Bentone BFG 1-2 H3 Especificaciones técnicas

Providing sustainable energy solutions worldwide
Installation- and maintenance instruction
BFG 1-2 H3
LME22.233C2
MB-ZRDLE 407
178 088 35-7 P93783 2023-01-11
Translation of the original instructions.

2Bentone
example Beispielexempel
352011030141
Designation
Type
Model
Serial no.
Motor supply
Main supply
MADE IN SWEDEN BY
LIGHT OIL 35-90kW 1,25-6,0 cSt 7-14bar
BF 1 KS 76-24
BF 1
BF 1 KS 76-24
1234567
1~230V 1,0A 50Hz IP 20
Man.Year 2019
Cap. Min-Max
3
?
1
-sv
1. Manualer på övriga språk
2. www.bentone.com\
nedladdning eller scanna
QR-koden.
3. Skriv in brännarens
artikelnummer som nns på
din typskylt (se bild) och välj
ditt språk.
Detaljerad ecodesign
information kan laddas ner
på: www.bentone.com/
ecodesign.
-en
1. Manuals in other languages
2. www.bentone.com\
download or scan QR-code.
3. Enter the burner`s article
number on your data plate
(see picture) and select
language.
Detailed ecodesign
information can be
downloaded at:
www.bentone.com/
ecodesign.
-da
1. Manualer på andre sprog
2. www.bentone.com\
download eller scan
QR-koden.
3. Indtast brænderens
artikelnummer, der ndes
på typeskiltet (se billede), og
vælg dit sprog.
Detaljerede oplysninger om
ecodesign kan downloades
på: www.bentone.com/
ecodesign.
-fr
1. Manuels dans d’autres
langues
2. www.bentone.com\
download ou scannez le
code QR.
3. Saisir le numéro d’article
du brûleur sur votre plaque
signalétique (consultez
l’illustration) et sélectionnez
la langue.
Des informations détaillées
sur l’écodesign peuvent être
téléchargées à l’adresse:
www.bentone.com/
ecodesign.
-de
1. Gebrauchsanweisungen in
anderen Sprachen
2. www.bentone.com\
download oder scannen Sie
den QR-Code.
3. Geben Sie die
Artikelnummer des Brenners
auf Ihrem Typenschild ein,
(siehe Bild) und wählen Sie
die Sprache aus.
Detaillierte Informationen
zum Ecodesign können unter
www.bentone.com/ecodesign
heruntergeladen werden.
2

3Bentone
Table of contents
1. General Information............................................................4
1.1 Delivery inspection........................................................................ 4
1.2 Safety ............................................................................................... 4
1.3 What to do if you smell gas......................................................... 5
2. Technical data.......................................................................6
2.1 Dimensions BFG 1-2 H3............................................................... 6
2.2 Capacity range............................................................................... 7
2.3 Gas categories, approved gases................................................ 7
2.4 Technicalspecication ................................................................. 7
2.5 Model BFG 1 H3 ............................................................................ 8
2.6 Components................................................................................... 9
2.7 Skeleton diagram........................................................................ 11
3. Installation..........................................................................12
3.1 General instructions................................................................... 12
3.2 Instructions .................................................................................. 12
3.3 Inspection and maintenance.................................................... 12
3.4 Preparation for assembly ......................................................... 12
3.5 Gas supply .................................................................................... 12
3.6 Electric connection ..................................................................... 12
4. Electric equipment.............................................................13
4.1 Safety system .............................................................................. 13
4.2 Wiring diagram............................................................................ 13
4.3 Function LME... ............................................................................ 14
4.4 Control program at faults; fault mode indicator LME .... .... 15
5. Mounting ............................................................................17
5.1 Hole pattern................................................................................. 17
5.2 Burner installation ...................................................................... 17
5.3 Gas connections.......................................................................... 17
5.4 Electric connection ..................................................................... 17
5.5 Gas quality.................................................................................... 18
5.6 De-aerating................................................................................... 18
5.7 Tightness control ........................................................................ 18
5.8 Calculationofgasow.............................................................. 19
6. Settings ...............................................................................20
6.1 Brake plate adjustment ............................................................. 20
6.2 Air adjustment ............................................................................. 20
6.3 Startup........................................................................................... 21
6.4 Control of combustion .............................................................. 21
6.5 Settingtheairpressureswitch ................................................ 22
6.6 Settingthegaspressureswitch,min...................................... 23
7. Gas valve, MultiBloc ZRDLE 405-420................................24
8. Service .................................................................................27
8.1 Burner Service Schedule, Gas .................................................. 27
8.2 Component replacement intervals.......................................... 27
8.3 Combustion device ..................................................................... 28
8.4 Fan motor replacement............................................................. 29
8.5 Air intake and suction cone ...................................................... 30
8.6 Fanwheel...................................................................................... 32
8.7 Electrical package ....................................................................... 33
8.8 Controlofamemonitoringandionizationcurrent ........... 35
9. Handing over of the installation ......................................37
10. Troubleshooting.................................................................38
11. Service- and inspection protocol .....................................40

