Vega VEGASON 61 Manual de usuario

Quick setup guide
Ultrasonic sensor for continuous level
measurement
VEGASON 61
Two-wire 4 … 20 mA/HART
Document ID: 51852

2
Contents
VEGASON 61 • Two-wire 4 … 20 mA/HART
51852-EN-231026
Contents
1 For your safety ......................................................................................................................... 3
1.1 Authorised personnel ....................................................................................................... 3
1.2 Appropriate use................................................................................................................ 3
1.3 Warning about incorrect use............................................................................................. 3
1.4 General safety instructions............................................................................................... 3
1.5 Conformity........................................................................................................................ 3
1.6 NAMUR recommendations .............................................................................................. 4
1.7 Environmental instructions ............................................................................................... 4
2 Product description................................................................................................................. 5
2.1 Conguration.................................................................................................................... 5
3 Mounting................................................................................................................................... 6
3.1 Mounting instructions ....................................................................................................... 6
4 Connecting to power supply................................................................................................... 7
4.1 Connection procedure...................................................................................................... 7
4.2 Wiring plan, single chamber housing................................................................................ 8
4.3 Wiring plan, double chamber housing .............................................................................. 8
5 Set up with the display and adjustment module PLICSCOM .............................................. 9
5.1 Insert display and adjustment module.............................................................................. 9
5.2 Setup steps ...................................................................................................................... 9
5.3 Menu schematic............................................................................................................. 12
6 Set up with smartphone/tablet, PC/notebook via Bluetooth............................................. 15
6.1 Preparations................................................................................................................... 15
6.2 Connecting..................................................................................................................... 17
6.3 Sensor parameter adjustment........................................................................................ 17
7 Supplement ............................................................................................................................ 19
7.1 Technical data ................................................................................................................ 19
Information:
This quick setup guide enables quick setup and commissioning of
your instrument.
Youcanndsupplementaryinformationinthecorresponding,more
detailed Operating Instructions Manual as well as the Safety Manual
thatcomeswithinstrumentswithSILqualication.Thesemanualsare
available on our homepage.
Operating instructions VEGASON 61 - Two-wire 4 … 20 mA/
HART: Document-ID 28775
Editing status of the quick setup guide: 2023-10-24

3
1 For your safety
VEGASON 61 • Two-wire 4 … 20 mA/HART
51852-EN-231026
1 For your safety
1.1 Authorised personnel
All operations described in this documentation must be carried out
only by trained and authorized personnel.
During work on and with the device, the required personal protective
equipment must always be worn.
1.2 Appropriate use
VEGASON 61 is a sensor for continuous level measurement.
Youcannddetailedinformationabouttheareaofapplicationin
chapter "Product description".
Operational reliability is ensured only if the instrument is properly
usedaccordingtothespecicationsintheoperatinginstructions
manual as well as possible supplementary instructions.
1.3 Warning about incorrect use
Inappropriate or incorrect use of this product can give rise to applica-
tion-specichazards,e.g.vesseloverllthroughincorrectmounting
or adjustment. Damage to property and persons or environmental
contamination can result. Also, the protective characteristics of the
instrument can be impaired.
1.4 General safety instructions
This is a state-of-the-art instrument complying with all prevailing
regulations and directives. The instrument must only be operated in
atechnicallyawlessandreliablecondition.Theoperatingcompany
is responsible for the trouble-free operation of the instrument. When
measuring aggressive or corrosive media that can cause a danger-
ous situation if the instrument malfunctions, the operating company
has to implement suitable measures to make sure the instrument is
functioning properly.
The safety instructions in this operating instructions manual, the
national installation standards as well as the valid safety regulations
and accident prevention rules must be observed.
For safety and warranty reasons, any invasive work on the device
beyond that described in the operating instructions manual may be
carried out only by personnel authorised by us. Arbitrary conversions
ormodicationsareexplicitlyforbidden.Forsafetyreasons,onlythe
accessoryspeciedbyusmustbeused.
To avoid any danger, the safety approval markings and safety tips on
the device must also be observed.
1.5 Conformity
The device complies with the legal requirements of the applicable
country-specicdirectivesortechnicalregulations.Weconrmcon-
formity with the corresponding labelling.

4
1 For your safety
VEGASON 61 • Two-wire 4 … 20 mA/HART
51852-EN-231026
The corresponding conformity declarations can be found on our
homepage.
1.6 NAMUR recommendations
NAMUR is the automation technology user association in the process
industry in Germany. The published NAMUR recommendations are
acceptedasthestandardineldinstrumentation.
ThedevicefullstherequirementsofthefollowingNAMURrecom-
mendations:
• NE 21 – Electromagnetic compatibility of equipment
• NE 43 – Signal level for fault information from measuring transduc-
ers
• NE53–Compatibilityofelddevicesanddisplay/adjustment
components
For further information see www.namur.de.
1.7 Environmental instructions
Protection of the environment is one of our most important duties.
That is why we have introduced an environment management system
with the goal of continuously improving company environmental pro-
tection.Theenvironmentmanagementsystemiscertiedaccording
to DIN EN ISO 14001.
Pleasehelpusfullthisobligationbyobservingtheenvironmental
instructions in this manual:
• Chapter "Packaging, transport and storage"
• Chapter "Disposal"

5
2 Product description
VEGASON 61 • Two-wire 4 … 20 mA/HART
51852-EN-231026
2 Product description
2.1 Conguration
Thetypelabelcontainsthemostimportantdataforidenticationand
use of the instrument:
• Instrument type
• Information about approvals
• Congurationinformation
• Technical data
• Serial number of the instrument
• QRcodefordeviceidentication
• Numerical code for Bluetooth access (optional)
• Manufacturer information
Tondorderdata,documentsorsoftwarerelatedtoyourdevice,you
have the following options:
• Move to "www.vega.com"andenterinthesearcheldtheserial
number of your instrument.
• Scan the QR code on the type label.
• Open the VEGA Tools app and enter the serial number under
"Documentation".
Type label
Documents and software

