OIL/NG/LP FIRED SPACE HEATER: BLAZE 600 D/G TURBO
REPORT # 0367MH007S
Installation Instructions-Manual-Maintenance-Parts List
CAUTION: DO NOT TAMPER WITH HEATER OR ITS CONTROLS. CALL A QUALIFIED SERVICE TECHNICIAN
Retain manual for future reference June 17, 2016
CERTIFIED FOR USE IN CANADA AND THE U.S.A.

CAMPO EQUIPMENT CO. LTD. (ECOBLAZE)
6 Carson Court, Brampton, ON, CANADA, L6T 4P8
Tel: (905) 793-2525 | Fax: (905) 793-8768 | www.campoequipment.com Page | 2

CAMPO EQUIPMENT CO. LTD. (ECOBLAZE)
6 Carson Court, Brampton, ON, CANADA, L6T 4P8
Tel: (905) 793-2525 | Fax: (905) 793-8768 | www.campoequipment.com Page | 3
READ INSTRUCTIONS PRIOR TO STARTING HEATERS
THIS HEATER IS DESIGNED AND APPROVED FOR USE AS A CONSTRUCTION HEATER
UNDER STANDARD ANSI Z83.7-2011/CSA2.14-2011, UL 733-2013 and CAN/CSA B140.8-
1967(R2015)
THESE HEATERS ARE SUITABLE FOR OUTDOOR USE
THE REQUIREMENTS OF LOCAL AUTHORITIES HAVING JURISDICTION SHALL BE
FOLLOWED
BLAZE 600 G TURBO
NOTE: THIS HEATER IS INTENDED FOR USE PRIMARILY AS TEMPORARY HEATING OF BUILDINGS UNDER
CONSTRUCTION, ALTERATION OR REPAIR
THIS UNIT IS APPROVED FOR USE WITH PROPANE OR NATURAL GAS. NEVER ATTEMPT TO BURN
GARBAGE OR PAPER IN THE HEATER AND REMOVE ALL PAPER AND RAGS FROM AROUND THE
HEATER. FOR YOUR SAFETY, DO NOT STORE OR USE GASOLINE OR OTHER FLAMMABLE
LIQUIDS OR VAPOURS IN THE VICINITY OF THE HEATER.
DO NOT TAMPER WITH THE HEATER AND CONTROLS! THE HEATER MUST BE SERVICED BY
QUALIFIED SERVICE PERSONNEL.
WARNING: THOSE WHO INSTALL THE HEATER MUST HAVE THE TRAINING AND EXPERIENCE
NECESSARY TO DO SO. READ THIS MANUAL CAREFULLY. FAILURE TO PROPERLY INSTALL
AND SETUP THE HEATER COULD RESULT IN PROPERTY DAMAGE, PERSONAL INJURY, OR LOSS
OF LIFE. THE QUALIFIED SERVICE PERSONNEL PERFORMING THIS WORK ASSUMES A SERIOUS
RESPONSIBILITY FOR THE CORRECT INSTALLATION, SETUP, AND START-UP OF THE HEATER.
THIS HEATER IS DESIGNED AND APPROVED FOR USE AS A CONSTRUCTION HEATER IN
ACCORDANCE WITH STANDARD ANSI Z83.7-2011/CSA2.14-2015. CHECK WITH YOUR
LOCAL FIRE SAFETY AUTHORITY IF YOU HAVE QUESTIONS ABOUT APPLICATIONS.
WARNING: INTENDED USE IS PRIMARILY THE TEMPORARY HEATING OF BUILDINGS UNDER
CONSTRUCTION, ALTERATION, REPAIR OR EMERGENCIES ONLY.
WARNING: ALWAYS PROVIDE ADEQUATE VENTILATION. MINIMUM ACCEPTABLE VENTILATION
REQUIRED: 1 SQ. IN. OF FRESH AIR MUST BE SUPPLIED FOR EVERY 1000 BTU/H OF HEAT.
WARNING: THIS HEATER SHALL BE INSTALLED SUCH THAT IT IS NOT DIRECTLY EXPOSED TO
WATER SPRAY, AND/OR DRIPPING WATER.
CHECK WITH YOUR LOCAL FIRE SAFETY AUTHORITY IF YOU HAVE QUESTIONS ABOUT
APPLICATIONS
THESE INSTRUCTIONS HAVE BEEN THOROUGHLY WRITTEN, BUT THEY CANNOT COVER EVERY
PECULIAR INSTALLATION AND CONTINGENCY. THEREFORE IF THERE IS ANY DOUBT AS TO

