BOSSCO 355AA DN15 Manual de usuario

AUTOMATIC NORMALLY CLOSED SOLENOID VALVE FOR GAS
355AA
DN 15 - DN 20 - DN 25
CE-51CT4873/ED05
CE-51CM4100/ED05
MADE IN ITALY
EN
EC approval according to EN 161, compliant with Regulation (EU) 2016/426

2
EN
INDEX
pag.
English ........................................................................................................................................................ 3
Drawings...................................................................................................................................................... 14
Dimensions (table 1) ..................................................................................................................................... 16
Spare coils and connectors (table 2) ............................................................................................................... 17
SIL Level (table 3) ......................................................................................................................................... 18
Diagram ....................................................................................................................................................... 19

3
EN
1.0 GENERAL INFORMATION
This manual shows you how to safely install, operate and use the device.
The instructions for use ALWAYS need to be available in the facility where the device is installed.
ATTENTION: installation/wiring/maintenance need to be carried out by qualified staff (as explained
in section 1.3) using appropriate personal protective equipment (PPE).
For any information pertaining to installation/wiring/maintenance or in any case problems that cannot be resolved with the use
of the instructions, it is possible to contact the manufacturer from the address and phone numbers provided on the last page.
1.1 DESCRIPTION
Normally closed automatic fast opening solenoid valves for gas. They open the flow of gas when the coil is electrically powered
and close them when power is disconnected. They can be controlled by pressure switches, thermostats, etc.
They can be equipped with CPI switches to control the valve’s obturator position (closed) remotely. The CPI can also be
installed at a later time ONLY IF the device is set-up properly (cap under the valve body). Further information regarding the
CPI switch is available in 6.0.
Reference standards: EN 161 - EN 13611.
1.2 KEY OF SYMBOLS
ATTENTION: Attention
is drawn to the technical
details intended for
qualified staff.
DANGER: In the event of
inobservance, this may cause damage
to tangible goods, to people and/or
pets.
DANGER: In the event
of inobservance, this may
cause damage to tangible
goods.

4
EN
1.3 QUALIFIED STAFF
These are people who:
•Are qualified to carry out product installation, assembly, start-up and maintenance;
•Know the regulations in force in the region or country pertaining to installation and safety;
•Are trained in first aid.
1.4 USING NONORIGINAL SPARE PARTS
•To perform maintenance or replace parts (ex. coil, connector, etc.) ONLY manufacturer-recommended parts can be used.
Using different parts not only voids the product warranty, it could compromise correct device operation.
•The manufacturer is not liable for malfunctions caused by unauthorised tampering or use of non-original parts.
1.5 IMPROPER USE
•The product must only be used for the purpose it was built for.
•It is not allowed to use different fluids than those expressly stated.
•The technical data set forth on the rating plate must not be exceeded whatsoever. The end user or installer is in charge of
implementing proper systems to protect the device, which prevent exceeding the maximum pressure indicated on the rating
plate.
•The manufacturer is not responsible for any damage caused by improper use of the device.

5
EN
2.0 TECHNICAL DATA
• Use : non-aggressive gases of the three families (dry gases)
• Ambient temperature (TS) : -20 ÷ +60 °C
• Supply voltages (see table 2) : 24 V/50 Hz - 110 V/50-60 Hz - 230 V/50-60 Hz*
• Power supply tolerance : -15% ... +10%
• Electric wiring : cable gland M20x1.5
• Absorbed power : see table 2
• Maximum operating pressure : (DN 15 - DN 20) 200 mbar
: (DN 25) 500 mbar
• Opening time : <1 s
• Closing time : <1 s
• Protection rating : IP65
• Class : A
• Mechanical resistance : Group 2
• Rp Threaded connections : (DN 15 - DN 20 - DN 25) according to EN 10226
• NPT threaded or ANSI 150 flanged connections : on request
• Filter element : 1 mm wire mesh
• In compliance with : Regulation (EU) 2016/426 (Appliances burning gaseous fuels)
Directive EMC 2014/30/EU - Directive LVD 2014/35/EU
Directive RoHS II 2011/65/EU
* Only single-phase, the device does not work if powered with three-phase voltage.

6
EN
2.1 MODEL IDENTIFICATION
See Table 2 on page 17.
2.2 SIL LEVEL
The SIL level of the stand-alone solenoid valve is SIL 2; when two solenoids are installed in series and the relative leak test
(Valve Proving System), certified according to EN 1643, the achieved level is SIL 3, as set forth in EN 676:2008. The solenoid
valve has PL d level. For further data refer to the SIL LEVEL table (table 3).
3.0 COMMISSIONING THE DEVICE
3.1 OPERATIONS PRIOR TO INSTALLATION
•It is necessary to close the gas upstream of the valve prior to installation;
•Make sure that the line pressure DOES NOT EXCEED the maximum pressure declared on the product label;
•Any protective caps (if any) must be removed prior to installation;
•Valve pipes and insides must be clear of any foreign bodies;
•Make sure that the pipe thread is not too long, to prevent damaging the body of the device when screwing it on;
•In accordance with EN 161 a suitable filter must be installed upstream of a gas closing safety device;
•With outdoor installation, it is advisable to provide a protective roof to prevent rain from damaging the electrical parts of
the device;
•Prior to carrying out any electrical wiring operations, make sure that the mains voltage matches the supply voltage indicated
on the product label;
•Cut out power prior to proceeding with wiring;
•According to the plant geometry, check the risk of explosive mixture arising inside the piping;
•If the solenoid valve is installed near other devices or as part of an assembly, compatibility between the solenoid
valve and this other device must be evaluated beforehand;
•Avoid installing the solenoid valve near surfaces that could be damaged by the coil temperature;
• Provide a protection against impacts or accidental contacts if the solenoid valve is accessible to unqualified personnel.

