Aspar 8AI Manual de usuario

RS485 MODBUS Module 8AI
Expansion Module – 8 analog inputs
Version 1 5 User Manual
Manufactured for

RS485 MODBUS Module 8AI
User Manual
Thank you for choosing our product.
This manual will help you with proper support and proper operation of the device.
The information contained in this manual have been prepared with utmost care by our
professionals and serve as a description of the product without incurring any liability for
the purposes of commercial law.
This information does not release you from the obligation of own judgement and
verification.
We reserve the right to change product specifications without notice.
Please read the instructions carefully and follow the recommendations contained
therein.
WAR I G!
Failure to follow instructions can result in equipment damage or impede
the use of the hardware or software.
Expansion Module – 8 analog inputs
User Manual Version 1 5 2 / 15

RS485 MODBUS Module 8AI
User Manual
1. Safety rules
•Before first use, refer to this manual
•Before first use, make sure that all cables are connected properly
•Please ensure proper working conditions, according to the device specifications
(eg: supply voltage, temperature, maximum power consumption)
•Before making any modifications to wiring connections, turn off the power supply
2. Module Features
2.1. Purpose and description of the module
8AI module allows measurement of voltages and currents. Values are read via
RS485 (Modbus), so we can easily integrate the module with popular PLCs, HMI or PC
equipped with the appropriate adapter.
The device has a set of 8 analog input measurements. In addition, the module is
equipped with 2 configurable digital outputs.
This module is connected to the RS485 bus with twisted-pair wire.
Communication is via MODBUS RTU or MODBUS ASCII. The use of 32-bit ARM
core processor provides fast processing and quick communication. The baud rate is
configurable from 2400 to 115200.
The module is designed for mounting on a DI rail in accordance with
DI E 5002.
The module is equipped with a set of LEDs used to indicate the status of inputs
and outputs useful for diagnostic purposes and helping to find errors.
Module configuration is done via USB by using a dedicated computer program.
You can also change the parameters using the MODBUS protocol.
Expansion Module – 8 analog inputs
User Manual Version 1 5 3 / 15

RS485 MODBUS Module 8AI
User Manual
2.2. Technical Specifications
Power Supply Voltage 10-38VDC; 10-28VAC
Maximum Current 120 mA @ 12V 100 mA @ 24V
Inputs
No of inputs 8
Voltage input 0V to 10V (resolution 1.5mV)
Voltage input -10V to 10V (resolution 1.5mV)
Voltage input 0V to 1V(resolution 0.1875mV)
Voltage input -1V to 1V(resolution 0.1875V)
Current input 4mA to 20mA (resolution 3.75μA)
Current input 0mA to 20mA (resolution 3.75μA)
Current input -20mA to 20mA (resolution 3.75μA)
Measurement resolution 14 bits
ADC processing time 16ms channel
Digital outputs Maximum current and voltage 500mA 55V
Temperature Work -20 °C - +65°C
Storage -40 °C - +85°C
Connectors
Power Supply 2 pin
Communication 3 pin
Inputs & Outputs 2 x 10 pin
Quick connector IDC10
Configuration Mini USB
Size
Height 120 mm
Length 101 mm
Width 22,5 mm
Interface RS485 Up to 128 devices
Expansion Module – 8 analog inputs
User Manual Version 1 5 4 / 15

RS485 MODBUS Module 8AI
User Manual
2.3. Dimensions of the product
Look and dimensions of the module are shown below. The module is mounted
directly to the rail in the DI industry standard. Power connectors, communication and
IOs are at the bottom and top of the module. USB connector configuration and
indicators located on the front of the module.
Expansion Module – 8 analog inputs
User Manual Version 1 5 5 / 15

RS485 MODBUS Module 8AI
User Manual
3. Communication configuration
3.1. Grounding and shielding
In most cases, IO modules will be installed in an enclosure along with other
devices which generate electromagnetic radiation. Examples of these devices are relays
and contactors, transformers, motor controllers etc. This electromagnetic radiation can
induce electrical noise into both power and signal lines, as well as direct radiation into
the module causing negative effects on the system. Appropriate grounding, shielding
and other protective steps should be taken at the installation stage to prevent these
effects. These protective steps include control cabinet grounding, module grounding,
cable shield grounding, protective elements for electromagnetic switching devices,
correct wiring as well as consideration of cable types and their cross sections.
3.2. Network Termination
Transmission line effects often present a problem on data communication
networks. These problems include reflections and signal attenuation.
To eliminate the presence of reflections from the end of the cable, the cable must
be terminated at both ends with a resistor across the line equal to its characteristic
impedance. Both ends must be terminated since the direction of propagation is bi-
directional. In the case of an RS485 twisted pair cable this termination is typically
120 Ω.
3.3. Setting Module ddress in RS485 Modbus Network
The following table shows how to set switch to determine the address of the
module. The module address is set with the switches in the range of 0 to 31. Addresses
From 32 to 255 can by set via RS485 or USB.
Addr SW5 SW4 SW3 SW2 SW1
0 OFF OFF OFF OFF OFF
1 OFF OFF OFF OFF ON
2 OFF OFF OFF ON OFF
3 OFF OFF OFF ON ON
4 OFF OFF ON OFF OFF
5 OFF OFF ON OFF ON
6 OFF OFF ON ON OFF
7 OFF OFF ON ON ON
8 OFF ON OFF OFF OFF
9 OFF ON OFF OFF ON
10 OFF ON OFF ON OFF
Addr SW5 SW4 SW3 SW2 SW1
11 OFF ON OFF ON ON
12 OFF ON ON OFF OFF
13 OFF ON ON OFF ON
14 OFF ON ON ON OFF
15 OFF ON ON ON ON
16 ON OFF OFF OFF OFF
17 ON OFF OFF OFF ON
18 ON OFF OFF ON OFF
19 ON OFF OFF ON ON
20 ON OFF ON OFF OFF
21 ON OFF ON OFF ON
Addr SW5 SW4 SW3 SW2 SW1
22 ON OFF ON ON OFF
23 ON OFF ON ON ON
24 ON ON OFF OFF OFF
25 ON ON OFF OFF ON
26 ON ON OFF ON OFF
27 ON ON OFF ON ON
28 ON ON ON OFF OFF
29 ON ON ON OFF ON
30 ON ON ON ON OFF
31 ON ON ON ON ON
Expansion Module – 8 analog inputs
User Manual Version 1 5 6 / 15

