aquilar AquiTron AT-ZAP Guía

AT-ZAP
Zone Alarm Panel
AquiTron
INSTALLATION
& OPERATION
INSTRUC-

AT-ZAP
80 - 275Vac @ 50/60 Hz
12Vdc ±20%
POWER CONSUMPTION
?? watt maximum
RELAYS
Number: One volt free relay per zone
(max 12), Two common LEAK and one
common FAULT.
Type: SPST congurable
Rating: 3 A at 250Vac/24 Vdc
TEMPERATURE
Storage: -18°C to 60°C (0°F to 140°F)
Operating: 0°C to 50°C (32°F to 122°F)
ENCLOSURE
NEMA 12; IP54
INSTALLATION ITEMS
(NOT SUPPLIED)
• Wall fasteners for surface mounting (four
screws)
• Rubber or elastomeric washers to seal
at mounting points
• Semi-ush recess ange (optional)
TOOLS REQUIRED
• Drill or hole punch for electrical
conduit entries
• Phillips (cross-head) screwdriver
• Small at-head screwdriver
STORAGE
Keep the module in a dry place prior to
installation to avoid possible damage to
internal components.
ADDITIONAL ITEMS
AT-PS-12-1
Battery Unit c/w battery
230Vac to 12Vdc
AT-BAT
Replacement 12Vdc, 7Ah Battery
APPROVALS
The AT-ZAP is approved for use in ordinary
areas. The module must be located in an
Ordinary Area, but may monitor intrinsically
safe TraceTek sensing cables located in
Hazardous Locations:
• TraceTek sensing cable in Class I,
Division 2, Groups A, B, C, D =Hazardous
Locations.
• If protected by agency-approved zener
barrier TraceTek sensing cable in Class I,
Division 1, Groups A, B, C, D Hazardous
Locations (Zone 0 or Zone 1 in Europe).
Contact your TraceTek distributor/agent
to select proper zener barrier.
MAXIMUM CIRCUIT LENGTH
100m (328ft) TraceTek sensing cable or 10
water or optical oil probes per zone. Leader
and jumper cable lengths are not included
in this limitation.
Please read these
instructions carefully
and keep them in a
safe place (preferably
close to the module)
for future reference.
These instructions
must be followed
carefully to ensure
proper operation.
AT-ZAP
Zone Alarm Panel
A. GENERAL INFORMATION
The AT-ZAP multi zone alarm has been designed specically for use with TraceTek sensing
cables (TT1000, TT1100, TT3000, TT5000, TT5001 and TT7000). The AT-ZAP can monitor per
zone up to 100 m (328 ft) of sensing cable, or 10 water detection probes. Optical probes, oat
switches and level indicators can also be incorporated into the system . The AT-ZAP is
designed for use in ordinary areas with temperatures of 0°C to 50°C (32°F to 122°F).
B. PRODUCT INFORMATION
LEAK DETECTION SOLUTIONS
1
Unit 30, Lawson Hunt Industrial Park,
Broadbridge Heath, Horsham, West Sussex,
RH12 3JR
+44 (0) 1403 216100
www.aquilar.co.uk