CAMPO EQUIPMENT CO. LTD. (ECOBLAZE)
6 Carson Court, Brampton, ON, CANADA, L6T 4P8
Tel: (905) 793-2525 | Fax: (905) 793-8768 | www.campoequipment.com Page | 4
INTERPRETATION OF ANY REQUIREMENTS, CONTACT YOUR LOCAL AUTHORITY HAVING
JURISDICTION, YOUR LOCAL DISTRIBUTOR, OR THE FACTORY.
INSTALLATION REGULATIONS:
1.) THE INSTALLATION OF THE UNIT SHALL BE IN ACCORDANCE WITH THE REGULATIONS OF
THE AUTHORITIES HAVING JURISDICTION.
WIRING: ALL INTERNAL WIRING OF THE HEATER IS COMPLETED BY THE MANUFACTURER. ALL
EXTERNAL WIRING MUST CONFORM TO EXISTING ELECTRICAL CODES AS LAID DOWN BY THE
AUTHORITIES HAVING JURISDICTION.
THE INSTALLATION OF THIS HEATER FOR USE WITH NATURAL GAS SHALL CONFORM WITH
LOCAL CODES OR, IN THE ABSENCE OF CODES, WITH THE NATIONAL FUEL GAS CODE ANSI
Z223.1/NFPA 54 AND THE NATURAL GAS AND PROPANE INSTALLATION CODE, CSA B149.1-00.
THIS HEATER MUST BE INSTALLED BY A QUALIFIED GAS TECHNICIAN, FOLLOWING LOCAL
CODES PUBLISHED BY THE AUTHORITY HAVING JURISDICTION. ALL INSTALLATIONS
PERFORMED IN THE STATE OF MASSACHUSETTS MUST BE COMPLETED BY A QUALIFIED
PLUMBER AND GAS FITTER OF THE STATE OF MASSACHUSETTS.
THE INSTALLATION OF THIS HEATER FOR USE WITH A PROPANE TANK OR CYLINDER SHALL
CONFORM WITH LOCAL CODES OR IN THE ABSENCE OF LOCAL CODES, WITH THE STANDARD
FOR THE STORAGE AND HANDLING OF LIQUEFIED PETROLEUM GASES, ANSI/NFPA 58 AND THE
NATURAL GAS AND PROPANE INSTALLATION CODE, CSA B149.1
THIS HEATER MUST BE LOCATED AT LEAST 10FT (3M) FROM ANY PROPANE GAS CYLINDER.
THIS HEATER SHALL NOT BE DIRECTED TOWARD ANY PROPANE GAS CONTAINER WITHIN 20FT
(6M).
OTHER STANDARDS GOVERN THE USE OF FUEL GASES AND HEAT PRODUCING
PRODUCTS IN SPECIFIC APPLICATIONS. YOUR LOCAL AUTHORITY CAN ADVISE YOU
ABOUT THESE.
READ INSTRUCTIONS PRIOR TO STARTING HEATERS
BLAZE 600 D TURBO
THIS UNIT IS APPROVED FOR USE WITH NO. 1 AND NO. 2 FUEL OIL. NEVER USE GASOLINE OR
CRANKCASE OIL WHICH MAY CONTAIN GASOLINE AS FUEL FOR THE HEATER. NEVER ATTEMPT
TO BURN GARBAGE OR PAPER IN THE HEATER AND REMOVE ALL PAPER AND RAGS FROM
AROUND THE HEATER. FOR YOUR SAFETY, DO NOT STORE OR USE GASOLINE OR OTHER
FLAMMABLE LIQUIDS OR VAPOURS IN THE VICINITY OF THE HEATER.
FOR YOUR SAFETY DO NOT ATTEMPT TO START THE HEATER IF:
1.) EXCESS OIL HAS ACCUMULATED
2.) THE HEATER IS FULL OF VAPOUR
3.) THE COMBUSTION CHAMBER IS EXTREMELY HOT

