Afore SAPM-10KW Manual de usuario

Installation and Operation Manual
Zero Injection Smart Meter
Building 7, No.333 Wanfang Rd, Minhang District, Shanghai, China. 201112
Version: A00001-01

Contents
1. About This Manual . . . . . . . . . . . . . . . . . . . . . .
2. Parameter. . . . . . . . . . . . . . . . . . . . . . . . . . .
3. Zero-injection Connection . . . . . . . . . . . . . . . . . .
4. Connect the Smart Meter to Single-phase System . . . . .
4.1 System Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.2 Inverter Setting . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.3 Single-phase System Wiring Diagram . . . . . . . . . . . . . . . . . .
5. Single-phase Inverter Zero-Injection FAQ . . . . . . . . . .
6. Explanation of Smart Meter Display Content . . . . . . . .
7. Connect the Smart Meter to Three-phase System . . . . . .
7.1 System Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7.2 Three-phase 3-25kW Inverter Setting . . . . . . . . . . . . . . . . . .
7.3 Three-phase 30-60kW Inverter Setting . . . . . . . . . . . . . . . . .
7.4 Multiple Inverter System Connection Setting . . . . . . . . . . . . . .
7.5 Wiring Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7.6 CT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7.7 Current Ratio Setting . . . . . . . . . . . . . . . . . . . . . . . . . . .
8. Three-phase Inverter Zero-Injection FAQ . . . . . . . . . .
8.1 Three-phase 3-25kW Zero-Injection FAQ . . . . . . . . . . . . . . . .
8.2 Three-phase 30-60kW Zero-Injection FAQ . . . . . . . . . . . . . . . .
9. Explanation of Smart Meter Display Content . . . . . . . .
10. Trouble Shooting . . . . . . . . . . . . . . . . . . . . . .
1
1
2
5
5
6
7
7
9
10
10
11
12
14
16
17
17
18
18
20
22
23

1. About This Manual
2. Parameter
Afore smart meter is an intelligent control device, which is designed for
grid-connected inverters. Its main function is to measure the generation and
consumption, transmit the data to the inverter through RS485 communication, to
ensure that the generated power of the inverter is less or equal to the user’s load.
Achieve the purpose of no power feed into the grid.
This manual describes the installation, operation and maintenance of the
following Afore Smart Meter.
About This Manual
01
Type
Power ( kW )
Max Power ( kW )
Accuracy ( % )
Rating voltage ( V )
Voltage Range ( V )
Rating Current ( A )
Max Current ( A )
Connection For Measurement ( Hz )
Type TAPM-50KW
50
55
1
230/400
320-440
72.5
80
Direct Connect
TAPM-130KW
130
150
1
230/400
320-440
200(MAX 5000 )
220(MAX 5000)
Via CT(current transducers)
SAPM-10KW
10
18
1
230
184-253
50
80
Direct Connect
For Single-phase System Applica�on
SAPM-10kW
For Three-phase System Applica�on
TAPM-50kW, TAPM-130kW
Frequency Range ( Hz )
Grid Type
Communication
Dimmension (W,L,H , mm)
IP
Installation
45-65
L+N
RS485
36 x 98 x 65
45-65
3P+N
RS485
72 x 100 x 65
IP20
35mm Rail

Zero-injection Connection 02
a. Single-phase Smart Meter
b. Three-phase Smart Meter
1. CAT5/CAT6 cable should be used between smart meter and inverter
Maximum length of cable less than 300m
2. Meter connection on the inverter
The meter needs to be connected to the inverter’s Zero-injection
port (RJ45 terminal).
3. Zero-injection Connection
Note:

Zero-Injection Wiring
03
1. For single-phase inverter, please follow below pin order
RS485A (Pin 7) to single-phase meter (Pin 24)
RS485B (Pin 8) to single-phase meter (Pin 25)
2. For three-phase 3-25kW inverter, please follow below pin order
RS485A (Pin 3 / 4) to three-phase meter (Pin 24)
RS485B (Pin 1 / 2) to three-phase meter (Pin 25)
3. For three-phase 30-60kW inverter, please follow below pin order
RS485A (Pin 1) to three-phase meter (Pin 24)
RS485B (Pin 2) to three-phase meter (Pin 25)
Note:
RJ45 Pin order for single-phase inverter
RJ45 Pin order for three-phase 30-60kW inverter
1. White green
2. Green
3. White orange
4. Blue
5. White blue
6. Orange
7. White brown
8. Brown
568B Standard
1234567812345678
(A) (B)
1. White orange
2. Orange
3. White blue
4. Blue
5. White blue
6. Green
7. White brown
8. Brown
568B Standard
(A) (B)
12345678
Zero-Injec�on Connector wiring for three-phase 3-25kW inverter
1/2
3/4
PIN Asignment
RS485 B
RS485 A

