AUTOMATION COMPONENTS, INC Version : 3.0
2305 Pleasant View Road I0000777
Middleton, Wisconsin 53562 Page 5 of 5
www.workaci.com (888) 967-5224
PRODUCT SPECIFICATIONS
Supply Voltage 4-20mA Output: 250 Ohm Load 16-36 VDC
4-20mA Output: 500 Ohm Load 20-36 VDC
0-5 VDC Output: 16-36 VDC / 24VAC (+/-10%)
0-10 VDC Output: 16-36 VDC / 24VAC (+/-10%)
Supply Current 24mA minimum
Output 2-wire, 4 to 20mA DC Current
or 3-wire, 0-5 or 0-10VDC
Sensor Accuracy1 ±0.5% FSO (includes linearity, hysteresis and repeatability)
±0.25% FSO with special calibration
Response Time 8 S
Operating Temperature Range -4 to 185°F (-20 to 85°C)
Compensated Temperature Range 32 to 122°F (0 to 50°C)
Humidity 10 to 95% RH, non-condensing
Thermal Effects2 ±0.067%FSO/ ºF (±0.12%FSO/ ºC)
Proof Pressure 270 inWC (67.2 kPa) for 1 inWC(0.25 kPa) range
350 inWC (87.1 kPa) for 10 inWC(2.5 kPa) range
562 inWC (140 kPa) for 40 inWC(9.95 kPa) range
Burst Pressure 415 inWC (103.3 kPa) for 1 inWC(0.25 kPa) range
550 inWC (136.9 kPa) for 10 inWC(2.5 kPa) range
1004.7 inWC (250 kPa) for 40 inWC(9.95 kPa) range
Media Dry air or inert non-conductive gases
Features DIP switch selectable ranges and outputs
Push button/Remote Auto Zero
Finger Push-Button Terminal Blocks
LCD Features (optional) Large 4-digit LCD display
DIP switch selectable display units (Pa or inWC)
Out-Of-Range Diagnostic Output
Enclosure UL94-V5 rated, flame retardant Polycarbonate
Approvals REACH
RoHS
WEEE
Note 1: Accuracy includes linearity, hysteresis and repeatability.
Note 2: Shift is relative to 77°F (25°C).
Table 2: Product Specifications
WARRANTY SPECIFICATION
The DLP Series pressure transmitters are covered by ACI’s Five (5) Year Limited Warranty, which is located in
the front of ACI’S SENSORS & TRANSMITTERS CATALOG or can be found on ACI’s web site:
www.workaci.com.