CAMPO EQUIPMENT CO. LTD. (ECOBLAZE)
6 Carson Court, Brampton, ON, CANADA, L6T 4P8
Tel: (905) 793-2525 | Fax: (905) 793-8768 | www.campoequipment.com Page | 5
DO NOT TAMPER WITH THE HEATER AND CONTROLS! THE HEATER MUST BE SERVICED BY
QUALIFIED SERVICE PERSONNEL.
WARNING: THOSE WHO INSTALL THE HEATER MUST HAVE THE TRAINING AND EXPERIENCE
NECESSARY TO DO SO. READ THIS MANUAL CAREFULLY. FAILURE TO PROPERLY INSTALL
AND SETUP THE HEATER COULD RESULT IN PROPERTY DAMAGE, PERSONAL INJURY, OR LOSS
OF LIFE. THE QUALIFIED SERVICE PERSONNEL PERFORMING THIS WORK ASSUMES A SERIOUS
RESPONSIBILITY FOR THE CORRECT INSTALLATION, SETUP, AND START-UP OF THE HEATER.
THESE INSTRUCTIONS HAVE BEEN THOROUGHLY WRITTEN, BUT THEY CANNOT COVER EVERY
PECULIAR INSTALLATION AND CONTINGENCY. THEREFORE IF THERE IS ANY DOUBT AS TO
INTERPRETATION OF ANY REQUIREMENTS, CONTACT YOUR LOCAL AUTHORITY HAVING
JURISDICTION, YOUR LOCAL DISTRIBUTOR, OR THE FACTORY.
IMPORTANT: IF YOU OBSERVE THE PRIMARY CONTROL IS LOCKED OUT, PUSH THE RED RESET
BUTTON ONLY ONCE. IF THE BURNER DOES NOT RE-LIGHT, DO NOT PUSH THE BUTTON A
SECOND TIME OR EXCESS OIL WILL ACCUMULATE IN THE COMBUSTION CHAMBER—CALL A
QUALIFIED SERVICE PERSON.
INSTALLATION REGULATIONS:
1.) INSTALLATION SHOULD BE IN ACCORDANCE WITH ALL LOCAL AND NATIONAL
REGULATIONS.
2.) IN CANADA USE THE CSA B139-1962 INSTALLATION CODE FOR OIL BURNING EQUIPMENT,
FOR RECOMMENDED INSTALLATION PRACTICE.
WIRING: ALL INTERNAL WIRING OF THE HEATER IS COMPLETED BY THE MANUFACTURER. ALL
EXTERNAL WIRING MUST CONFORM TO EXISTING ELECTRICAL CODES AS LAID DOWN BY THE
AUTHORITIES HAVING JURISDICTION. IN CANADA, REFER TO CSA C22.1 CANADIAN ELECTRICAL
CODE AND IN THE UNITED STATES AS OUTLINED IN THE BOCA CODE, OR THE NFPA 70 NATIONAL
ELECTRICAL CODE.
WARNING: LACK OF COMBUSTION AIR CAN CAUSE A DIRTY FIRE, ODOURS IN ENCLOSED
SPACES, AND BACKDRAFTING, POTENTIALLY RESULTING IN NAUSEA OR ASPHYXIATION OF
THE OCCUPANTS.
BLAZE 600 D/G
SPECIFICATIONS
BLAZE 600G-
BECKETT (NG/LP)
BLAZE 600D-
BECKETT (OIL)
Burner Make & Model CG10 CF800
Voltage 120V
120V
Input (BTU/h) 575,000 NO.1 (581,699) @ 175 PSI
NO.2 (588,000) @ 175 PSI
CFM/AMPS 5,500/11.5 5,500/11.5
MOTOR HP
1
1