AT-ZAP
Zone Alarm Panel
LEAK DETECTION SOLUTIONS
1. Z1/2 Sensing cable plug and socket
2. Z3/4 Sensing cable plug and socket
3. Z5/6 Sensing cable plug and socket
4. Z7/8 Sensing cable plug and socket
5. Z9/10 Sensing cable plug and socket
6. Z11/12 Sensing cable plug and socket
7. Z1/2 Leak relay cable plug and socket
8. Z3/4 Leak relay cable plug and socket
9. Z5/6 Leak relay cable plug and socket
10. Z7/8 Leak relay cable plug and socket
11. Z9/10 Leak relay cable plug and socket
12. Z1/2 Leak relay cable plug and socket
13. Summary fault relay plug & socket
14. Common leak relay 1 plug & socket
15. Common leak relay 2 plug & socket
16. Z1/2 6Vdc latching solenoid output
17. Z3/4 6Vdc latching solenoid output
18. Z5/6 6Vdc latching solenoid output
19. Z7/8 6Vdc latching solenoid output
20. Z9/10 6Vdc latching solenoid output
21. Z11/12 6Vdc latching solenoid output
22. Power Cable Terminal Block (Mains In)
23. Power Cable Terminal Block (Mains Out)
24. Ground/earth stud
25. Fuse T1.6AL 250Vac
26. 230Vac/12Vdc Power Supply
27. 12/24Vdc Accessory Connection
28. Battery Backup Connection
29. 12Vdc Power Input
30. Buzzer
31. Serial Expansion Port (not currently
used)
32. Interface board connection
33. Network Connection (not currently used)
2
Unit 30, Lawson Hunt Industrial Park,
Broadbridge Heath, Horsham, West Sussex,
RH12 3JR
+44 (0) 1403 216100
www.aquilar.co.uk
1 3 52 4 6
Z1 Z3 Z5 Z7 Z9 Z11
Z2 Z4 Z6 Z8 Z10 Z12
716
8
17
9
18
10
19
11
20
12
21
22 23
24
30
32
33
31
27 28 29
25
26
13
14
15
Z1
Z1Z2
Z3
Z3Z4
Z5
Z5Z6
Z7
Z7Z8
Z9
Z9
Z10
Z11
Z11Z12
Z2
Z4
Z6
Z8
Z10
Z12
1. CR 2032 Battery
2. Display Connector
3. Main PCB Connector
4. Serial Expansion Port
5. USB Connector for History dump.
DOOR BOARD
1
3
5
2
4

LEAK DETECTION SOLUTIONS
3
Choose a location indoors where the module will be protected from the elements
andtemperature extremes
WARNING: Ignition hazard. Do not mount the AT-ZAP unit in a hazardous location. Sensing
cable connected to the AT-ZAP may (subject to approvals restrictions) be located in hazardous
locations, but the module itself must not.
C. SELECT A MOUNTING POSITION
PREPARE THE MODULE FOR
MOUNTING
Important: The AT-ZAP is an electronic unit.
During installation, take the following
precautions to avoid damage to its electronic
components:
• Handle with care, avoid mechanical
• damage.
• Keep the electronics dry.
• If handling circuit boards, hold them by
their edges to avoid physical contact with
electronic components.
• Avoid exposure to static electricity.
• Avoid contamination with metal lings,
liquids, or other foreign matter.
• Remove the module from its packaging.
• Open the enclosure door using a Phillips
(cross-head) screwdriver.
• It is recommended to use the 25 provided
20/25mm knockouts for cable entry either
with conduit or stung glands. If drilling
of the enclosure is necessary we would
recommend removing the PCB to prevent
damage.
• Anti static precautions should be taken
before touching the boards inside.
• Carefully disconnect the ribbon cable and
PSU connections from the motherboard.
• Unscrew the ve Phillips (cross-head)
screws holding the motherboard to
the enclosure (see Fig 1). Remove the
motherboard, and put it out of harm’s way.
MOUNT THE MODULE
The module mounts with four screws with
mounting centers as noted in Fig 2. To seal
around the mounting screw (necessary to
maintain the IP54 rating), use a rubber or
elastomeric washer.
• Taking care to protect the User Interface
board on the enclosure door, drill/punch
entries as required (see Fig 2).??
• Note: The AquiTronTM / TraceTek sensing
circuit is power limited, so the TraceTek
leader or jumper cable and the power
supply cable must not run in the same
conduit.
• Fit conduit bushings/adapters.
• Remove all traces of metal lings and dust
from inside the module enclosure.
Figure 1
Unit 30, Lawson Hunt Industrial Park,
Broadbridge Heath, Horsham, West Sussex,
RH12 3JR
+44 (0) 1403 216100
www.aquilar.co.uk
AT-ZAP
Zone Alarm Panel
remove all ve screws attaching
the motherboard
NOTE: It is not necessary to remove the PCB
to mount the panel.

