Product part no. 830030 AdvantageLi Dual Zone Fire Control Panel
Manual part no 650.000050 4 August 20 2020
. AdvantageLi Control Panel Compliance Notice
The AdvantageLi Control Panel is designed per NFPA 17, NFPA 70, NFPA 7 and NFPA
010 standards for installation, operation, and maintenance.
Product Type: Releasing Device
Power Limited Circuits: All circuits are power limited
Supervised Circuits: Initiating (Detection), Actuation, Auxiliary, Abort
Battery Information: This control unit is designed using qty ( ) lithium thionyl chloride
batteries as both the primary and secondary power source. Use only FireAway
Advantage-Lithium Battery part no. 830031 as replacement.
Battery Disposal: Do not incinerate, or subject cells to temperatures in excess of 100oC.
Such abuse can result in loss of seal, leakage, and/or cell explosion. Dispose of in
accordance with appropriate local regulations.
SDS Sheet available by contacting http://tfsinc.com
Emergency Contact:
Chemtrec 1-800-4 4-9300
1-703-5 7-3887
Transportation of Lithium batteries and devices that contain lithium batteries is
closely regulated. Regulations change periodically. Be sure to refer to
International Air Transport Association (IATA) requirements (http://iata.org).
The battery included with the AdvantageLi control panel is a non-rechargeable,
lithium metal battery. When shipped separate from the AdvantageLi control panel
its outer packaging should be labeled to include reference to UN3090 Lithium
Metal Batteries listed as Hazard Class 8.
When the battery is shipped as included with the AdvantageLi control panel, the
outer packaging should be labeled to include reference to UN3091 – Lithium
Metal Batteries Contained in Equipment or Lithium Metal Batteries Packed with
Equipment listed as Hazard Class 9.
The battery packs are DOT tested for construction compliance and rated as
35413 4BAT-001 per UN Manual of Test and Criteria, Part III, sub-section 38.3.