Albion TMV2 Instrucciones de instalación

Albion Valves (UK) Ltd
www.albionvalvesuk.com
Email: [email protected]
Tel: 01226 729900
TMV2 ART 33 Screwed Rev 1
TMV2 Installation &
Operating Manual
ART 33
Screwed Thermostatic
Mixing Valve

2
TMV2 ART 33 Screwed Rev 1
Contents
1. Introduction
2. Approvals
3. TechnicalSpecication
4. Product Dimensions
5. Conditions of normal use (TMV2)
6. Installation and Assembly
7. Commissioning & Adjustment
8. Maintenance & In-Service Testing
9. TMV Cleaning Instructions
10. Warranty
1. Introduction
• Thevalvescoveredbytheseinstructionshavebeentestedandcertiedasbeingin
compliance with BS EN 1111 : 1999 & BS EN 1287 : 1999.
• Valves operating outside the requirements of these standards are not covered by the TMV
2 Scheme and are not guaranteed to operate as type 2 valves.
• The installer should be aware of his duty of care and responsibility in ensuring that
compliance with regulation is adhered to. The valve is not guaranteed to function correctly
totheTMV2specicationunlessitisinstalledandusedinaccordancewiththese
instructions.
• The Albion ART 33 thermostatic mixing valve is available in 15mm and 22mm size, is
intendedtobettedintoapplicationswherethereliablecontrolofhotwatertemperatureis
necessary to prevent scalding.
• In the event of cold-water supply failure, the product will shut off the hot water supply.
2. Approvals
• TheAlbionART33iscertiedunderboththeTMV2schemeandhasbeenindependently
tested by the recognized test laboratory NSF Wales and is a Water Regulations Advisory
Scheme (WRAS) approved product and the listed in the Water Fittings and Material
Directory.

3
TMV2 ART 33 Screwed Rev 1
3. Technical Specication
Factory Temperature Setting 42°C
Temperature Adjustment Range 30°C – 48°C
Mix Temperature Stability +/-2°C
Cold Water Supply Temperature 5°C – 25°C
Hot Water Supply Temperature 55°C – 65°C
Temperature Differential (Hot Inlet – Outlet) 12°C
Supply Pressure Imbalance 2:1
Maximum Static Pressure 10 Bar
4. Product Dimensions
Dimensions are given for ART 33 in Table 1
Table 1
Model DN Size B C D E
ART 33 1/2” 59 114 126 50.9
ART 33 3/4” 61 135 137 50.9

4
TMV2 ART 33 Screwed Rev 1
5. Conditions of Normal Use (TMV2)
Water Regulations
• The thermostatic mixing valve must be installed in accordance with the regulations of the
local water company and the Water Supply (Water Fittings) Regulations 1999.
Operating Pressure Range BS EN 1111 High Pressure BS EN 1287 Low Pressure
Maximum Static Pressure (Bar) 10 10
Hot & Cold Pressure (Bar) 0.5 – 5.0 0.1 – 1.0
Hot Supply Temperature (°C) 55 – 65 55 – 65
Cold Supply Temperature (°C) 5 – <25 5 – <25
Mix Water Temperature (°C) Maximum 46 Maximum 46
• Thermostatic Mixing Valves are temperature sensitive devices and must not be subjected
to extreme temperatures, either hot or cold, in use for installation.
• Valves operating outside these conditions of use cannot be guaranteed to operate as Type
2 valves.
• Designations of Use
HP - B / S / W / T
LP - B / S / W
6. Installation & Assembly

5
TMV2 ART 33 Screwed Rev 1
• The valve body is clearly marked with “C” and a blue indicator for cold and “H” and a red
indicator for hot.
• Before installation, the hot and cold-water inlet of the mixing valve must be clear of debris.
the valve must be correctly connected to the respective supplies.
• Isolationvalvesmustbettedadjacenttothevalveinlet.APressurereducingvalve(PRV)
mustbettedifdeemednecessary.
• Check the main valve assembly bores are free of debris and the end sealing faces are
clean.
• Checkthetwotailpiecesandconrmtheyarecompletewithunionnutsandcompression
nuts with olives.
• Insertthesealingwasherintotheinletsandoutletandscrewtheinletandoutletttings
onto the valve body, taking care not to over tighten.
• Assemble the valve to the pipe work and ensure the hot and cold-water pipes have full
penetration into the tailpieces.
• After installation check carefully for leaks.
• Thevalvemustalwaysbettedinalocationwhereitisaccessibleforbothtestand
maintenance.

