BrookVent aircycle 4.1 Manual de usuario

[Type here]
in Heat Recovery Ventilation
Installation, maintenance & user manual
Applicable to the following aircycle 4.1 models:
PR DUCT C DE DESCRIPTI N
AS 90-0401-WDS-01 aircycle 4.1 c/w Integral Humidistat & Summer Bypass - Wall Mount
AS 90-0401-WDS-01V aircycle 4.1 c/w Integral Humidistat & Summer Bypass - Wall Mount Inverted
AS 90-0401-FDS-01 aircycle 4.1 c/w Integral Humidistat & Summer Bypass - Floor Mount
AS 90-0401-FDS-01V aircycle 4.1 c/w Integral Humidistat & Summer Bypass - Floor Mount Inverted
PERF RMANCE
UNRIVALLED

1
V. 4.1-04-08-21
brookvent.co.uk
C NTENTS
PLEASE KEEP THESE INSTRUCTI NS WITH THE PR DUCT.
Please read this manual fully prior to installing the MVHR unit.
1.0 Introduction ................................................................................................................................ 2
2.0 Safety .......................................................................................................................................... 3
3.0 Specifications/ Dimensions (mm) ...............................................................................................
4.0 Installation ................................................................................................................................ 10
.0 Electrical Connections/ Wiring ................................................................................................. 19
6.0 Controls and Settings ................................................................................................................ 21
7.0 Maintenance ............................................................................................................................. 38
8.0 User Operation .......................................................................................................................... 44
9.0 Trouble Shooting ....................................................................................................................... 46
10.0 Customer Support ..................................................................................................................... 47

2
V. 4.1-04-08-21
brookvent.co.uk
IMPORTANT
This appliance is not intended for use by persons (including children) with reduced
physical sensory or mental capabilities, or lack of experience and knowledge, unless
they have been given supervision or instruction concerning use of the appliance by a
person responsible for their safety.
1.0 Introduction
The Brookvent aircycle 4.1 is a highly efficient Mechanical Heat Recovery Ventilation
(HRV/MHRV) system, specifically designed for medium to large dwellings and apartments.
The system should be run continuously 24 hours a day and should only be disconnected
by a competent person during service or maintenance.
Heat Recovery ventilation works best in new homes, which are extremely airtight and
have high efficiency ratings. These dwellings require a high level of fresh air to ensure a
healthy living environment.
The system works by drawing stale air from ‘wet rooms’ such as Bathrooms, WC’s and
Kitchens, recovering up to 94% of the heat from this air using a highly efficient heat
exchanger, before expelling waste air from the home. Simultaneously, fresh air is drawn
into the home, filtered, and warmed by the recovered heat and is supplied into the
‘habitable rooms’ such as bedrooms, dining rooms and living rooms.
1.1 Model Variations
This installation manual refers to the Brookvent aircycle 4.1 and pertains to the
following models:
PR DUCT C DE DESCRIPTI N
AS 90-0401-WINS-01 aircycle 4.1 c/w Integral Humidistat - Wall Mount
AS 90-0401-FINS-01 aircycle 4.1 c/w Integral Humidistat - Floor Mount
AS 90-0401-WDS-01 aircycle 4.1 c/w Integral Humidistat - Wall Mount
AS 90-0401-FDS-01 aircycle 4.1 c/w Integral Humidistat - Floor Mount

3
V. 4.1-04-08-21
brookvent.co.uk
1.2 Product Guarantee
This product is guaranteed against defects for a period of 5 years from date of purchase
with the first year covering parts and labour and the remaining 4 years covering parts
only.
In the instance of a defect, Brookvent may repair the product, replace the product free of
charge or refund the cost of the product at Brookvent’s own discretion. In terms of
installation, operation and maintenance please follow all instructions provided. If this
product has been misused, not properly installed, not properly maintained, or handled
carelessly it may lead to this guarantee being declared void.
Brookvent does not accept liability for damage caused by non-observance of the
installation instructions. Service activities must be carried out by Brookvent or by
competent installers using original Brookvent parts. This guarantee does not affect your
statutory right as a consumer.
Brookvent operate a policy of continuous innovation and improvement and thus
reserve the right to alter product specifications and appearances without notice.
2.0 Safety
The following information must be read carefully to ensure safe installation and
operation of the Brookvent HRV system.
2.1 General Safety
Do not use this appliance for functions other than those described in this booklet.
Never touch the appliance with wet hands.
The unit is only suitable for 230 VAC/50Hz electric mains.
Never modify the fan or electronics, all repairs must be conducted by Brookvent.
Never connect the power if electronics cover is not fitted.
Do not store flammable products in close proximity to the unit.
If cleaning/ dusting the external surface, do so with a dry cloth only.
Isolate power before removing any panels/covers (excluding filters).
Never remove the heat recovery core while the fans are running. NB. It can take
some time for the fans to come to a stop once power has been isolated.

