Ventis TT Silent-M 100 Manual de usuario

VENTS INLINE FANS IN
SOUND-INSULATED CASING
USER’S MANUAL
www.ventilation-system.com
TT Silent-M
EN

2
EN
This user’s manual is a main operating document intended for technical, maintenance, and operating staff.
The manual contains information about purpose, technical details, operating principle, design, and installation of the
TT Silent-M unit and all its modifications.
Technical and maintenance staff must have theoretical and practical training in the field of ventilation systems and should
be able to work in accordance with workplace safety rules as well as construction norms and standards applicable in the
territory of the country.
FOLLOW THE USER’S MANUAL REQUIREMENTS TO ENSURE DURABLE AND
TROUBLE-FREE OPERATION OF THE UNIT
CONTENTS
Safety requirements.......................................................................................................................................................................................................................... 3
Delivery set ............................................................................................................................................................................................................................................ 9
Operation guidelines ....................................................................................................................................................................................................................... 9
Brief description ................................................................................................................................................................................................................................. 9
Product sales ......................................................................................................................................................................................................................................... 9
Designation key ................................................................................................................................................................................................................................. 11
Installation and set-up..................................................................................................................................................................................................................... 12
Connection to power mains ....................................................................................................................................................................................................... 18
Electronics operation algorithm ............................................................................................................................................................................................... 23
Technical maintenance................................................................................................................................................................................................................... 25
Troubleshooting.................................................................................................................................................................................................................................. 26
Storage and transportation regulations............................................................................................................................................................................... 26
Manufacturer’s warranty................................................................................................................................................................................................................ 27

3
EN
All user’s manual requirements as well as the provisions of all the
applicable local and national construction, electrical, and technical
norms and standards must be observed when installing and operating
the unit.
Disconnect the unit from the power supply prior to any connection,
servicing, maintenance, and repair operations.
Only qualied electricians with a work permit for electrical units
up to 1000 V are allowed for installation. The present user’s manual
should be carefully read before beginning works.
Check the unit for any visible damage of the impeller, the casing, and the
grille before starting installation. The casing internals must be free of any
foreign objects that can damage the impeller blades.
While mounting the unit, avoid compression of the casing! Deformation
of the casing may result in motor jam and excessive noise.
Misuse of the unit and any unauthorised modifications are not allowed.
Do not expose the unit to adverse atmospheric agents (rain, sun, etc.).
SAFETY REQUIREMENTS

4
EN
Transported air must not contain any dust or other solid impurities,
sticky substances, or fibrous materials.
Do not use the unit in a hazardous or explosive environment containing
spirits, gasoline, insecticides, etc.
Do not close or block the intake or extract vents in order to ensure the
efficient air flow.
Do not sit on the unit and do not put objects on it.
The information in this user’s manual was correct at the time of the
document’s preparation.
The Company reserves the right to modify the technical characteristics,
design, or configuration of its products at any time in order to
incorporate the latest technological developments.
Never touch the unit with wet or damp hands.
Never touch the unit when barefoot.

5
EN
This unit is not intended for use by persons (including children) with
reduced physical, sensory or mental capabilities, or lack of experience
and knowledge, unless they have been given supervision or instruction
concerning use of the unit by a person responsible for their safety.
Children should be supervised to ensure that they do not play with the
unit.

6
EN
Connection to the mains must be made through a disconnecting
device, which is integrated into the fixed wiring system in accordance
with the wiring rules for design of electrical units, and has a contact
separation in all poles that allows for full disconnection under
overvoltage category III conditions.
If the supply cord is damaged, it must be replaced by the manufacturer,
its service agent, or similarly qualified persons in order to avoid a safety
hazard.
CAUTION: In order to avoid a safety hazard due to inadvertent resetting
of the thermal cut-out, this unit must not be supplied through an
external switching device, such as a timer, or connected to a circuit that
is regularly switched on and off by the utility.

7
EN
Ensure that the unit is switched off from the supply mains before
removing the guard.
WARNING: If there are any unusual oscillating movements, immediately
stop using the unit and contact the manufacturer, its service agent or
suitably qualified persons.
The replacement of parts of the safety suspension system device shall
be performed by the manufacturer, its service agent or suitably qualified
persons.

8
EN
THE PRODUCT MUST BE DISPOSED SEPARATELY AT THE END OF ITS SERVICE LIFE.
DO NOT DISPOSE THE UNIT AS UNSORTED DOMESTIC WASTE.
Fixing means for attachment to the ceiling such as hooks or other
devices shall be fixed with a sufficient strength to withstand 4 times the
weight of the appliance.
The mounting of the suspension system shall be performed by the
manufacturer, its service agent or suitably qualified persons.
The appliance is to be installed so that the blades are more than 2.3m
above the floor.
Precautions must be taken to avoid the back-flow of gases into the room
from the open flue of gas or other fuel-burning appliances.

9
EN
DELIVERY SET
Fan 1 pc.
Screws with dowels 4 pcs.
Plastic screwdriver (only for the models with a timer) 1 pc.
User’s manual 1 pc.
Packing box 1 pc.
OPERATION GUIDELINES
The fan is rated for connection to single-phase AC 220-240 V/50 Hz or 220 V/60 Hz power mains.
The unit is rated for continuous operation.
The arrow on the fan casing must match the air direction in the system.
The fan is rated as a class II electric appliance.
Ingress protection rating against access to hazardous parts and water ingress is IPX4.
The fan is rated for operation at the ambient air temperature from +1 °C up to +40 °C.
Power [V/Hz] Transported air temperature [°C]
220-240/50 -25...+60
220/60 -25...+40
BRIEF DESCRIPTION
The unit described herein is a mixed-flow duct fan for supply or exhaust ventilation of premises. The fan is designed for
connection to ø 100, 125, 150, 160, 200, 250 and 315 mm air ducts.
An external control unit can be connected to the fan.
The fan design is constantly being improved, thus some models may be slightly different from those described in this manual.
To comply with the ErP 2018 regulation, a local demand controller and speed controller must be used.

10
EN
Overall dimensions:
Ø D B H L M N
TT Silent-M 100 98 243 237 505 231 44
TT Silent-M 125 123 243 237 474 231 44
TT Silent-M 150 148 274 263 580 231 44
TT Silent-M 160 157 274 263 580 231 44
TT Silent-M 200 198 392 295 560 310 115
TT Silent-M 250 248 445 360 665 370 130
TT Silent-M 315 313 526 434 785 450 180
L L
øD H øD H
BM BM
NN