6
TMV2 ART 33 Screwed Rev 1
Exploded View of ART 33
7. Commissioning & Adjustment
• The Albion ART 33 thermostatic mixing valve is supplied factory pre-set at 41--43°C.
However, installation conditions will dictate, that the product be adjusted on site.
• Prior to commencing commissioning, the following checks should be carried out
• The designation of the TMV matches the application.
• The supply pressures and temperatures are within the operating range of the valve.
• Isolatingvalvesaretted.
• The supply temperatures are within the range permitted for the valve and by
guidance information on the prevention of legionella etc.
• If all these conditions are met, proceed to set the temperature as below: -
• Remove the protective cap on top of the valve.
• Back-out the nut using a hexagon wrench:
o To increase the temperature, turn clockwise
o To decrease the temperature, turn anti-clockwise
• Temperature is in accordance with the valve application as per the table below: -
HP (0.5 – 5.0 Bar)
High Pressure
LP (0.1 – 1 Bar)
Low Pressure Application Maximum
Temperature (°C)
HP-B LP-B Bidet 38
HP-S LP-S Shower 41
HP-W LP-W Wash Basin 41
HP-T Bath 46

7
TMV2 ART 33 Screwed Rev 1
• When the valve has been installed with the correct conditions of use it is advised that
the valve is subjected to normal operation prior to the commissioning at the application
temperature. Operate the valve from full cold to full hot at least three times by removing
the blue plastic cap and using a hexagon wrench to adjust.
• With the valve at the full cold position bring the valve to the correct application
temperature by turning the nut clockwise. If the valve exceeds this temperature, return the
valve to the full cold condition, and reset it to the correct temperature +0-2°C. Do not set a
valve with a lowered temperature as this will not provide consistent operation.
• After adjustment replace the cap to lock the valve in position and prevent tampering.
• Commissioning Test sequence
• After adjusting the temperature of the mixed water in accordance with the valve application.
• Record the temperature of the hot and cold-water supplies.
• Recordthetemperatureofthemixedwateratthelargestdraw-offowrate.
• Recordthetemperatureofthemixedwateratasmallerdraw-offowrate,whichshallbe
measured.
• Isolate the cold-water supply to the mixing valve and monitor the mixed water temperature
recordingthemaximumtemperatureachievedandthenalstabilizedtemperature.
• Record the equipment, thermometer etc. used for the measurements.
• Thenalstabilisedtemperaturemustnotexceedthevaluesinthetablebelowandmust
never exceed 46°C: -
Application Max Temperature °C
Bidet 40
Shower 43
Wash Basin 43
Bath 46 (note 1)
Note 1
• 46°C is the maximum mixed water temperature from the bath tap. The
maximum temperature takes account of the allowable temperature tolerances inherent in
thermostatic mixing valves and temperature losses in metal baths. It is not a safe bathing
temperature for adults or children.
• The British Burns Association recommends 37 to 37.5°C as a comfortable
bathing temperature for children. In premises covered by the Care Standards Act 2000,
the maximum mixed water outlet temperature is 43°C.

