FIRE FIGHTER'S GUIDE - FFCIF TYPE 3
1. VIEW NEXT ALARM
Press "NEXT" key once -
- The LCD will display the next alarm.
2. ACKNOWLEDGE DISPLAYED ALARM
Press "ACK" key once.
- LCD will display "ACKD" for the displayed alarm.
- The flashing alarm LED for the zone will go steady.
- If all alarms are acknowledged, the ALARM LED will go steady.
3. RESET ALL ACKNOWLEDGED ALARMS
Press "RESET" key once.
- LCD will display "Resetting acknowledged alarms".
- Alarm LEDs for acknowledged alarms will turn off.
- If all alarms are reset, the LCD will display
"No more events in alarm list", otherwise the oldest unacknowledged
alarm will be displayed.
4. ISOLATE ALL ACKNOWLEDGED ALARMS
Press "ISOLATE" key once.
- LCD will display "Isolating acknowledged alarms".
- Isolate LEDs for acknowledged alarms will turn on.
- If all alarms are isolated, the LCD will display "No more events in
alarm list", otherwise the oldest unacknowledged alarm will be
displayed.
5. ISOLATE/DE-ISOLATE BELLS
Press "BELLS ISO" key once.
- If the "Bells Isolate" LED is OFF
- The "Bells Isolate" LED will turn ON steady.
- The bells will turn OFF if they are ON.
- If the "Bells Isolate" LED is ON
- The "Bells Isolate" LED will turn OFF.
- If any un-isolated alarms exist, the bells will ring.
6. BRIGADE TEST
Press and hold the "BRIG TEST" key for at least 2 seconds. If enabled:
- The FIP will signal Alarm to the brigade.
-Any ancillary functions controlled by MAF ALARM will turn ON, unless
they are isolated.

THIS PAGE INTENTIONALLY LEFT BLANK

F4000
LCD OPERATOR'S MANUAL
F4000 PRODUCT MANUAL
VOLUME 7
Document Number: LT0117
Issue 2.38; 19 April 2002
- APPROVALS -
AUSTRALIAN STANDARDS AS1603.4 1987 (Incl. Amdt 1 & 2):
- SSL Certificate of Compliance Number 131
- SSL Register of Accredited Products Number 398 (Fire Protection Equipment)
AUSTRALIAN STANDARDS AS4050(INT) 1992
NEW ZEALAND STANDARDS NZS4512-1981 (INCL AMDT 1 & 2)
AS/NZS 3548 1995 CLASS A
The F4000 Fire Indicator Panel is manufactured for:
Tyco Services Fire & Safety
25 Cleeland Road
Oakleigh South
VIC 3167
AUSTRALIA
Tel : +61-3-9543 2220
Fax : +61-3-9543 2155
COPYRIGHT (C) 1995, 1996, 1997, 1998, 2000, 2001, 2002
Information contained in this document is subject to copyright, and shall not be reproduced in any
form whatsoever, without the written consent of Tyco Services Fire & Safety.
Information contained in this document is believed to be accurate and reliable, however Tyco
Services Fire & Safety reserves the right to change the content without prior notice.

F4000 LCD Operator's Manual Document No: LT0117
Page ii 19 April 2002 Issue 2.38
INSTALLATION DETAILS
For your reference please complete the following information on the F4000 LCD Fire
Indicator Panel supplied.
F4000 FIP SUPPLIED BY
F4000 FIP INSTALLATION LOCATION
CONTRACT/JOB NUMBER
F4000 SERIAL NUMBER
F4000 SYSTEM AS INSTALLED
DRAWING NUMBER Issue:
F4000 SYSTEM PARAMETERS
DRAWING NUMBER Issue:
Date Panel Manufactured
Date Panel Installed
Date Panel Commissioned
Maintenance Company
Telephone B.H. A.H.
Service Contact
Site Contact or Registered User
(include title)
Company / Address
Telephone B.H.
EMC COMPLIANCE
WARNING: This product is a Class A product. In a domestic environment this product
may cause radio interference in which case the user may be required to take
adequate measures.