4Bentone
172 515 01-2 2021-10-05
1. General Information
The burner may only be used for its intended purpose in accordance with the
product’s technical data.
We reserve the right to make design changes and cannot be held liable for any
misprints or typographical errors.
Modifying the design or using accessories or components that have not been
approved by Enertech in writing is strictly prohibited.
This Installation and Maintenance manual:
• is to be regarded as part of the burner and must always be kept near
the installation site.
• must be read prior to installation.
• is intended for use by authorised personnel.
1.1 Delivery inspection
• Make sure everything is delivered and the goods have not been
damaged during transit. Transport damage should be reported to the
shipping company.
• If something is wrong with a delivery, report it to the supplier.
1.2 Safety
- before installation:
• Installation and work on the burner and associated system
components may only be carried out by persons who have undergone
relevant training.
• The product is packaged to prevent damage from occurring when
handled – Handle the product with care! Lifting equipment must be
used to lift larger packages.
• The products must be transported/stored on a level surface in a dry
environment, max. 80% relative humidity, no condensation.
Temperature -20 to +60 °C.
- installation:
• The burner must be installed in accordance with local regulations for
re safety, electrical safety, and fuel distribution.
• The premises must comply with local regulations pertaining to use of
the burner and must have adequate air supply.
• The installation site must be free of chemicals.
• Fire extinguisher with Class BE recommended.
• Make sure when installing the burner that there is enough space to
service the burner.
• The electrical installation must be professionally carried out in
accordance with current mains electricity regulations and in a
professional manner.
• Make sure that the burner is suitable for the application (see Technical
Data).
• All components must be installed without being bent, twisted or
subjected to mechanical or thermal forces that affect components.

5Bentone
• Care must be taken by the installer to ensure that no electrical cables
or fuel lines are pinched or otherwise damaged during installation or
service.
• Sharp edges can occur on, for example: ame tube, fan wheel and air
damper.
• The gas outlet from the pressure regulator must be con gured in
accordance with applicable regulations and lead to a safe area.
- before rst start:
• The burner must not be put into operation without proper safety and
protection devices.
• Permitted ambient temperature during operation -10 to +60 °C. Max.
80% relative humidity, no condensation.
• The surface temperature of the burner’s components may exceed
60 °C.
• Handle with caution – the burner has moving parts, and there is risk
of crushing injuries.
• Seal inspections must be performed during installation and servicing
to prevent leakage.
• Fitting and installation work has been completed and approved.
• Electrical installation has been correctly performed.
• Flue gas ducts and combustion air ducts are not blocked.
• All actuators and control and safety devices are in working order and
correctly set.
• If the boiler is equipped with an access hatch, this must be equipped
with a hatch opening switch connected to the burner’s safety system.
• When in operation, the burner’s noise level can exceed 85 dBA – use
hearing protection!
- Operation:
• Carry out all stipulated settings, service and inspection work within
the set time.
1.3 What to do if you smell gas
• Turn off the fuel supply.
• Turn off the device and remove the boiler from operation.
• Open windows and doors.
• Prevent open ames or sparking, e.g. do not turn lights on or off, do
not use any electrical appliances or mobile phones.
• Evacuate the building.
• Notify the installer or gas supplier of the problem so that it can be
recti ed.

