Internal Wiring
4
CAUTION: For continued protection against risk of fire, replace only with
same type and rating of fuse.
F3: Little fuse, 218 Series, 6.3A/250V time delay, 5 x 20 mm
F1, F2: Wickmann, TE5 Series, 5.0A Time Delay, short pin
Notes:
1. This product must be connected to mains supply only by permanent field
wiring using the following wire type: THWN, 18 AWG - 250 KCMIL 300 V,
Nylon jacketed w/ high dielectric PVC insulation (UL-83, UL-1063 and UL-
758).
2. All electrical connection and conduits are to be made per National Electric Code
ANSI/NFPA70, or per the applicable code in the country of installation. Use only
conduit and conduit fittings that meet UL 797 safety standard.
3. All wire terminal splice connectors must be UL and CSA rated up to 300 V per UL
486 and temperature rated per UL Flammability UL 94V-2/HB.
This product is intended for use single phase power distribution systems and
relies on the building's installation for short-circuit (over current) protection
and line voltage disconnect. Protective device (circuit-breaker) rating must
not exceed 20 Amps. The installer of this equipment is responsible for
provisioning this circuit-breaker, which must be located in the electrical
distribution panel (breaker-panel) of the building, in close proximity to the
PL-1 thermostat(s) and clearly labeled as being the disconnect for the product.
Compliance is checked by inspection.
ELECTRICAL SHOCK HAZARD: DISCONNECT BREAKERS BEFORE
SERVICING OR INSTALLING THIS PRODUCT!