Document No: LT0117 F4000 LCD Operator's Manual
Issue 2.38 19 April 2002 Page iii
TABLE OF CONTENTS
Installation Details………………………………………………………………………………. ii
End User Liability Disclaimer……………………………………………………… v
Amendments…………………………………………………………………………………….. vi
1 INTRODUCTION .......................................................................................... 1-1
1.1 SCOPE.................................................................................................................. 1-2
1.2 ATTACHMENTS ................................................................................................... 1-3
1.3 ASSOCIATED DOCUMENTATION ...................................................................... 1-4
1.4 GLOSSARY OF TERMINOLOGY......................................................................... 1-6
2 SYSTEM DESCRIPTION ............................................................................. 2-1
2.1 SYSTEM COMPONENTS..................................................................................... 2-2
2.2 LCD FIP DISPLAYS............................................................................................ 2-10
2.3 LCD KEYPAD INTRODUCTION......................................................................... 2-12
2.4 AUDIBLE TONES ............................................................................................... 2-18
2.5 NETWORKED PANELS...................................................................................... 2-19
3 SYSTEM SPECIFICATIONS........................................................................ 3-1
3.1 SYSTEM CAPACITY ............................................................................................ 3-2
3.2 PHYSICAL ............................................................................................................ 3-3
3.3 ELECTRICAL ........................................................................................................ 3-6
3.4 INDICATORS ........................................................................................................ 3-7
3.5 KEYPAD CONTROLS........................................................................................... 3-8
4 INTERPRETING THE DISPLAY .................................................................. 4-1
4.1 RESPONDING TO ALARMS ................................................................................ 4-2
4.2 DEALING WITH FAULTS ..................................................................................... 4-3
4.3 SYSTEM INDICATORS ........................................................................................ 4-4
4.4 ZONE INDICATORS ............................................................................................. 4-8
4.5 LED PHASING ...................................................................................................... 4-9

F4000 LCD Operator's Manual Document No: LT0117
Page iv 19 April 2002 Issue 2.38
4.6 CONTROL OF FIP BY MULTIPLE OPERATORS .............................................. 4-10
5 OPERATING INSTRUCTIONS - BRIGADE FUNCTIONS ........................... 5-1
5.1 INTRODUCTION TO BRIGADE FUNCTIONS...................................................... 5-2
5.2 SILENCING THE INTERNAL SOUNDER............................................................. 5-4
5.3 ACKNOWLEDGE ZONES IN ALARM .................................................................. 5-5
5.4 RESET ACKNOWLEDGED ZONES IN ALARM................................................... 5-6
5.5 ISOLATE ACKNOWLEDGED ZONES IN ALARM................................................ 5-7
5.6 ISOLATING/DE-ISOLATING BELLS .................................................................... 5-8
5.7 DISPLAYING THE ALARM CAUSE...................................................................... 5-9
5.8 EXITING FFCIF MODE....................................................................................... 5-10
5.9 RECALLING THE ALARM LIST.......................................................................... 5-11
5.10 BRIGADE TEST................................................................................................. 5-12
6 OPERATING INSTRUCTIONS - SYSTEM FUNCTIONS............................. 6-1
6.1 BATTERY TEST ................................................................................................... 6-2
6.2 BELL TEST ........................................................................................................... 6-4
6.3 BELL ISOLATE OR DE-ISOLATE ........................................................................ 6-5
6.4 LCD/LAMP (LED) TEST........................................................................................ 6-6
6.5 SYSTEM TEST ..................................................................................................... 6-7
6.6 RECALL SYSTEM FAULTS................................................................................ 6-10
6.7 SYSTEM FAULT RESET .................................................................................... 6-14
6.8 RECALL HISTORY ............................................................................................. 6-15
6.9 SET SYSTEM TIME............................................................................................ 6-17
6.10 SET SYSTEM DATE .......................................................................................... 6-18
6.11 SET LCD ACCESS PASSWORD ...................................................................... 6-19
6.12 GLOBAL RESET................................................................................................ 6-20
6.13 GLOBAL ISOLATE............................................................................................. 6-21
6.14 RECALL SYSTEM CRCS .................................................................................. 6-22

