Athena C10 Series Manual de usuario

ATHENA CONTROLS, INC.
5145 Campus Drive
Plymouth Meeting
PA 19462 U.S.A.
Tel: (610) 828-2490
Fax: (610) 828-7084
AthenaControls.com
Controller
Indicator
Transmitter
1/32 DIN - 48 x 24
C10 line cc
User manual • M.I.U.C10-1/02.06 • Cod. J30-478-1AC1 SEA
UL
CUS
LISTED

Controller
Indicator
Transmitter
1/32 DIN - 48 x 24
C10 line cc
274.8
UL
CUS
LISTED

2
information
cc
NOTES
ON ELECTRIC
SAFETY AND
ELECTROMAGNETIC
COMPATIBILITY.
Please, read carefully these instructions before proceeding with
the installation of the controller.
Class II instrument, rear panel mounting.
This controller has been designed with compliance to:
Regulations on electrical apparatus (appliance, systems and installa-
tions) according to the European Community directive 73/23 CEE amend-
ed by the European Comunity directive 93/68 CEE and the Regulations
on the essential protection requirements in electrical apparatus EN 61010-
1 (IEC 1010 - 1) : 90 +A1:92 + A2:95.
Regulations on Electromagnetic Compatibility according to the
European Community directive n089/336/CEE, amended by the European
Community directive n° 92/31/CEE and the following regulations:
Regulations on RF emissions
EN50081 - 1 residential environments
EN50081 - 2 for industrial environments
Regulation on RF immunity
EN500082-2 for industrial equipment and system
It is important to understand that it’s responsibility of the installer to ensure
the compliance of the regulations on safety requirements and EMC.
The device has no user serviceable parts and requires special equipment
and specialised engineers. Therefore, a repair can be hardly carried on
directly by the user. For this purpose, the manufacturer provides techni-
cal assistance and the repair service for its Customers.
Please, contact your nearest Agent for further information.
All the information and warnings about safety and electromagnetic
compatibility are marked with the Bsign, at the side of the note.

3
Table of contents
TABLE OF CONTENTS 1INSTALLATION...........................................................................................................................Page 4
2ELECTRICAL CONNECTIONS.....................................................................................Page 8
3PRODUCT CODING..............................................................................................................Page 14
4OPERATIONS..............................................................................................................................Page 18
5AUTOMATIC TUNE...............................................................................................................Page 28
6TECHNICAL SPECIFICATIONS...................................................................................Page 29
Main universal input
Control Alarms Retransmission
Resources
OP1
PV
OP2
OP4
(option)
Setpoint
Operating mode
PV
C10
1Single OP1 OP2 OP4
output
2Single OP2 OP1 OP4
output
0Indication OP1 OP2 OP4
only
Modbus RS485
Parameterisation
Supervision
Fuzzy tuning
with automatic selection
One shot
Auto tuning One shot
Natural frequency

4
1 - Installation
1INSTALLATION
Installation must only be carried
out by qualified personnel.
Before proceeding with the instal-
lation of this controller, follow the
instructions illustrated in this man-
ual and, particularly the installation
precautions marked with the B
symbol, related to the European
Community directive on electrical
protection and electromagnetic
compatibility.
B
To prevent hands or metal touch-
ing parts that may be electrically
live, the controllers must be
installed in an enclosure and/or in
a cubicle.
1.1 GENERAL DESCRIPTION
IP 20 Termination Unit
EN61010 - 1 (IEC1010 - 1)
Product code label
Sealin front panel gasket
Mounting clamps
Front panel
IP65 protection
EN 60529 (IEC 529)
Panel surface

5
1 - Installation
1.2 DIMENSIONAL DETAILS
48 mm
1.89 in
25 mm
0.99 in
120 mm
4.72 in
20 mm max
0.79 in max
1.3 PANEL CUT-OUT
65 mm min
2.56 in min
42 mm min.
1.65 in min.
22.2+0.3 mm
0.87+0.01 in
45+0.6 mm
1.78+0.023 in

6
1 - Installation
Special conditions
MAltitude > 2000 m
TTemperature >50°C
%Rh Humidity > 95 %
PConducting atmosphere Use filter
Warm up
Use forced air ventilation
Use 24V~supply version
Suggestions
Forbidden Conditions D
CCorrosive atmosphere
EExplosive atmosphere
Operating conditions
MAltitude up to 2000 m
TTemperature 0…50°C
%Rh Relative humidity 5…95 % non-condensing
1.4 ENVIRONMENTAL RATINGS B

7
1 - Installation
1.5.1 INSERT THE INSTRUMENT
1Prepare panel cut-out
2Check front panel gasket posi-
tion
3Insert the instrument through
the cut-out
1.5 PANEL MOUNTING
1.5.2 INSTALLATION SECURING
1Position the mounting clamps
2Push the mounting clamps
towards the panel surface to
secure the instrument
1
3
2
1.5.3 CLAMPS REMOVING
1Insert the screwdriver in the clips
of the clamps
2Rotate the screwdriver
1
2
1.5.4 INSTRUMENT UNPLUGGING B
1Push and
2pull to remove the instrument
Electrostatic discharges can dam-
age the instrument
Before removing the instrument the
operator must discharge himself
to ground
1
1
2
1
2
1
1MΩ

8
2 - Electrical connections
2ELECTRICAL
CONNECTIONS
2.1 TERMINATION UNIT B
12 screw terminals
Option terminals
Holding screw 0.5 Nm
Positive screw driver PH1
Negative screw driver 0,8 x 4 mm
Recommended wire terminal leads
Pin connector q1.4 mm - 0.055 in max
Ø
Fork-shape AMP 165004 Ø 5.5 mm - 0.21 in
L
Stripped wire L 5.5 mm - 0.21 in
123456
789101112
0,5
Nm
Rear
terminal
cover
Cable size
0,5…1,5 mm2
(22 a 16 AWG)
5.7 mm
0.22 in
mA
mV
1
TC
OP1
23456
78910 11 12
b
B
A
RTD
LN
NO C
RS485
(OP4) OP2 - L
+18V— OUT
F50- 474 1A1C1

9
2 - Electrical connections
PRECAUTIONS B
Despite the fact that the instrument
has been designed to work in an
harsh and noisy environmental
(level IV of the industrial standard
IEC 801-4), it is strongly recom-
mended to follow the following
suggestions.
A
All the wiring must comply with the
local regulations.
The supply wiring should be rout-
ed away from the power cables.
Avoid to use electromagnetic con-
tactors, power relays and high
power motors nearby.
Avoid power units nearby, espe-
cially if controlled in phase angle
Keep the low level sensor input
wires away from the power lines
and the output cables.
If this is not achievable, use shield-
ed cables on the sensor input, with
the shield connected to earth.
2.2 RECOMMENDED ROUTING OF WIRES B
123456
789101112
LN IN
Conduit for supply and output cables
Conduit for low level sensor cables
AB
DEC
123456
789101112
LN IN
AB
DEC
A= Supply
B= Outputs
C= Analog inputs
D= Analogue output
Serial communications
E= SSR drive output
Otros manuales para C10 Series
1
Tabla de contenidos
Manuales populares de Transmisor de otras marcas

Dejero
Dejero EnGo 3x Manual de usuario

Rosemount
Rosemount 4600 Manual de usuario

Speaka Professional
Speaka Professional 2342740 Manual de usuario

trubomat
trubomat GAB 1000 Manual de usuario

Teledyne Analytical Instruments
Teledyne Analytical Instruments LXT-380 Manual de usuario

Rondish
Rondish UT-11 Manual de usuario