6
3 Mounting
VEGASON 61 • Two-wire 4 … 20 mA/HART
51852-EN-231026
3 Mounting
3.1 Mounting instructions
The reference plane for the measuring range is the lower edge of the
transducer.
Make sure that a minimum distance from the reference plane - the
so-called dead zone, in which measurement is not possible - is
maintained.Theexactvalueofthedeadzoneisstatedinchapter
"Technical data".
1
2
Fig. 1: Minimum distance to the max. level
1 blocking distance
2 Reference plane
Mount the sensor at least 200 mm (7.874 in) away from the vessel
wall.
1
2
> 200 mm
Fig. 2: Mounting on round vessel tops
1 Reference plane
2 Vessel center or symmetry axis
Reference plane for
measuring range
Mounting

7
4 Connecting to power supply
VEGASON 61 • Two-wire 4 … 20 mA/HART
51852-EN-231026
4 Connecting to power supply
4.1 Connection procedure
Proceed as follows:
1. Unscrew the housing lid
2. If a display and adjustment module is installed, remove it by turn-
ing it to the left
3. Loosen compression nut of the cable gland and remove blind
plug
4. Removeapprox.10cm(4in)ofthecablemantle,stripapprox.
1 cm (0.4 in) of insulation from the ends of the individual wires
5. Insert the cable into the sensor through the cable entry
6. Lift the opening levers of the terminals with a screwdriver (see
following illustration)
7. Insert the wire ends into the open terminals according to the wir-
ing plan
Fig. 3: Connection steps 6 and 7
8. Press down the opening levers of the terminals, you will hear the
terminal spring closing
9. Check the hold of the wires in the terminals by lightly pulling on
them
10. Connect the shielding to the internal ground terminal, connect the
externalgroundterminaltopotentialequalisation
11. Tighten the compression nut of the cable entry gland. The seal
ring must completely encircle the cable
12. Screw the housing lid back on
Theelectricalconnectionisnished.

8
4 Connecting to power supply
VEGASON 61 • Two-wire 4 … 20 mA/HART
51852-EN-231026
4.2 Wiring plan, single chamber housing
I2C
Display
1
12 5678
Fig. 4: Wiring plan - single chamber housing
1 Voltage supply, signal output
4.3 Wiring plan, double chamber housing
I2C
1
12
Fig. 5: Wiring plan - double chamber housing
1 Voltage supply, signal output
Wiring plan
Wiring plan

9
5 Set up with the display and adjustment module PLICSCOM
VEGASON 61 • Two-wire 4 … 20 mA/HART
51852-EN-231026
5 Set up with the display and adjustment
module PLICSCOM
5.1 Insert display and adjustment module
The display and adjustment module can be inserted into the sensor
and removed again at any time. It is not necessary to interrupt the
voltage supply.
Proceed as follows:
1. Unscrew the housing lid
2. Place the display and adjustment module in the desired position
ontheelectronics(fourpositionsin90°osetcanbeselected)
and turn to the right until it clicks into place.
3. Screw housing lid with inspection window tightly back on
Disassembly is carried out in reverse order.
The display and adjustment module is powered by the sensor, an ad-
ditional connection is not necessary.
Fig. 6: Insert display and adjustment module in the single chamber housing
Note:
Ifyouintendtoretrottheinstrumentwithadisplayandadjustment
module for continuous measured value indication, a higher lid with an
inspection glass is required.
5.2 Setup steps
1. Go to the menu "Basic adjustment" via the display and adjust-
ment module.
Mount/dismount display
and adjustment module
Set parameters

10
5 Set up with the display and adjustment module PLICSCOM
VEGASON 61 • Two-wire 4 … 20 mA/HART
51852-EN-231026
Basic adjustment
Display
Diagnostics
Service
Info
2. Carry out the adjustment in the menu items "Min. adjustment" and
"Max. adjustment".
Max.adjustment
100.00 %
=
1.000 m(d)
2.000 m(d)
Min. adjustment
0.00 %
=
5.000 m(d)
4.000 m(d)
3. Select in the menu item "Medium" the medium of your applica-
tion,forexample"Aqueous solution".
Medium
Liquid
4. Select in the menu item "Application" the vessel, the application
andthevesselform,forexample,"Storage tank".
Vessel shape
Storage tank
The sensor measures the distance from the sensor to the medium
surface. For indication of the real level, an allocation of the measured
distance to the percentage height must be carried out.
The actual level is then calculated on the basis of these entered
values. At the same time, the operating range of the sensor is limited
frommaximumrangetotherequestedrange.
Parameter adjustment
Otros manuales para VEGASON 61
10
Tabla de contenidos
Otros manuales de Sensor de seguridad de Vega

Vega
Vega EL 8 Manual de usuario

Vega
Vega VEGAFLEX 81 Manual de usuario

Vega
Vega VEGAPULS C 11 Manual de usuario

Vega
Vega VEGAPULS C 23 Manual de usuario

Vega
Vega VEGAPULS C 21 Manual de usuario

Vega
Vega DSGH Manual de usuario

Vega
Vega VEGASON 61 Manual de usuario

Vega
Vega VEGAFLEX 81 Manual de usuario

Vega
Vega VEGASON 62 Manual de usuario

Vega
Vega VEGAFLEX 81 Manual de usuario






