4
V. 4.1-04-08-21
brookvent.co.uk
2.2 Responsibility of the Installer
Correct Installation, balancing and commissioning of the MHRV unit as per the
requirements of this document.
Record measured air flow volumes on each of the valves at high and low rate.
Compliance to requirements and local additional rules.
Explanation of the ventilation system to the user.
Warning for the user, to check or replace the air filters on time.
All the above, as set out in the latest edition of the Domestic Ventilation
Compliance Guide and the SAP Appendix Q – Installation Guide and Checklist
specific to the UK market.
2.3 Responsibility of the ccupant
Replacement of the filters as per the recommended/ required interval.
Cleaning the valves in the rooms regularly to prevent blockage.
To ensure that the system is functioning properly on a regular basis
To use manual boost switches (where provided) to prevent build-up of pollutants
or mould growth.
IMPORTANT
Dirty or clogged filters may cause inadequate ventilation in the home which may lead to
air quality issues. It is important that the filters are changed at least once per year or as
required.
In new build properties it may be prudent to check/ change your filters after the first 3
months of occupancy depending on the amount of residual ‘building dust’ present
within the property. Failure to do so will affect your warranty.
Filters can be purchased directly online from brookvent.co.uk

V. 4.1-04-08-21
brookvent.co.uk
3.0 Specifications/ Dimensions (mm)
FRONT SIDE
TOP

6
V. 4.1-04-08-21
brookvent.co.uk
3.1 Duct Connections

7
V. 4.1-04-08-21
brookvent.co.uk
3.2 Detailed Specification
Weight: 29kg
Materials:
• Main enclosure: High density, impact resistant EPP (Expanded Polypropylene)
• PCB & control panel enclosure: ABS FR
• Drainage tray: PP
• Filters: Polyester media (G3)
• Filter cover: Rubber
• Mounting Bracket: Zinc Plated Steel
• Fan Scrolls: ABS
Electrical:
• 230v EC Low energy, backward curved centrifugal fans
• PCB c/w digital controls
• Supplied complete with 4 core flying lead: (Live: Brown), (Neutral: Black),
(Earth: Yellow & Green), (230v Switched Live (Boost): Grey)
• Plug and play components for easy maintenance
Installation: Wall or Floor Mount
Standards:
Fully complies with Building Regulations for UK & Ireland
SAP Appendix Q Listed | Energy Savings Trust Best Practice | CE
Guarantee Period: 5 Years

8
V. 4.1-04-08-21
brookvent.co.uk
3.3 SAP Appendix Q Results
SAP 2005 (See SAP - PCDB for further details) http://www.ncm-pcdb.org.uk/sap/
SAP 2012 (See SAP - PCDB for further details) http://www.ncm-pcdb.org.uk/sap/
Exhaust Terminal
Configuration
Airflow Rate
(l/s)
100% Variable
Specific Fan
Power
(W/l/s)
Heat Exchange
Efficiency (%)
Energy Savings
Trust Best
Practice
Compliance
Kitchen + 1 Wet
Room 15 0.48 94 YES
Kitchen + 2 Wet
Room 21 0.42 93 YES
Kitchen + 3 Wet
Room 27 0.41 92 YES
Kitchen + 4 Wet
Room 33 0.45 91 YES
Kitchen + 5 Wet
Room 39 0.49 90 YES
Kitchen + 6 Wet
Room 45 0.56 90 YES
Kitchen + 7 Wet
Room 51 0.65 89 YES
Exhaust Terminal
Configuration
Airflow Rate
(l/s)
100% Variable
Specific Fan
Power
(W/l/s)
Heat Exchange
Efficiency (%)
Energy Savings
Trust Best
Practice
Compliance
Kitchen + 1 Wet
Room 21 0.45 93 YES
Kitchen + 2 Wet
Room 29 0.45 92 YES
Kitchen + 3 Wet
Room 37 0.49 91 YES
Kitchen + 4 Wet
Room 45 0.58 90 YES
Kitchen + 5 Wet
Room 53 0.67 88 YES
Kitchen + 6 Wet
Room 61 0.83 87 YES
Kitchen + 7 Wet
Room 69 0.99 86 YES

9
V. 4.1-04-08-21
brookvent.co.uk
3.4 Airflow: Pressure/ Performance Curve
3.5 Acoustic Performance
0
100
200
300
400
00
600
700
0 20 40 60 80 100 120 140 160 180
Pressure Pa
Flow l/s
Pressure Vs Flow
Este manual sirve para los siguientes modelos
4
Tabla de contenidos
Otros manuales de Admirador de BrookVent

BrookVent
BrookVent AF 90-DMEV-100 Manual de usuario

BrookVent
BrookVent AIRVENT SM ACOUSTIC Instrucciones de funcionamiento

BrookVent
BrookVent BTP EC 100 Instrucciones de montaje

BrookVent
BrookVent AS 92-ACE-H-125 Guía del usuario

BrookVent
BrookVent Aircycle 1.1 Manual de instrucciones

BrookVent
BrookVent airstream DMEV 100 HT Instrucciones de montaje

BrookVent
BrookVent AIRSTREAM XE+ Instrucciones de montaje

BrookVent
BrookVent AirVent SM 1200+ Manual de usuario

BrookVent
BrookVent 90-0103-WDS-01 Instrucciones de montaje