneous Sensors
folder), save your program, and follow the wiring shown in Step
2 of SCWin.
NOTE
The example measurement instructions that follow do not store
data to final storage. Additional instructions (DataTable and
CallTable for the CR2XX) are required to store data
permanently.
NOTE
5.1 Sample Program
This sample program measures a single CS15-L Current Transformer directly
connected to the SE 1 channel of the CR2xx.
The multiplier in this program example is 0.2 and is representative of one
application. The multiplier can be changed to match calibrated measurements.
You should use a multiplier that you have validated for your purposes.
EXAMPLE 1
‘CR200 Series
‘Program Name CS15-L.CR2
‘
‘Wiring:
‘SE1 White
‘Gnd Black
‘EX1 Red
‘Gnd Clear
‘
‘Declare Public Variables
2

CS15-L Current Transformer
Public Crnt_A
Public N
Dim Offset
Dim SumSqr
Dim mV
Dim I
Units Crnt_A = Amps
‘Main Program
BeginProg
N = 48
Scan (1,Sec)
‘CS15 Current Transformer measurement CS15_L:
Excitev (Ex1,mV2500)
Offset=0
SumSqr=Offset
For I=1 to N
VoltSe (mV,1,1,1.0,0)
SumSqr=SumSqr+mV^2
Offset=Offset+mV
Next
ExciteV (Ex1,0)
Crnt_A=SQR ((SumSqr – (Offset^2/N))/N) *0.2
If Crnt_A<0.2 then Crnt_A=0
‘Call Output Tables to store data
NextScan
EndProg
3

CS15-L Current Transformer
4
This is a blank page.

This is a blank page.

Campbell Scientific Companies
Campbell Scientific, Inc. (CSI)
815 West 1800 North
Logan, Utah 84321
UNITED STATES
www.campbellsci.com
Campbell Scientific Africa Pty. Ltd. (CSAf)
PO Box 2450
Somerset West 7129
SOUTH AFRICA
www.csafrica.co.za
Campbell Scientific Australia Pty. Ltd. (CSA)
PO Box 444
Thuringowa Central
QLD 4812 AUSTRALIA
www.campbellsci.com.au
Campbell Scientific do Brazil Ltda. (CSB)
Rua Luisa Crapsi Orsi, 15 Butantã
CEP: 005543-000 São Paulo SP BRAZIL
www.campbellsci.com.br
Campbell Scientific Canada Corp. (CSC)
11564 - 149th Street NW
Edmonton, Alberta T5M 1W7
CANADA
www.campbellsci.ca
Campbell Scientific Ltd. (CSL)
Campbell Park
80 Hathern Road
Shepshed, Loughborough LE12 9GX
UNITED KINGDOM
www.campbellsci.co.uk
Campbell Scientific Ltd. (France)
Miniparc du Verger - Bat. H
1, rue de Terre Neuve - Les Ulis
91967 COURTABOEUF CEDEX
FRANCE
www.campbellsci.fr
Campbell Scientific Spain, S. L.
Psg. Font 14, local 8
08013 Barcelona
SPAIN
www.campbellsci.es
Please visit www.campbellsci.com to obtain contact information for your local US or International representative.
Tabla de contenidos
Manuales populares de Transformador de otras marcas

Delta Electronics
Delta Electronics Current Sense Transformers TCE1906H Manual de usuario

Hobart
Hobart 6T28-600CL Manual de usuario

Shinkawa
Shinkawa LS Series Manual de usuario

Huawei
Huawei JUPITER-3000K-H1 Manual de usuario

Monacor
Monacor IMG STAGELINE LTR-102 Manual de usuario

Lionel
Lionel ZW Manual de usuario