CAMPO EQUIPMENT CO. LTD. (ECOBLAZE)
6 Carson Court, Brampton, ON, CANADA, L6T 4P8
Tel: (905) 793-2525 | Fax: (905) 793-8768 | www.campoequipment.com Page | 6
Ductability
(Return/Supply)
Static Pressure
24ft/150ft
upto 4”
24ft/150ft
upto4”
Outlet Duct Size
2 X 12" OR 1 X 16
2 X 12" OR 1 X 16
Inlet Duct Size
2 X 12" OR 1 X 16
2 X 12" OR 1 X 16
Gas Conversion Easy switch over
Blue handle Ball
Valve on Gas
manifold.
Closed position:
Propane
Open position:
Natural Gas
N/A
Manifold pressure “W.C.
2.9”NG or 2.9”LP
(Pressure to be set
before NG/LP
switchover valve
and after adjusting
valve on manifold-
1.7” if set after the
N/LP Switchover
valve)
N/A
Minimum/Maximum
Supply Pressure “W.C.
8/10
FOR NG AND LP
OPERATION
N/A
Nozzle
N/A
2.75 X 60b
Pump Pressure
N/A
175
GPH
N/A
4.2
Fuel
NG or LP
No. 1 or No. 2 /
Kerosene or Furnace
Oil
Head Setting
10.3 (10.1 head)
1
Air Setting (Beckett-
Shutter/Band)
10/0 3/0

CAMPO EQUIPMENT CO. LTD. (ECOBLAZE)
6 Carson Court, Brampton, ON, CANADA, L6T 4P8
Tel: (905) 793-2525 | Fax: (905) 793-8768 | www.campoequipment.com Page | 7
CONNECTING THE CYLINDER
Clearance to LP containers: 10 feet (3M)
IF CYLINDERS ARE USED TO SUPPLY THE HEATER, NO CYLINDERS SMALLER THAN 100
LB CAPACITY SHALL BE USED. THESE CYLINDERS MUST SUPPLY A VAPOUR
WITHDRAWAL ONLY.
1.) ALL CYLINDER CONNECTIONS MUST BE MADE USING A WRENCH TO TIGHTEN THE
POL FITTING.
2.) BE SURE THAT THE CYLINDER VALVE IS IN THE CLOSED POSITION WHEN
CONNECTING OR DISCONNECTING THE CYLINDER.
3.) PROPER PROCEDURE FOR GAS LEAK TESTING: A SOAP AND WATER SOLUTION
MUST BE APPLIED TO ALL CONNECTIONS IN ORDER TO LEAK CHECK THE SYSTEM.
4.) THE HOSE ASSEMBLY MUST BE VISUALLY INSPECTED PRIOR TO EACH USE OF
THE HEATER.
THE GAS MUST BE TURNED OFF AT THE PROPANE SUPPLY CYLINDER(S) WHEN THE
HEATER IS NOT IN USE. WHEN THE HEATER IS TO BE STORED INDOORS, THE
CONNECTION BETWEEN THE PROPANE SUPPLY CYLINDER(S) AND THE HEATER MUST
BE DISCONNECTED AND THE CYLINDERS REMOVED FROM THE HEATER AND STORED IN
ACCORDANCE WITH STANDARDS FOR THE STORAGE AND HANDLING OF LIQUIFIED
PETROLEUM GASES, ANSI/NFPA 58 AND CSA B149.1, NATURAL GAS AND PROPANE
INSTALLATION CODE.
PIPING: THIS HEATER MUST BE INSTALLED BY A QUALIFIED GAS TECHNICIAN
FOLLOWING LOCAL CODES PUBLISHED BY THE AUTHORITY HAVING JURISDICTION.
SIZING OF SUPPLY PIPING MUST BE DETERMINED USING THE LENGTH OF PIPE RUN AS
WELL AS TOTAL BTUH RATING OF THE APPLIANCE(S). APPROPRIATE PIPING TABLES
MUST BE USED TO DETERMINE SIZE OF SUPPLY PIPING DEPENDANT ON THE LENGTH
OF RUN FROM SOURCE.
CONNECTING TO AN EXTERNAL FUEL TANK
(BLAZE 600 D TURBO)
APPROVAL AGENCY OMNI OMNI
DRY WEIGHT (lbs.) 600 600
Dimensions 76.7” x 31” x 58”
76.7” x 31” x 58”
FLUE SIZE
6”
6”