AT-ZAP
Zone Alarm Panel
LEAK DETECTION SOLUTIONS
REASSEMBLE THE MODULE
Note: Before replacing the motherboard,
ensure that the interior of
the enclosure is clean.
• Replace the motherboard and secure it in
place with the Phillips (cross-head) screws.
• Reconnect the ribbon cable (taking care not
to bend any pins in the connection).
• Close and secure the door of the enclosure.
4
Cable entry knockouts are provided as follows:
Back plate 2 x 20mm and 3 x 25mm
Base 8 x 20mm and 4 x 25mm
Top 2 x 20mm and 2 x 25mm
Each side 1 x 20mm and 1 x 25mm
D. PREPARE SENSING CABLE / SENSING PROBE / DEVICE
Ensure that the sensing cable (sensing device) has been installed in accordance with the
instructions provided.
MAKE CONNECTIONS
• Conrm that the power to the AT-ZAP unit
has been turned o.
• Open the enclosure door.
• Feed the end of the TraceTek modular
leader cable (or bulk jumper cable) through
the knockout/adapter/bushing if tted.
• Connect the four colour-coded wires to the
Sensor Interface plug for the required zone
1-12 (see Fig 3).
Important: Observe the colour coding.
If wires are not connected to the correct
terminals, the leak detection system cannot
operate properly.
Insert the sensing cable plug into the ZI
socket for the zone required (Z1-Z12)
Figure 2
Unit 30, Lawson Hunt Industrial Park,
Broadbridge Heath, Horsham, West Sussex,
RH12 3JR
+44 (0) 1403 216100
www.aquilar.co.uk
270mm
264mm
248mm
300mm
18mm
26mm
26mm
26mm
28mm

AT-ZAP
Zone Alarm Panel
LEAK DETECTION SOLUTIONS
5
CONNECTING THE POWER WIRING
• Open door of AT-ZAP enclosure.
• Pass the power cable through the knock-
out/adapter/bushing if tted.
• Note: Proper grounding/earthing is
important to avoid the possibility of
electromagnetic interference.
• Connect the power supply wires to the
special three-pin terminal block marked LNE
(Live, Neutral, Earth), observing the polarity.
E. CONNECTING THE POWER CABLE AND RELAYS
LN
• The electrical supply should be fused
at no more than 3 amps via an un-
switched fused spur adjacent to the
unit.
• Note: Do not exceed maximum
voltage.
• The unit is equipped with a 12Vdc battery
back-up power circuit. If this option is
required connect the + and - (positive and
negative) battery leads (leads not supplied)
(g 6).
BATTERY BACKUP
• A separate battery unit is available
AT-BU which will house a 12Vdc 7Ah
battery - AT-BAT.
• Batteries should be tested, maintained
and replaced in accordance with the
battery manufacturers instructions
and recommendations.
CONNECT THE LEAK AND FAULT
(CABLE BREAK) RELAYS
The AT-ZAP has:
One volt free relay per zone
One 6Vdc latching solenoid output per zone
Two common LEAK relay
One summary FAULT relay
RELAY IDENTIFICATION
LEAK relays:
Positionon the left hand side of the
motherboard as shown on the Layout
Diagram number 7-12.
Figure 5
Figure 6
Unit 30, Lawson Hunt Industrial Park,
Broadbridge Heath, Horsham, West Sussex,
RH12 3JR
+44 (0) 1403 216100
www.aquilar.co.uk
SENSO R
RED
GR N
YEL
BLK
x3
x7
x10
x12
• See AT-ZAP Setup section for how to enable
zones.
• Linking out of zones is not required unless
they have been enabled in software. (see
g.4 for linking out details)
Figure 3
SENSO R
RED
GRN
YEL
BLK
x3
x7
x10
x12
Figure 4

AT-ZAP
Zone Alarm Panel
LEAK DETECTION SOLUTIONS
COMMON LEAK RELAY
Bottom left connections
FAULT RELAY:
The AT-ZAP’s FAULT relay will also indicate
power failure as the relay contacts will
de-energize to signal an alarm condition.
Therefore, loss of power as well as a cable
break would trip the relay and any equipment
connected.
Common to all zones relays are SPDT and
independent of the next.
N/O N/CC
6
Note: The relay plugs can accept wires 12 to
24 AWG. Cable should have a temperature
rating of 65°C.
Note: Maximum load for relays is 3 amps,
250Vac/24Vdc.
Unit 30, Lawson Hunt Industrial Park,
Broadbridge Heath, Horsham, West Sussex,
RH12 3JR
+44 (0) 1403 216100
www.aquilar.co.uk
1
2
3
4
56 7
1. Zone Enabled/Zone Names
2. Zone Status
3. Date and Time
4. System Status
5. Info Button
6. Settings Button
7. Mute / Reset Button
F. SETUP