24A 25B
Zero-Injection Wiring 04
The distance between the inverter and smart meter is suggested sless
than 100M. For the distance more than 100M, it needs to parallel a
120Ω resistor between 24A and 25B of the smart meter.
Note:
Single-phase Smart Meter
Three-phase Smart Meter
24A 25B
24A 25B
24A 25B

Connect the Smart Meter to Single-phase System
05
4. Connect the Smart Meter to Single-phase System
4.1 System Diagram
PV GENERATOR
Afore Simplex
SAPM-10KW Meter
HOUSEHOLD CONSUMERS
GRID
Communication path
Power path
......
RS485
HNS1000TL-1~HNS10000TL
Inverter
LOAD
CT
L N
RS485B
RS485A
I*
LINE
DDSU666 DIN-RAIL METER
230V */100mA 800imp/kWh
(White)
87
65
3 4
I(Blue)
Note:
When the load exceeds 10kW, a CT needs to be added, see the
figure below:

Connect the Smart Meter to Single-phase System
06
Afore New Energy Normal
Power=xx W
1s Delay
ENT
ENT
ENT
Upstream: ON
ENT
Step 2
Step 1
UP/DOWN
Choose Function Enable
UP/DOWN Choose ON
press ENT to confirm
PassWord
xxxx
UP/DOWN
Choose password: 5432
Setting
Inverter Info
Function Enable
safety
UP/DOWN
Choose Setting
ESC
Press ENT
Choose MeterFun
4.2 Inverter Setting
ESC
UP/DOWN
Choose Zero Injection
Zero Injection
safety
UP/DOWN Choose ON
press ENT to confirm
PassWord
xxxx
UP/DOWN
Choose password: 5432
ENT
MeterFun: OFF
PtoGrid:xxW
MeterFun: ON
PtoGrid:xxW

a. After complete wiring between smart meter and inverter. The power Pdisplay
on the smart meter will synchronize with inverter Pac display.
Single-phase Inverter Zero-Injection FAQ
07
Step 3
Note:
After activate "Zero Injection" function, please restart the inverter.
4.3 Single-phase System Wiring Diagram
5. Single-phase Inverter Zero-Injection FAQ
Afore
Inverter
Load
Meter AC
L
pin
8
pin
7
L
4
3
2
25
24
1
N
N
L
N
UP
DOWN
ESC
ENT
POWER FAULTGRID
INTemp = 35.1℃
Pac = 932.2 W
Inverter Pac
Three-phase Smart Meter
932.2

b. If the Zero-injection function is not activated or communication cable is not well
connected, the power displayed on the inverter is Pac=0W.
Single-phase Inverter Zero-Injection FAQ
08
c. If the smart meter’s pin order is incorrect wiring, the Smart Meter and the
inverter Pac will display negative values.
Note:
Due to the fluctuation on the grid side, the data transition delay will
occur between smart meter and inverter. And the values displayed on
the smart meter and inverter will be different.
Note:
The button on the smart meter cannot be kept pressing for a long
time, it can only be pressed intermittently, otherwise the meter will be
locked.
UP
DOWN
ESC
ENT
POWER FAULTGRID
INTemp = 35.1℃
Pac = 0 W
Inverter Pac
Single-phase Smart Meter
932.2
UP
DOWN
ESC
ENT
POWER FAULTGRID
INTemp = 35.1℃
Pac = - 932.2 W
Inverter Pac
Single-phase Smart Meter
-932.2
Este manual sirve para los siguientes modelos
2
Tabla de contenidos
Manuales populares de Instrumento de medición de otras marcas

Endress+Hauser
Endress+Hauser Proline Promag 50 Especificaciones técnicas

Siemens
Siemens SITRANS F Coriolis FCT030 Manual de lista de piezas

KLINGER
KLINGER CMF V Series Manual de usuario

EXFO
EXFO FTB-2 Manual de operación y mantenimiento

Keysight
Keysight M8290A Manual de usuario

ADTEK
ADTEK MW-5 Manual de usuario