List of functions UAD 3 - V3
Measur. mode .... .... Display of the actually measured value and the measuring unit
MENU Display keylock
UNLK No keylock, all parameters can be adjusted
LOCK Keylock active, all parameters visibal but can not be changed
SP1...SP4 Switch point menu SP1..SP4
MODE STND Standard evaluation (rising/falling)
WIND Window technology
ERRO Error output
ON .... Switch-on value for SP1...SP4; if the ON-value is smaller
than the OFF-value, the switch evaluatiuon is falling
OFF .... Switch-off value SP1...SP4
LEV Inversion of the switching output
HLFS High-level-fail-safe (Normally Open function)
LLFS Low-level-fail-safe ((Normally Closed function)
DEL 0,0s..9,9 s Switch-on / switch-off delay for SP1...SP4 in seconds
SPSC DSP1 Switch point reacts on display values of display 1
DSP2 Switch point reacts on display values of display 2
ANO1...ANO2 Analog output menu
ANOP ON Analog output in operation
OFF Analog output switched off
AOZS .... Scale the analog output - start value (e.g. 0 bar = 4 mA)
AOFS Scale the analog output - end value (e.g. 400 bar = 20 mA)
DISP1...DISP2 Display menu
MODE STND Display channel 1 resp. channel 2
DIFF Display difference between channel 1 and ch. 2 (ch. 1 – ch. 2)
UTXT ABCD Enter the measuring unit as text
DAMP 0,0s..9,9 s Damping of the displayed measuring value in seconds
OFFS .... Measuring value -Offset, means shifting the display range
CUT .... Cut-Off, means signal-surpression within the cut-off range
BGZS .... Scale the bargraph - start value
BGFS .... Scale the bargraph - end value
PEAK Peakholding menu
MIN .... Display the peak value „Min“
CLRM NO no deletion
YES delete „Min“-value memory
MAX .... Display the peak value „Max“
CLRX NO no deletion
YES delete „Max“-value memory
CAL1...CAL2 Calibration menu
DECP 0000..0,000 Determination of the decimal-point for the measuring value
ZSCL .... Scale the measuring-value indication - start value
FSCL .... Scale the measuring-value indication - end value
CODE Calibration of the manufacturer
4. Operation
After the unit is switched on, the unit starts an automatic self-test.
The device is menu operated and configured by the three keys on the front.
With the „M“ key (= mode) you change between the operation / indicating level to the dialog values and the
adjusted / actual values. With the keys („⇑“ = up) and („⇓“= down) you change between the dialog values
in the menu or change the values / functions in the menus.
A change of any configuration starts always with the M-Mode and indicated by the flashing cursor. After a
change has been made with the up- resp. down-key the M-mode key must be pressed to confirm each
configuration; to set numbers, each digit has to be confirmed with the M-Mode before adjusting the next
one. By confirming the last digit the new configuration will be stored in the memory.
Pushing the down key at the end of the sub-menu the software will switch automatically to the main-menu.
If the dialog is not continued within two minutes the device automatically returns to the measuring mode.
5. Key lock
Activating the („⇑“ = up) and („⇓“ = down) keys together for more than 5 seconds will block any changings
in all menues; shown by „LOCK“ in the display.
In this mode, all configuration values can be checked only, but not changed.
Repeating this action will unlock the configuration menu and shown by „UNLK“ in the display.
6. Error handling
The internal self-check software will monitor the proper functioning of the unit. When any of the following
failures will occur, the flashing display will indicate the following text:
Main Menu Sub Menu Value Description
Display Error Cause
max Positive excess of the measuring range The measured value exceeds the max. of the range
Channel 1 (indicated in display 1)
positive excess of the measuring range
Channel 2 (indicated in display 2)
min Negative excess of the measuring range The measured value is lower than the min. of the range
Channel 1 (indicated in display 1)
negative excess of the measuring range
Channel 2 (indicated in display 2)
anao Failure of the analog output 1 Output loop is not closed or short circuited
(indicated in display 1)
Failure of the analog output 2
(indicated in display 2)
data Stored data failure (EEProm) (internal) Memory failure
prog Processor failure (internal) Microcontroller failure
cal Calibration error channel 1 (internal) Calibration values are wrong
(indicated in display 1)
Calibration error channel 2 (internal)
(indicated in display 2)
Attention:
At first the peak value
menu for channel 1 in
display 1 is indicated,
then for channel 2 in
display 2.