Utility Distribution System
Operation and Maintenance
Manual

Page 1
509 Sharptown Road P.O. Box 345 Bridgeport, NJ 08014
Internet: http://caddycorp.com Phone: 856-467-4222
Table of Contents
Installation
Introduction ..................................................................................................................... 2
Island System Model ID .................................................................................................. 3
Overhead System Model OD .......................................................................................... 4
Wall System Model WL................................................................................................... 5
Electrical Connections..................................................................................................... 6
Electrical Fire Fuel Connections...................................................................................... 7
Operating Instructions
Connection Plate............................................................................................................. 9
Plumbing Connections & Gas Valve Operations........................................................... 10
Hose Assemblies .......................................................................................................... 11
General Plumbing System ............................................................................................ 12
Ventilator Water Wash System ..................................................................................... 13
Steam Purging System ................................................................................................. 15
Care and Cleaning of Stainless Steel Equipment ......................................................... 17
Product Warranty .......................................................................................................... 19
Inspect all equipment for damage immediately upon delivery or within the time specified by the
carrier.
In the unusual case that a claim for shipping damage is required, you must file the claim with the
carrier. Caddy can provide assistance in supplying information to support your claim.

Page 2
509 Sharptown Road P.O. Box 345 Bridgeport, NJ 08014
Internet: http://caddycorp.com Phone: 856-467-4222
Introduction
This manual will acquaint you with the operation and proper maintenance of your Caddy Utility Distribution System. It
is important that you read this manual thoroughly and follow its recommendations.
In certain instances, the manual makes references to features, which may or may not be part of your equipment. To
determine whether such references apply to you, please consult your submission and electrical drawings, which have
been prepared for you as part of this manual.
Thank you for selecting Caddy Corporation’s equipment. Your continued interest and satisfaction are always our
primary concern.

Page 3
509 Sharptown Road P.O. Box 345 Bridgeport, NJ 08014
Internet: http://caddycorp.com Phone: 856-467-4222
Utility Distribution System Model ID
Installation
1. Read the entire manual and study drawings before starting installation.
2. Check that all electrical and plumbing rough-ins are as specified and agree with the drawing.
3. The ID system consists of the following parts:
a. Riser
b. Raceway
c. Pedestal
4. Remove all access panels on raceway, riser and pedestal to reveal internal plumbing, electrical systems,
and internal flanges.
5. Place ID sections according to the drawing to determine the proper mounting position beneath the hood.
6. Once sections are in position, join field joints (if any) by bolting internal flanges together and applying
silicone sealant over seams.
7. Secure risers to floor with appropriate bolts.

Page 4
509 Sharptown Road P.O. Box 345 Bridgeport, NJ 08014
Internet: http://caddycorp.com Phone: 856-467-4222
Utility Distribution System Model OD
Installation
1. Read entire manual and study drawings before starting installation.
2. Check that all electrical and plumbing rough-ins are as specified and agree with the drawing.
3. The OD system consists of the following parts:
a. Riser
b. Raceway
4. Remove all access panels on raceway and riser to reveal internal plumbing, electrical systems, and internal
flanges.
5. Place OD sections according to the drawing to determine the proper mounting position.
6. Once sections are in position, join field joints (if any) by bolting internal flanges together and apply silicone
sealant over seams.
7. OD mounting procedure:
a. Position unit flush with finished ceiling (see submission drawing).
b. Bolt 3/8" mounting rod into holes provided in each riser.
c. Stabilize each 3/8” rod to cross member of ceiling.

Page 5
509 Sharptown Road P.O. Box 345 Bridgeport, NJ 08014
Internet: http://caddycorp.com Phone: 856-467-4222
Utility Distribution System Model WL
Installation
1. Read entire manual and study drawings before starting installation.
2. Check that all electrical and plumbing rough-ins are as specified and agree with the drawing.
3. The WL system consists of the following parts:
a. Riser
b. Raceway
c. Pedestal
4. Remove all access panels on raceway, riser and pedestal to reveal internal plumbing, electrical systems
and internal flanges.
5. Place WL sections according to the drawing to determine proper mounting positions.
6. Once sections are in position, join field joints (if any) by bolting internal flanges together and apply silicone
sealant over seams.
7. Secure pedestals to floor with appropriate bolts.