CAMPO EQUIPMENT CO. LTD. (ECOBLAZE)
6 Carson Court, Brampton, ON, CANADA, L6T 4P8
Tel: (905) 793-2525 | Fax: (905) 793-8768 | www.campoequipment.com Page | 8
Beckett CF800 is fitted with 3/8” SAE male fittings and is set up for a 2 line system to eliminate
priming. Ensure fuel tank has a supply line and a return line and connect the supply line to the 3/8”
SAE fitting on the inlet side of the fuel filter and the return line to the return fitting located on the
Beckett Burner pump. For a 1 line system remove bypass plug located on inlet port of Beckett
Pump and just connect fuel line to inlet side of fuel filter.
FUEL (BLAZE 600 G TURBO)
THIS HEATER WILL OPERATE ON PROPANE OR NATURAL GAS—NOT BOTH. THE
MANIFOLD PRESSURES ARE LISTED ON THE APPROVAL LABEL. TO DETERMINE WHICH
FUEL TO USE SEE RATING PLATE. DO NOT ATTEMPT TO USE THE HEATER WITHOUT
CONSULTING THE RATING PLATE.
NOTE: THE PROPER POSITION ON THE EASY SWITCH OVER BLUE HANDLE BALL VALVE
MUST BE USED AND RATING PLATE MUST REFLECT THE FUEL THE HEATER IS BURNING.
DO NOT OPERATE THE HEATER WITHOUT CONSULTING THE RATING PLATE.
HEATER CONVERSION MUST BE DONE BY A QUALIFIED TECHNICIAN AND RATING PLATE
MUST REFLECT ANY CHANGE.
THIS UNIT HEATER IS EQUIPPED FOR NATURAL GAS OR LP GAS. THIS UNIT HEATER IS
EQUIPPED WITH ORIFICES SIZED FOR OPERATION WITH NATURAL OR LP GAS VIA THE
EASY SWITCH OVER BLUE HANDLE BALL VALVE. FOR CONVERSION TO LP (OR
NATURAL) GAS SEE INSTRUCTION PLATE ON THE APPLIANCE.
EasyswitchoverBluehandleBallValveonGasmanifold.
Closedposition:Propane
Openposition:NaturalGas
HOSES
ALL HOSES USED TO CONNECT THIS HEATER TO FUEL SUPPLY MUST BE TYPE 1
APPROVED PROPANE/NATURAL GAS HOSE ASSEMBLIES.
ELECTRICAL
WARNING: ELECTRICAL GROUNDING INSTRUCTIONS
THIS APPLIANCE IS ABLE IS TO RECEIVE 1 PHASE POWER.
120V SUPPLY MUST BE AVAILABLE.
INSTALLATION

CAMPO EQUIPMENT CO. LTD. (ECOBLAZE)
6 Carson Court, Brampton, ON, CANADA, L6T 4P8
Tel: (905) 793-2525 | Fax: (905) 793-8768 | www.campoequipment.com Page | 9
12/3 AWG UPTO 50FT
10/3 AWG BEYOND 50FT
NOTE: IF ANY OF THE ORIGINAL WIRE AS SUPPLIED WITH THE APPLIANCE MUST BE
REPLACED, IT MUST BE REPLACED WITH TYPE TEW 14GA WIRE OR ITS EQUIVALENT.
ELECTRICAL SYSTEM BLAZE
600 D/G
Volts-Hertz-Phase 120-60-1
Full Load (Amps) 11.5
Max fuse size in AMPS
with time delay
15
The electrical grounding of the heater shall be in compliance with the National Electrical Code, ANSI/NFPA
70, or the CSA C22.1, Canadian Electrical Code, Part I

CAMPO EQUIPMENT CO. LTD. (ECOBLAZE)
6 Carson Court, Brampton, ON, CANADA, L6T 4P8
Tel: (905) 793-2525 | Fax: (905) 793-8768 | www.campoequipment.com Page | 10
Blaze 600D Turbo Schematic with R Motor
(Beckett CF800 Oil Burner)
Este manual sirve para los siguientes modelos
2
Tabla de contenidos
Idiomas:
Otros manuales de Calentador de Blaze
Manuales populares de Calentador de otras marcas

Empire Heating Systems
Empire Heating Systems WCC65 Manual de usuario

Wetekom
Wetekom 92 86 43 Manual de usuario

Desa
Desa SPC170-F Manual de usuario

Watlow
Watlow Watrod Electric Tubular Heaters Manual de usuario

Haverland
Haverland ECO-DRY GPS Series Manual de lista de piezas

Stelpro
Stelpro ASILVC2060 Series Manual de usuario