8
TMV2 ART 33 Screwed Rev 1
8. Maintenance & In-Service Testing
• The purpose of in-service testing is to regularly monitor and record the performance of the
thermostatic mixing valve. Deterioration in performance can indicate the need for service
work on the valve and/or water supply.
• Carry out the test sequence using the same or equivalent equipment used for
commissioning the valve.
• Ifthemixedwatertemperaturehaschangedsignicantlyfromtheprevioustestresults
(e.g. >1°C), record the change and before re-adjusting the mixed water temperature carry
out the following checks;
• Allin-lineorintegralltersareclean.
• Any in-line or integral non-return valves or other anti-back siphonage devices are in
good working condition.
• Any isolation valves are fully open.
• With an acceptable mixed water temperature, complete the test sequence as per section 7
of this document.
• In the absence of any other instruction or guidance, it is recommended that In-Service
Tests are carried out once every 12 months as a minimum. If the temperature is outside
of the expected range it will be necessary to remove and clean the valve in accordance
with cleaning procedure prior to recommissioning.
• Ifthereisaresidualowduringthecommissioningorbi-annualverication(cold
water supply isolation test) then this is acceptable providing the temperature of the water
seeping from the valve is no more than 2° above the designated maximum mixed water
outlet temperature setting of the valve.
• Ifawatersupplyisfedbygravitythenthesupplypressureshouldbeveriedtoensurethe
conditions of use are appropriate for the valve.
• Temperaturereadingsshouldbetakenatthenormalowrateafterallowingthesystem
to stabilize. The sensing part of the thermometer probe must be fully submerged in
the water that is to be tested. Any TMV that has been adjusted or serviced must be re-
commissioned and re-tested in accordance with the manufacturer’s instructions.

9
TMV2 ART 33 Screwed Rev 1
9. TMV Cleaning Instructions
• Most domestic water supplies contain calcium which will separate out when the water is
heated in a system. The degree and speed of scaling may vary depending on factors such
aswaterowrates,systemdesign,thehardnessofthewaterandthetemperatureto
which the water is heated.
• Deposits of scale may over time form in the valve, particularly at the hot inlet. The
formation of the scale may adversely affect the performance of the valve which will be
detected during the in-service testing. If this occurs it will be necessary to remove
the valve for de-scaling and service.
Cleaning Procedure
• Isolate the hot and cold supply.
• Remove the valve to a clean working area.
• Remove the protective cap.
• Unscrew the headwork of the valve.
• Carefully remove the temperature sensitive thermal element and piston assembly and put
to one side.
• Removethemainspringandowguideandcarefullyputtooneside.
• Inspect the components for contamination or damage.
• Clean or replace as necessary.
• There may be a need to periodically grease components. Please ensure that the grease is
WRAS approved.
• Remove the O-ring.
• Clean the valve body and headwork using a propriety de-scaler.
• Thoroughly rinse the body and headwork in clean water.
• CarefullytO-ringtobody.
• Carefullyre-tallcomponentsandperformthecommissioningsequence.

10
TMV2 ART 33 Screwed Rev 1
10. Warranty
• Albion Valves (UK) Ltd offer a 12 month guarantee of the ART 33 TMV.
• The guarantee offered covers manufacturing / material defects.
• Theguaranteewillbevoidshouldtheproductnothavebeenttedandmaintainedasper
Albion Valves (UK) Ltd instruction.
• Accidental damage is not covered by the guarantee.
Tabla de contenidos
Otros manuales de Unidad de control de Albion

Albion
Albion ART24 Manual de instrucciones

Albion
Albion ART 22 Manual de instrucciones

Albion
Albion ART 622 Instrucciones de instalación

Albion
Albion ART 679 Instrucciones de instalación

Albion
Albion ART 22 Instrucciones de instalación

Albion
Albion TMV3 Instrucciones de instalación

Albion
Albion ART 20C Instrucciones de instalación
Manuales populares de Unidad de control de otras marcas

Festo
Festo Compact Performance CP-FB6-E Manual de lista de piezas

Elo TouchSystems
Elo TouchSystems DMS-SA19P-EXTME Manual de usuario

JS Automation
JS Automation MPC3034A Manual de usuario

JAUDT
JAUDT SW GII 6406 Series Guía rápida

Spektrum
Spektrum Air Module System Manual de usuario

BOC Edwards
BOC Edwards Q Series Manual de usuario