LEAK DETECTION SOLUTIONS
7
Unit 30, Lawson Hunt Industrial Park,
Broadbridge Heath, Horsham, West Sussex,
RH12 3JR
+44 (0) 1403 216100
www.aquilar.co.uk
AT-ZAP
Zone Alarm Panel
For maximum exibility the AquiTron Zonal Alarm Panel (AT-ZAP) has many congurable
options to suit individual site conditions.
Congurable parameters are:
• Device Name - See Section F 1.1 Device Name
• Time/Date - See Section F1.2 Time & Date
• Zones – See Section F 1.3 Zones
• Relays – See Section F 1.4 Relays
• Solenoid outputs – See Section F 1.5 Solenoid Valve Outputs
• Accessory Voltage – See Section F 1.6 Accessory Voltage
• Re-Alarm Settings – See Section F 1.7 Re-Alarm Settings
• Manual Override – See Section F 2.1 Manual Override
• History options – See Section F 2.2 History Options
• Company Details – See Section F 3.1 Company Details
• Commissioning/Service Engineer Details – See Section F 3.2 Engineer Details
• Service Indicator – See Section F 3.3 Service Indicator
• Factory Reset – See Section F 3.4 Factory Reset
The settings button is used to access the settings menus. From here you have access to the
various submenus shown below.
To enter the Setup and installer menus passwords are required for access.
Use the on screen keyboard to enter the relevant password and press the ‘Enter’ button.

LEAK DETECTION SOLUTIONS
8
Unit 30, Lawson Hunt Industrial Park,
Broadbridge Heath, Horsham, West Sussex,
RH12 3JR
+44 (0) 1403 216100
www.aquilar.co.uk
AT-ZAP
Zone Alarm Panel
PASSWORD
Set up Menu: aquitron30
Installer Menu: aquitron12
F 1. SETUP MENU

LEAK DETECTION SOLUTIONS
9
Unit 30, Lawson Hunt Industrial Park,
Broadbridge Heath, Horsham, West Sussex,
RH12 3JR
+44 (0) 1403 216100
www.aquilar.co.uk
AT-ZAP
Zone Alarm Panel
F 1.1 DEVICE NAME
Settings>>Setup>>Password>>Device Name
The default name ‘AquiTron - AT-ZAP-12’ can be changed if required. For instance you may have
several systems on a site and wish to identify them separately.
When at the ‘set Device Name’ screen, use the onscreen keyboard to enter the required name
then press enter. The name will be changed. If a mistake is made, or to rename, repeat the
process.
Press back to exit.
F 1.2 TIME & DATE
Settings>>Setup>>Password>>Date/Time
Tabla de contenidos
Otros manuales de Sistema de seguridad de aquilar

aquilar
aquilar DOLEJSZ AquiTron AT-RAP-12 Instrucciones de instalación

aquilar
aquilar AquiTron AT-MZA Manual de usuario

aquilar
aquilar AquiTron AT-APA Manual de usuario

aquilar
aquilar AquiTron AT-RAP-230 Instrucciones de instalación

aquilar
aquilar SD2 Guía de configuración

aquilar
aquilar AquiTron AT-RAP-230 Instrucciones de instalación
Manuales populares de Sistema de seguridad de otras marcas

EDM
EDM Solution 6+6 Wireless-AE Manual de usuario

Highway Safety Group
Highway Safety Group EA401 Manual de usuario

Siren
Siren LED GSM Manual de usuario

Detection Systems
Detection Systems 7090i Instrucciones de montaje

Se-Kure Controls
Se-Kure Controls MicroMini SK-4841 Manual de usuario

Siemens
Siemens FDM273 Manual de usuario