Ablerex ATS-16A Manual de usuario

ATS-16A/20A/30A/32A
Automatic Transfer Switch
User Manual

1
Table of Contents
1. Safety Instructions..................................................................................2
2. Product Description................................................................................3
3. Installation and Operating Instructions...................................................6
3.1.Packaging...............................................................................................6
3.2.Choose an installation location ..............................................................6
3.3.Product Introduction...............................................................................7
3.4.Product Installation and Operation.......................................................14
4. Troubleshooting....................................................................................17
5. System Specifications..........................................................................18
6. Appendix A. Dry contacts available for configuration...........................20
7. Appendix B. SNMP Card available Error Code....................................21
8. Appendix C. LCD available Error Code................................................22

2
1. Safety Instructions
SAVE THESE INSTRUCTIONS. This manual contains important
instructions that should be followed during installation and
maintenance of the ATS.
1. Do not disassemble this product without a technician from the original
manufacturer or authorized distributor. Doing so voids your warranty and is
also a shock hazard.
2. Every component of this product is checked for high specification standards.
Performance maintenance or parts replacement should only be done by a
qualified technician or authorized distributor.
3. Do not install the product at the following locations without a qualified
technician:
Medical equipment directly related to human life preservation;
Equipment on elevators or rapid transit systems related to personal safety;
Critical computing hardware for public systems;
Other equipment similar to the ones mentioned above.
4. Please discuss with your distributor before installing the product at the
locations mentioned above. Special considerations and designs are required
for the operation, setup, management, and maintenance of critical equipment
and emergency backup power generators related to personal safety and
public facilities.
5. Do not place vases or other water containers on top of the main unit. Water
spilled into the machine may damage internal components and pose a shock
hazard.
6.Using this product in locations with sparks, smoke, or natural gas may result in
arcing, personal injury, and fire hazards.
7.The operating environment and storage method affects the product lifespan
and malfunctions. Thus, please keep the product away from the following
operating environments:
Locations specified in the operating manual as high temperature, low
temperature, and high humidity (temperatures outside -5 to 40 a℃nd
relative humidity outside 0% to 90%);
Locations with sparks;
Locations with dust, corrosive material, salt content, or flammable gas;
Outdoors.
8.Immediately stop using this product in the event of abnormal sounds or odors.
Contact your distributor for maintenance.
9.Improper grounding results in electrical leakage. Please make sure your AC
input power is properly grounded.
10.Please confirm the input voltage does not exceed the rated capacity of the
ATS.

3
2. Product Description
ATS Feature:
The ATS (Automatic Transfer Switch) features two independent power
supply circuits supplying power to the load (as shown in Figure 1 below). In the
event of a power failure in the main circuit, the ATS automatically switches to the
other circuit to supply power to the load. The ATS automatically switches back to
the main circuit after power is restored. In addition, the ATS also provides user
configurable power states (voltage or frequency) for the ATS switching condition.
Figure 1. ATS block diagram
ITS Feature:
ITA is a ATS module plus maintenance function. It can continue to
power its output load during maintain or replace the ATS module.
Figure 2. ITS HOT SWAP block diagram
Load
SOURCE A
SOURCE B

4
Procedure for replacing or maintaining ATS module in ITS product
1. To turn “Source Switch” to “Source A” position if ATS module powers
load by Source A, otherwise to turn “Source Switch” to “Source B”
position.
ATS
Source A
Source B
LOAD
SourceSwitch
OutputSwitch
1.
2.
2. To turn “Output Switch” from “Normal” to “Bypass” position. It will have
4ms maximum breaker time at this step. Now the load power comes
from Bypass loop.
Source A
Source B
LOAD
SourceSwitch
OutputSwitch
1.
2.
3. To maintain or replace ATS module.
4. To command output source of ATS module same as Bypass loop.
5. To turn “Output Switch” from “Bypass” to “Normal” position. It will have
4ms maximum breaker time at this step. Now the load power comes
back to ATS loop.

5
ATS
Source A
Source B
LOAD
SourceSwitch
OutputSwitch
1.
2.

6
3. Installation and Operating Instructions
3.1. Packaging
3.1.1. Remove the PE foam.
3.1.2. Inspect accessories
○
1RS-232 cable x1 pcs
○
2USB cable x1 pcs
○
3CD (monitoring software, Setting tool ) x1 pcs
○
4User manual
○
5Handle and screws x1 set
○
6Backplate and screws x1 set (only ATS Standard Series)
3.2. Choose an installation location
An appropriate installation location will optimize system performance,
reduce the chances of malfunctions, and prolong product lifespan. Please follow
the guidelines below for an appropriate location:
3.2.1. Avoid excessive high temperature or high humidity;
3.2.2. Keep away from dust, volatile gases, excessive salt content, or
corrosive gases;
3.2.3. Do not use outdoors.

7
3.3. Product Introduction
3.3.1. Front Panel
No. Item Description/function
○
1Mute button Turns off alarm
○
2Source selection button Select source to view info: Input A, Input B, or
Load
○
3Info selection button Select source info to view: Voltage, current,
frequency, load capacity
○
4Input selection button Switch input source: Input A Input B
○
5LCD System status display
○
6Error indicator Lit: System malfunction or abnormal
Dim: System normal
○
7Input indicator B Lit: Normal input voltage and frequency
Dim: Abnormal input voltage and frequency
Flashing: Indicates higher priority
○
8Input indicator A Lit: Normal input voltage and frequency
Dim: Abnormal input voltage and frequency
Flashing: Indicates higher priority
○
9USB port Connection for software setup or monitoring
software
○
10 RS-232 port Connection for software setup or monitoring
software
○
11 Dry contact port Dry Contact
○
12 External communication
slot For external communication cards, e.g. RS-
485, SNMP

8
3.3.2. LCD
Symbol Description/function
Input A error or power failure
Input B error or power failure
Overload
System malfunction or abnormal
Alarm on
Alarm off
Digital display showing input/output power
connected to load
ATS numeric display

9
3.3.3. Rear Panel
ATS Standard Series:
ATS-120(120V-20A)
ATS- 130(120V-30A)
ATS-216(230V-16A)
ATS- 232(230V-32A)
Este manual sirve para los siguientes modelos
7
Tabla de contenidos