BT Redcare Advanced Manual de usuario

Advanced and
Advanced Extra
Installation Guide

Contents
2 Introduction
5 Mounting And Wiring
9 Programming
14 Configuration
51 Disposal
52 Glossary Of Terms
53 Support

Introduction

3
Product Description
Figure 1 – Advanced and Advanced Extra unit (not to scale)
Advanced and Advanced Extra is a dual path alarm signalling unit for transmitting alarm signals from a customer’s alarm
panel, via the BT Redcare network, to an Alarm receiving Centre (ARC). Both Advanced and Advanced Extra units are IP
primary path with dual SIM 4G/2G mobile technology as the back up path. The units are designed for use in both Security
and Fire systems.
The unit communicates via the BT Redcare Network and a valid TA account must exist for the unit to communicate.
The TA account will have been populated with the serial number of the unit.
The unit has 16 general purpose alarm inputs, and 3 outputs, making it suitable for connection to most common alarm
panels.
The unit is supplied already fitted with two BT Redcare enabled SIM cards, one an EE UK fixed SIM and a UK Roaming SIM.
Both enabled for 4G/2G connectivity.

4
Specifications
Size: 95mm x 67mm x 17mm
Power: 9V – 30V
Current:
Alarm inputs: 16 General purpose inputs 1-16. (-0.5V – 30V)
Alarm threshold: High >2V, and Low <1.3V
Outputs: 3 x Relay NO C NC (Comms, Func, Fire)
RS232 port: remote panel access (UDL) and signalling to some intruder panel types
RS485 port: remote panel access (UDL) and signalling to some intruder panel types
Configuration: Using on board configuration buttons, web portal or App
Processor: STM32
Wireless module: ELS61
Average Average Max loading
Normal Operation (inc relays and dial capture operated)
IP/4G unit @12V 85mA 185mA
IP/4G unit @24V 45mA 100mA

Mounting and Wiring

6
Removal of Cover
The top cover can be removed by gently releasing each of the 4 clips on the base of the unit by pushing the clips outward
with a screwdriver blade.
Regular access to the inside of the unit should not be required, although occasional access may be required to access the
SIM cards.
Mounting
The unit should be mounted inside the alarm panel, or inside a separate powered housing, using the sticky mounting pads
supplied.
For security installations the enclosure must meet or exceed the protection requirements of the particular security grade
for the whole installation as per EN 50131-1.
For fire alarm panels the enclosure must meet the requirements of EN 54-21 7.3 (eg. IP30 or above). Enclosure
requirements for the signalling unit are the same as for the fire alarm panel itself and must meet EN 54-2. The enclosure
must restrict access to installer level 3. The enclosure must provide the facility to indicate the state of the fault and
acknowledge outputs on the signalling unit.
The supplied aerial should be mounted vertically outside of the housing by removing the adhesive backing.
Figure 2 - Layout of terminals (not to scale)

7
Connection Terminals
The screw terminals for the alarm inputs are suitable for use with a standard 3mm blade terminal screwdriver.
Power connections
Power to the unit is via 2 screw terminals at the centre, with positive to the right nearest Pin 9.
The supply voltage range is 9V to 30V. The unit is designed to be connected to the auxiliary power output on an
associated alarm panel, or separate powered enclosure. For use with intruder alarm panels the power supply must meet
the requirements of EN 50131-6.
For use with Fire alarm panels the power supply must meet the requirements of EN 54-4 and the unit must be mounted
in the same enclosure as the power supply from which it derives its power. Ensure the power source is sufficient to power
all devices connected. See the power requirements in the specification section for more information. The account at the
Alarm Receiving Centre (ARC) should be put “on test” before power up, as signals will be sent following initialisation.
Alarm inputs
The unit has 16 alarm inputs which are presented on screw terminals along the bottom of the unit. These are labelled as
Pin 1-8 and 9 -16.
By default the 16 alarm inputs require a positive condition to be presented to send an alarm. (Default = Positive applied).
This can be changed using the Pin Learn button or through the configuration menu. See later section on configuration.
Fig 3 - Alarm input allocations. (Functions must be agreed with your ARC)
1
2
3
4
5-10
11
13
14-16
Fire alarm (When programed Fire NAK and ACK outputs operate in conjunction with pin 1)
Fire Fault or Hold up alarm
Intruder alarm
Open / Close (Set / Unset) (Func out put can be set up as RPS in conjunction with pin 4)
General alarm
ATS input (BSIA F175 mode) (Can be reprogrammed as a normal alarm pin)
AC Fail alarm (has a 7 minute delay which can be altered in programming)
General alarm
Input (PIN) Use

8
Outputs
Three relay outputs are provided on screw terminals at the top of the unit.
Output 1 is Comms, Output 2 is Func, and Output 3 is Fire.
For fire alarm installations the indication of ‘acknowledgement of fire alarm’ and ‘SPT fault’ messages must be provided by
the fire panel into which the SPT is mounted. System fault indications which are notified by the line fault output
(Output 1) must be latched by the fire panel as required by EN 54-21.
See the further sections on outputs for a full explanation.
Serial data connections
The serial data connection labelled TX, RX, B and A is configurable for RS485 or RS232 connection depending on the
panel.
This is done in the configuration menu.
These ports allow serial alarm panel connection. See Panel Upload Download section.
Dial capture
The dial capture (Dial Cap) terminals enable interfacing with an alarm panel’s digital communicator. The alarm panel can
then send SIA, CID or Fast Format messages through the unit to the Alarm Receiving Centre.
Dial capture can also be used for upload download UDL allowing remote access with some types of alarm panel.
Ethernet connection
The Ethernet port needs to be connected to a suitable Ethernet network using CAT5 cable. For most IP installations,
a standard Ethernet patch cable can be used.
Aerial connection
Connect the supplied aerial to the MMCX connector on the top right of the unit. The aerial should be placed in a vertical
position that receives the best wireless coverage. Carry out a survey to establish the best location.
If necessary, a selection of high gain and extension aerials can be purchased from the BT Redcare shop at
https://www.btinstallershop.com

Programming
Otros manuales para Advanced
1
Este manual sirve para los siguientes modelos
1
Tabla de contenidos
Otros manuales de Transmisor de BT Redcare
Manuales populares de Transmisor de otras marcas

Dejero
Dejero EnGo 3x Manual de usuario

Rosemount
Rosemount 4600 Manual de usuario

Speaka Professional
Speaka Professional 2342740 Manual de usuario

trubomat
trubomat GAB 1000 Manual de usuario

Teledyne Analytical Instruments
Teledyne Analytical Instruments LXT-380 Manual de usuario

Rondish
Rondish UT-11 Manual de usuario