6Bentone BFG 1
145
290
186
35
272
195
B
A
2. Technical data
The burner is intended for:
• Operation in installations according to EN 303 and EN 676.
Fuels:
• Natural gas H, E, L, LL.
• LPG, Butane and Propane.
2.1 Dimensions BFG 1-2 H3
The above-mentioned measurements are maximum measurements.
They can vary, depending on which components are used.
2.1.1 Dimensions anges
Flange
172 525 45-3 2023-01-11
145
109,5
10
23,5

7Bentone BFG 1
2.3 Gas categories, approved gases
Only dry gas is permitted for use.
2.2 Capacity range
Capacity Gas quantity at
min. power Nm3/h
Gas quantity at
max. power Nm3/h
BFG 1 H3 25-100kW
G 20 2.6 10.6
G 25 3.1 12.3
G 30 0.8 3.1
G 31 1.0 4.1
Gas valve
MultiBloc
Max. connection
pressure mbar
Min connection
pressure mbar
MB-ZRDLE 407 360 See data plate
Category Country of destination Supply pressure
II2R3R AT, BE, BG, CH, CY, CZ, DE, DK, EE, ES, FI, FR, GB, GR, HR,
HU, IE, IS, IT, LT, LU, LV, MK, MT, NL, NO, PL, PT, RO, RS, SE,
SI, SK, TR
20 mbar
II2H3B/P AT, CH, CY, DK, FI, LT, RO, SE, SK 20 mbar
II2H3P GB, IE 20 mbar
II2L3B/P NL, RO 20 mbar
II2E3B/P PL 20 mbar
I2E(R)B BE 20 mbar
I3P BE 20 mbar
160302-302-4
Measurements according to EN 15036-1:2006
Alt.1 The noise level of the burner can be reduced by equipping the burner
with silencer. Installation must be done so it does not prevent air supply
to the burner.
Alt.2 The burner’s noise level can be reduced by connecting the burner’s air
intake to the air duct that opens into an appropriate location. Installation
must be done so it does not prevent air supply to the burner.
2.4 Technical specication
BFG 1
Main supply 1) 230V, 1~, 1.1/1.5A, 50/60Hz, IP20
Max fuse rating 6.3A
NOX-class 2
Noise level 75dBA
1) Max operating current, see data plate.

8Bentone BFG 1
29,0-31,0
16,0-71,0
ø103
2,5-3,5
7,5-8,5
Natural gas LPG
2.5 Model BFG 1 H3
2.5.1 Burner output/Basic settings
Flame tube
length mm
Flame tube
Dimension A mm
Flame tube
Dimension B ø
145 121,5 103
245 221,5 103
The above-mentioned measurements are maximum measurements.
They can vary, depending on which components are used.
!Do not exceed working
eld.
!Scale value valid at
0 mbar in furnace
pressure.
0,0
2,0
4,0
6,0
8,0
10,0
12,0
14,0
16,0
18,0
20,0
22,0
25 35 45 55 65 75 85 95
160303-630
kW
Scale
Burner output
Air damper, first stage
Air damper, second stage
Brake plate adjustment
-0,5
0,0
0,5
1,0
1,5
2,0
2,5
3,0
3,5
4,0
4,5
5,0
5,5
20 30 40 50 60 70 80 90 100
mbar
kW
25-100 kW
160303-631

9Bentone BFG 1
2.6 Components
1. Gas valve (MultiBloc)
2. Adjustment gas valve, rst stage
3. Adjustment gas valve, second stage
4. Protective cover start gas adjustment
5. Adjustment regulator pressure
6. Electrical contact, gas valve
7. Electrical contact, gas pressure switch S9
8. Gas pressure switch
9. Connection gas valve
10. Ignition transformer
11. Gas burner control
12. Electrical contact, X3 (see wiring diagram)
13. Motor
14. Capacitor
15. Flame tube
6
45
10
8
13
15
14
1
2
3
7
11
12
9

10 Bentone BFG 1
13
12
27
11
1
30
29
28
26 25
24
23
22
21
20
19
18
17
9
16
8
76
27
33
35
34
32
36
16. Measuring point regulator pressure
17. Electrical contact, damper motor M2
(see wiring diagram)
18. Damper motor
19. Air regulator, rst stage
20. Screw lock adjustment, rst stage
21. Electrical contact, second stage X5 och X6
(see wiring diagram)
22. Air regulator, second stage
23. Air pressure switch
24. Measuring point for the air pressure switch
on the low-pressure side
25. Air ow indicator
(indicates the air setting)
26. Air intake
27. Reset button
28. Nozzle assembly adjustment
under cover plate
29. Cover plate
30. Screw for division of burner
in front and rear part
31. Nozzle assembly
32. Brake plate
33. Ignition electrode
34. Ionisation electrode
35. Nozzle