AUTOMATION COMPONENTS, INC Version : 5.0
2305 Pleasant View Road I0000777
Middleton, Wisconsin 53562 Page 6 of 6
www.workaci.com (888) 967-5224
PRODUCT SPECIFICATIONS
Supply Voltage 4-20 mA Output: 16-36 VDC (250 Ohm Load max.) / 22-36 VDC (500 Ohm Load max.)
0-5 VDC / 0-10 VDC Output: 16-36 VDC / 24 VAC (+/- 10%)
Supply Current 4-20 mA Output: 24 mA minimum | 0-5 VDC / 0-10 VDC Output: 6 mA maximum
Output Signals Current Output: 4-20 mA, 2-Wire Loop Powered (Standard); (Current limited to 21.4 mA max)
Voltage Signals: 0-5 VDC / 0-10 VDC Field Selectable, 3-Wire; Output limited @ 5.25 & 10.5
VDC)
Response Time (0-100%
FSO)
8 seconds
Output Update Rate 1 second
Pressure Ranges See Product Ordering Grid (Data Sheet); Field Selectable Uni and Bi-Directional Ranges
Accuracy¹ +/- 0.5% FSO; +/- 0.25% (Only for Specified Range)
Zero Function Pushbutton Zero Function
Thermal Effects² +/- 0.067% FSO / °F (0.12% FSO / °C)
Proof Pressure / Burst A/DLP-001: Proof: 270 inWC (67.2 kPa) | Burst: 415 inWC (103.3 kPa) for 1 inWC (249.8 Pa)
Pressure³ A/DLP-010: Proof: 350 inWC (87.12 kPa) | Burst: 550 inWC (136.9 kPa) for 10 inWC (2490.8 Pa)
A/DLP-040: Proof: 562 inWC (140 kPa) | Burst: 1004.7 inWC (250 kPa) for 40 inWC (9963.6 Pa)
Operating Temperature
Range
-4 to 185°F (-20 to 85°C)
Compensated Temperature
Range
32 to 122°F (0 to 50°C)
Storage Temperature
Range
-22 to 185°F (-30 to 85°C)
Operating Humidity Range 10 to 95% RH, non-condensing
Media Types Dry air or inert non-conductive gases
Enclosure Material /
Flammability Rating
Flame Retardant Polycarbonate; UL94-5VA
Wiring Connections Finger Pushbutton (Spring) Terminal Blocks; accepts 16-24 AWG wires
Conduit Knockouts Watertight Cordgrip Installed (1/2" NPT Conduit fittings accepted when Cordgrip removed)
Pressure Fitting Material Nickel Plated Brass or Stainless Steel
Tubing Size Accepted 1/4" O.D. x 0.170" I.D. Poly Tubing
Approvals CE, Reach, RoHS2, WEEE
Product Weight (No Pitot
Tube OR Din Rail)
Non-LCD Display Version: 0.53 lbs (0.240 kg) | LCD Display Version: 0.58 lbs (0.263 kg)
Product Weight (With Pitot
Tube & Din Rail)
Non-LCD Display Version: 0.80 lbs (0.363 kg) | LCD Display Version: 0.85 lbs (0.385 kg)
NIST Certification 3 Point: Test Points 10%, 50%, and 90% FSO
5 Point: Test Points 10%, 30%, 50%, 70% and 90% FSO
Note¹: Accuracy includes linearity, hysteresis & repeatability.
Note²: Shift is relative to 77°F (25°C).
Note³: "x" designates both the LCD "-D-" & Non-LCD Display "-N-" versions.
Table 2: Product Specifications
WARRANTY SPECIFICATION
The DLP Series pressure transmitters are covered by ACI’s Five (5) Year Limited Warranty, which is located in the front of ACI’S
SENSORS & TRANSMITTERS CATALOG or can be found on ACI’s web site: www.workaci.com.