Logic Function
The setting for the type of operation is carried out via dip switches located on the top of the circuit, near the fuse F5. In this location there is a dip-switch
with 8 positions (S1).
DIP SWITCH S
DIP If set to O enables pre-flashes for about 3 seconds
DIP2 If set in the OFF, photocells work only in closing, reversing the march of automation.
If set to O , the photocells will activate in only open until it remains on the limit switch close. After, in OPE no longer will activate.
DIP3 If set to O , photocell TEST is enabled.
Practically before moving automation in closing, the control unit makes a control test on photocells. Attention: If enabled, the transmitter of the
photocells must be connected on pin 20 and 21 of M3.
DIP8 Se posizionato in O si attiva la fase di programmazione tempi. Vedi paragrafo relativo. If set in O position, the programming time phase
activates. See the relative paragraph.
Operation logic DIP 4-5-6-7
The dip 4-5-6-7 are used to select the type of operation that the control-box must have when it receives the command to Open or Close ..
Follow the table below and verify the function is activated, and its mode of operation. The symbol "#" indicates the position of the DIP is irrelevant.
Function DIP 4 DIP 5 DIP 6 DIP 7
AOFF OFF OFF #
BOFF OFF ON #
COFF ON OFF #
DOFF ON ON #
EON OFF OFF OFF
FON OFF OFF ON
GON OFF ON OFF
HON OFF ON ON
ION ON ON OFF
LON ON ON ON
MON ON OFF #
Working
AStep – step
OPE – STOP - CLOSE, without automatic closure
BStep – step
OPE – STOP - CLOSE, with automatic closure
CStep – step
OPE - CLOSE, without automatic closure
DStep – step
OPE - CLOSE, with automatic closure
Semi-automatic: During the opening is no longer accepting pulses until it closes. It has not automatic closing. To close use the CLOSE input.
FSemi-automatic:
Same as point E but during the break, also a pulse of OPE makes re-close.
GAutomatic: When opening a pulse on the OPE input has no effect. Paused, it resets the pause time.
HAutomatic: The same as the G but a pulse on the OPE input during the break actuates the closing
ISemiautomatic OPE - STOP - CLOSE: After STOP impulse given by OPE input, time of break is counted off and closed. A pulse given during
the break it resets the time.
LSemiautomatic same as point I, but during the break, a pulse on OPE input makes it re-close.
MPRESE T MA working.
Warning: channel 1 of the receiver is electrically connected at OPE input and then makes the same function. Channel 2 can be set to function as the
CLOSE input or PEDESTRIA . See paragraph RADIO RECEIVER.
Working times programming
Programming without end-of-stroke connected
- Bring the automation in the closed position. Set DIP switch 8 in O position
- Give a pulse to Open input or with the radio-transmitter (channel 1). The automation will start in Opening.
- Once it has reached the end of the opening stroke, give a second pulse on the OPE input or with the transmitter (channel 1)
- Leave spend the time of pause and give the 3rd pulse on Open input or with the transmitter (channel 1).
- The automation will start closing. Once it has reached the end of the closing stroke, give a fourth pulse on Open input or with the transmitter (channel 1).
- Set the dip switch 8 to OFF
Programming with end-of-stroke connected
- Bring the automation in the closed position. Set DIP switch 8 in O position
- Give a pulse to Open input or with the radio-transmitter (channel 1). The automation will start in Opening.
- Once it has reached the end of the opening stroke, starts counting the pause time.
-- Leave spend the time of pause and give a pulse on Open input or with the transmitter ( channel 1).
– The automation will start closing. Once it has reached the end of the closing stroke, set the dip switch 8 to OFF