RS485 MODBUS Module 8AI
User Manual
3.4. Types of Modbus Registers
There are 4 types of variables available in the module
Type Beginning
address Variable Access Modbus
Command
1 00001 Digital Outputs Bit
Read & Write 1, 5, 15
2 10001 Digital Inputs Bit
Read 2
3 30001 Input Registers Registered
Read 3
4 40001 Output Registers Registered
Read & Write 4, 6, 16
3.5. Communication settings
The data stored in the modules memory are in 16-bit registers. Access to
registers is via MODBUS RTU or MODBUS ASCII.
3.5.1. Default settings
You can restore the default configuration by the switch SW6 (see 3.5.2 - Restore
the default configuration)
Baud rate 19200
Parity No
Data bits 8
Stop bits 1
Reply Delay [ms] 0
Modbus Type RTU
3.5.2. Restore the default configuration
To restore the default configuration:
•turn off the power
•turn on the switch SW6
•turn on the power
•when power and communication LED flash turn off the switch SW6
Caution! After restoring the default configuration all values stored in the registers will
be cleared as well.
Expansion Module – 8 analog inputs
User Manual Version 1 5 7 / 15

RS485 MODBUS Module 8AI
User Manual
3.5.3. Configuration registers
Modbus Dec Hex Name Values
Address
40003 2 0x02 Baud rate
0 – 2400
1 – 4800
2 – 9600
3 – 19200
4 – 38400
5 – 57600
6 – 115200
other – value * 10
40005 4 0x04 Parity
0 – none
1 – odd
2 – even
3 – always 1
4 – always 0
40004 3 0x03 Stop Bits LSB 1 – one stop bit
2 – two stop bits
40004 3 0x03 Data Bits MSB 7 – 7 data bits
8 – 8 data bits
40006 5 0x05 Response delay Time in ms
40007 6 0x06 Modbus Mode 0 – RTU
1 – ASCII
4. ndicators
ndicator Description
Power supply LED indicates that the module is correctly powered.
Communication The LED lights up when the unit received the correct packet and sends the
answer.
Inputs state LED indicates that the signal to input is connected.
Outputs state LED indicates that the output is on.
Expansion Module – 8 analog inputs
User Manual Version 1 5 8 / 15
1 2 3 4 5 6
ON
Communication
Power Supply
2 digital outputs
state
8 inputs state

RS485 MODBUS Module 8AI
User Manual
5. Module Connection
Expansion Module – 8 analog inputs
User Manual Version 1 5 9 / 15

RS485 MODBUS Module 8AI
User Manual
6. Selecting the input mode
Each input can be used to measure the voltage (the default) or current. To change the
operating mode in addition to configuration changes by using the program, also set the
jumpers inside the module as shown below
Jumper Description
off Voltage measurement
shorted Current measurement
7. Switches
Switch Function Description
1 Module address +1
Setting module address from 0 to 31
2 Module address +2
3 Module address +4
4 Module address +8
5 Module address +16
6 Restoring default settings
Restoring default settings
( see 3.5.1 - Default settings and 3.5.2 - Restore the
default configuration).
Expansion Module – 8 analog inputs
User Manual Version 1 5 10 / 15
Tabla de contenidos
Otros manuales de Hardware de computadora de Aspar
Manuales populares de Hardware de computadora de otras marcas

EMC2
EMC2 VNX Series Manual del propietario

Panasonic
Panasonic DV0PM20105 Manual de usuario

Mitsubishi Electric
Mitsubishi Electric Q81BD-J61BT11 Manual de usuario

Gigabyte
Gigabyte B660M DS3H AX DDR4 Manual de usuario

Raidon
Raidon iT2300 Manual de usuario

National Instruments
National Instruments PXI-8186 Manual de usuario