Page 6
509 Sharptown Road P.O. Box 345 Bridgeport, NJ 08014
Internet: http://caddycorp.com Phone: 856-467-4222
Electrical Connections
Installation
1. If system has field joint(s), wiring must be interconnected at the joint(s) before attaching main service.
a. Connect corresponding busbars together with the brass bolts and nuts that are provided.
b. Connect control wiring (if supplied) to corresponding terminals or quick disconnect device.
2. Connect the electrical service(s) to the system as follows:
a. Secure service conduit to the electrical housing. A service entrance knockout must be provided.
b. Attach main service wires to the corresponding terminals.
c. If fire fuel shut-off is provided, which is indicated by a red terminal block, proceed with the
instructions on Page 10.
d. Check and tighten all connections.
e. Connect all cord assemblies to the appropriate equipment as shown on submission drawing. Cut
cord assemblies if necessary to make neat appearance.
f. Wire conduit from vent light switch (if provided) to vent lights. See electrical drawing.
g. Wire to exhaust fan motor starter or control (if provided). See electrical drawing.

Page 7
509 Sharptown Road P.O. Box 345 Bridgeport, NJ 08014
Internet: http://caddycorp.com Phone: 856-467-4222
Electrical Fire Fuel Connections
Installation
Route three wires in ½" conduit (as shown on drawing) from the micro-switch in the fire control system (by others) to
the equipment shut-off terminal block (red) in the Utility Distribution System. DO NOT remove any existing wires
from terminals. Connect wires to the UNUSED posts of the Red terminal block as follows:
a. Connect the neutral wire to the terminal with the White wire.
b. Locate wire which supplies 120 volts during normal operating conditions (and is switched OFF when
fire control system is activated), and connect this to the terminal with the Black wire.
c. Locate wire which supplies 120 volts when fire control system is activated, and connect this to the
terminal with the Red wire.

Page 8
509 Sharptown Road P.O. Box 345 Bridgeport, NJ 08014
Internet: http://caddycorp.com Phone: 856-467-4222
Fire Fuel Shut-Off
(optional feature)
Operating Instructions
Electric
Actuation of the fire control system per the submission drawing will trip all circuit breakers and controls equipped with
the fire-fuel shut-off feature and de-energize the corresponding outlets. After the fire control system is returned to
normal operation conditions, these circuit breakers will be de-energized until the circuit breakers are reset.
Gas
Actuation of the fire control system per the submission drawing will stop the gas flow to all gas operated equipment.
After the fire control system is returned to normal operating condition, the button marked gas reset must be
depressed. This will reopen the gas solenoid valve(s) and allow gas to flow to all gas operated equipment.
IMPORTANT NOTE After the gas system has been reset, all pilot lights must be re-lit.
Remote Status Indicator Lights
These lights are located remotely from each connection plate; however, they are interconnected to each connection
plate and show circuit breaker ON or OFF status.
Ventilator Light Switch (Optional)
The ventilator light switch is located on the control panel. Be sure that the ventilator light switch circuit breaker,
which is located next to the light switch, is in the ON position.

Page 9
509 Sharptown Road P.O. Box 345 Bridgeport, NJ 08014
Internet: http://caddycorp.com Phone: 856-467-4222
Electrical Connection Plate
Operating and Installation
1. Turn all individual equipment controls to the OFF position before attempting to connect or disconnect any
cord and plug assembly. After the cord and plug assembly is connected, equipment may be turned ON.
2. The connection plate consists of the following:
a. Point-of-use circuit breaker
b. Outlet
c. Indicator Light
3. To energize the outlet, turn the circuit breaker to the ON position.
NOTE Upon initial start-up, the circuit breakers may occasionally require a “break in” procedure. Turn the circuit
breakers OFF and ON several times.
4. The equipment is now ready for operation.
Tabla de contenidos
Manuales populares de Hardware de computadora de otras marcas

EMC2
EMC2 VNX Series Manual del propietario

Panasonic
Panasonic DV0PM20105 Manual de usuario

Mitsubishi Electric
Mitsubishi Electric Q81BD-J61BT11 Manual de usuario

Gigabyte
Gigabyte B660M DS3H AX DDR4 Manual de usuario

Raidon
Raidon iT2300 Manual de usuario

National Instruments
National Instruments PXI-8186 Manual de usuario