Document No: LT0117 F4000 LCD Operator's Manual
Issue 2.38 19 April 2002 Page v
7 OPERATING INSTRUCTIONS - ZONE FUNCTIONS.................................. 7-1
7.1 ZONE ALARM OR FAULT TEST.......................................................................... 7-2
7.2 ZONE OR ANCILLARY ISOLATE OR DE-ISOLATE ............................................ 7-6
7.3 ANCILLARY TEST .............................................................................................. 7-11
7.4 ZONE OR ANCILLARY RESET.......................................................................... 7-13
7.5 AUTO-RESET MODE ......................................................................................... 7-15
7.6 ZONE STATUS RECALLS.................................................................................. 7-18
8 OPERATING INSTRUCTIONS - POINT FUNCTIONS................................. 8-1
8.1 ANALOGUE RECALLS......................................................................................... 8-2
8.2 ANALOGUE DETECTOR HISTORY, TRACKING, DEVICE RESET.................. 8-10
8.3 SETTING DETECTOR SENSITIVITIES.............................................................. 8-11
8.4 POINT ISOLATION ............................................................................................. 8-16
9 PLACING INTO OPERATION...................................................................... 9-1
9.1 GENERAL ............................................................................................................. 9-2
9.2 MAINS ISOLATE SWITCH ................................................................................... 9-3
9.3 POWER UP........................................................................................................... 9-3
9.4 COMMISSIONING CHECKLIST ........................................................................... 9-4
10 SYSTEM MAINTENANCE & TROUBLE SHOOTING.................................10-1
10.1 SYSTEM MAINTENANCE ................................................................................. 10-2
10.2 TROUBLE-SHOOTING...................................................................................... 10-5
APPENDIX A …………………………………………………………………………. A-1
APPENDIX B …………………………………………………………………………. B-1
APPENDIX C …………………………………………………………………………. C-1

F4000 LCD Operator's Manual Document No: LT0117
Page vi 19 April 2002 Issue 2.38
TYCO SERVICES FIRE & SAFETY
END USER LIABILITY DISCLAIMER
The F4000 Fire Indicator Panel provides a configuration programming facility, which may be
accessed via a programming terminal using a password.
Because this programming facility allows the user to define in detail the operation of the
F4000 System which is being customised, changes may be made by the user that prevent
this installation from meeting statutory requirements.
TYCO SERVICES FIRE & SAFETY therefore cannot accept any responsibility as to the
suitability of the functions generated by the user using this programming facility.

Document No: LT0117 F4000 LCD Operator's Manual
Issue 2.38 19 April 2002 Page vii
AMENDMENTS
ISSUE DATE COMMENTS ECN
1 10/09/93 Original for Software Version 2.0
1.1 03/11/93 Minor Text Changes/Updates
2.2 15/12/95 Updated for Software Version V2.2X and V2.2XN.
Includes:
Support for "130 Series" Devices.
New Analogue Sensitivity Adjustment.
New Fault Present and Database.
Change/CRC Display.
2.22 25/07/96 Updated for V2.22/2.22N software, updated pages i, vi, 4-3,
4-7, 5-8, 6-5, 6-11, 6-12.
2468
2.23 24/10/96 Updated for V2.23/V2.23N, pages i, iv, vi, 4-5, 6-11, 6-12
and Chapter 8.
2510
2.23A 10/04/97 Bell Test Key Sequence corrected (was Sys Test 2). 2602
2.30 14/10/97 Updated for V2.30/V2.30N
Sections 0, 1, 2.1.7, 2.1.9, 2.1.11, 2.3.1, 2.3.5, 2.4, 3.1,
3.2.6, 5.1.2, 5.7.2, 6.6.3, 6.9.3, 7.6.2, 7.6.3, 8.3.1, 8.3.4,
8.4.2, Appendix A, Table III base information, pg A-5 6)
2621
2.31 27/04/98 Updated for V2.31/V2.31N.
Sections 2.4, 3.3, 4.3.5, 6.1.3, 6.4, 6.6.3, 9.3
2.35 01/02/00 Updated for V2.35/V2.35N, converted to Word 97, Sections
1.1, 1.3, 1.4, 2.3.1, 2.3.8, 4.6, 5.1.2, 5.2.1, 5.6.1, 5.7.2,
5.9.2, 6.6.3, 6.4, 6.9, 8.1.2, 8.1.3, 8.1.4, 8.1.5, 8.2.3.
Added 8.1.6. Updated Fire Fighter’s Type 3 Guide.
2983
2.35A 02/05/00 Revised to include networking features from LT0150. 3074
2.37 19/04/01 Brand changed to Tyco. Revised Section 5.2.1 and added
P133A, Z134A details to Appendix A.
3169
2.38 19/04/02 Revised for V2.38 for Dirty Alert, Charger Ignore time after
NZ 1 hour battery test, and Charger LED cadence.
3288

F4000 LCD Operator's Manual Document No: LT0117
Page viii 19 April 2002 Issue 2.38
THIS PAGE IS INTENTIONALLY LEFT BLANK