7
EN
3.2 INSTALLATION (see example in 3.4)
•Assemble the device by screwing it, with the correct seals, onto the plant with pipes and/or fittings whose
threads are consistent with the connection being attached;
•Do not use the coil (11 ) as a lever to help you screw it on, only use the specific tool;
•The arrow, shown on the body (4) of the device, needs to be pointing towards the application;
•The device can also be installed vertically without prejudicing correct operation. It cannot be put in upside
down (with the coil (11 ) pointing downwards);
•During installation, avoid debris or metal residues from getting into the device;
•To guarantee mechanical tension-free assembly, we recommend using compensating joints, which also adjust to the pipe’s
thermal expansion;
•If the device is to be installed in a ramp, it is the installer’s responsibility to provide suitable supports or correctly sized
supports, to properly hold and secure the assembly. Never, for any reason whatsoever, leave the weight of the ramp only on
the connections (threaded or flanged) of the individual devices;
•In any case, following installation, check the tightness of the plant;
•Wiring cannot have cables connected directly to the coil. ALWAYS and ONLY use the connector identified by the
manufacturer;
•Before wiring the connector (1), unscrew and remove the central screw (13). Use proper cable terminals (see figures on
page 21). NOTE: Connector (1) wiring must be do ensuring a product rating of IP65;
•Wire the connector (1) with 3x0.75mm² cable with external Ø 6.2 to 8.1 mm. The cable must have double sheathing, be
suitable for use outdoors, with minimum voltage of 500V, and minimum temperature of 105°C;

8
EN
•Connect terminals 1 and 2 to the power supply and the earth cable to terminal .
•Secure the connector (1) to the coil (11 ), tightening (recommended tightening torque 0.4 N.m ± 10%) the centre screw (13);
•The valve needs to be earthed either through the pipe or through other means (ex. cable jumpers).
3.3
INSTALLATION IN PLACES WHERE THERE IS THE RISK OF EXPLOSION (DIRECTIVE 2014/34/EU)
The solenoid valve is not suitable for use in potentially explosive areas.

9
EN
123
5
47
6
13
piping
applicaon
discharge in open air
internal thermal unit
external roof
8
9
Power
12
11
10
3.4 GENERIC EXAMPLE OF AN INSTALLATION
(Burner Gas Train)
1. Gas filter
2. OPSO shut off valve
3. Pressure regulator
4. Minimum pressure switch
5. 355AA fast opening
automatic solenoid valve
6. Maximum pressure switch
7. Slow opening automatic solenoid valve
8. External reset
9. Burner control
10. Valve proving system
11. Relief valve
12. Pressure gauge and relative button
13. Gas detector

10
EN
4.0 FIRST STARTUP
• Before start-up make sure that all of the instructions on the rating plate, including the direction of flow, are observed;
•After having gradually pressurised the system, check tightness and operation of the solenoid valve, electrically
powering / disconnecting the connector ONLY IF connected to the coil.
IMPORTANT NOTE: Do not use the connector as a switch to open/close the solenoid valve.
4.1 - RECOMMENDED PERIODIC CHECKS
•Use a suitable calibration tool to ensure the bolts are tightened as indicated in 3.2;
•Check tightness of the flanged/threaded connections on the system;
•Check tightness and operation of the solenoid valve;
It is the responsibility of the final user or installer to define the frequency of these checks based on the severity of the service conditions.
5.0 MAINTENANCE
No maintenance operations need to be carried out inside the device.
If the coil and/or connector need to be replaced:
•Before performing any operation, make sure that the device is not electrically powered;
•Since the coil is also suitable to be permanently powered, high coil temperature in case of continuous operation is
entirely normal. It is advisable to avoid touching the coil with bare hands after a continuous power supply lasting longer
than 20 minutes. In case of maintenance, wait for the coil to cool down or, if necessary, use suitable protections;
NOTE: if the coil (11 ) needs to be changed following an electrical failure, we recommend changing the connector (1) as well. The coil
and/or connector replacement operations need to be carried out taking care to ensure the product’s IP65 rating.
Este manual sirve para los siguientes modelos
11
Tabla de contenidos
Otros manuales de Unidad de control de BOSSCO
Manuales populares de Unidad de control de otras marcas

Festo
Festo Compact Performance CP-FB6-E Manual de lista de piezas

Elo TouchSystems
Elo TouchSystems DMS-SA19P-EXTME Manual de usuario

JS Automation
JS Automation MPC3034A Manual de usuario

JAUDT
JAUDT SW GII 6406 Series Guía rápida

Spektrum
Spektrum Air Module System Manual de usuario

BOC Edwards
BOC Edwards Q Series Manual de usuario