© Telect, Inc. All rights reserved. 3.6.17 v.2
1.509.926.6000 :: telect.com
Low-Current 20/20 GMT Series Fuse Panels
Power :: Models 06004-01 & 06004-11 Installation Guide
6
2. Select the proper pair of brackets and discard the other two.
3. Mount the brackets to sides of the panel, as shown in the following examples. Tighten screws
to about 29 in.-lb (~3.3 N•m).
The panel can be mounted so that the panel’s face is ush or extended in 0.5-in. (12.7 mm) increments
from the rack. (The clover-leaf pattern on the face of the bracket points downward on the right side of the
panel and upward on the left.)
Telect, Inc. • USA +1.509.926.6000 • Mexico +52.33.3836.37.52
www.telect.com • © 2010 Telect, Inc., All Rights Reserved, 130358-2 A0.1
Page 6
2. Select the proper pair of brackets and discard the other two.
3. Mount the brackets to sides of the panel, as shown in the following examples. Tighten screws
to about 29 in.-lb (~3.3 N•m).
The panel can be mounted so that the panel’s face is flush or extended in 0.5-in. (12.7 mm)
increments from the rack. (The clover-leaf pattern on the face of the bracket points downward
on the right side of the panel and upward on the left.)
4. Locate an unused rack position and mount the panel
using the four, 12-24 thread-cutting screws and lock-
washers provided, as shown on the right.
5. Tighten the screws to 35 in.-lb (4.29 N•m).
6. Before connecting any conductor, use a multimeter to
measure the resistance between the input terminal of
each side (+A and -A for Side A; +B and -B for Side
B) at the rear corner of the panel. Expect 500Ωor
more for both Side A and Side B.
WARNING! Failure to properly ground this equipment can create hazardous conditions to
installation personnel and to the equipment.
ALERT! Only use components and crimping tools approved by agencies or certifying
bodies recognized in your country or region such as Underwriter’s Laboratories (UL),
TUV, etc.
7. For ground wiring, use a listed (approved) crimping tool to attach a listed (approved), single-
hole compression lug suitable for a #10 (~5 mm) screw onto a suitable ground wire.
Bracket for a
19-in. Rack
Bracket for a
23-in. Rack
(Flush Mount) (Flush Mount)
Bracket for a
19-in. Rack
(Extended 2 in.)
Clover-Leaf Pattern Points Downward
on Right Side of Panel.
Figure 6 - Bracket Installation (Examples)
Figure 7 - Mounting the Panel
Telect, Inc. • USA +1.509.926.6000 • Mexico +52.33.3836.37.52
www.telect.com • © 2010 Telect, Inc., All Rights Reserved, 130358-2 A0.1
Page 6
2. Select the proper pair of brackets and discard the other two.
3. Mount the brackets to sides of the panel, as shown in the following examples. Tighten screws
to about 29 in.-lb (~3.3 N•m).
The panel can be mounted so that the panel’s face is flush or extended in 0.5-in. (12.7 mm)
increments from the rack. (The clover-leaf pattern on the face of the bracket points downward
on the right side of the panel and upward on the left.)
4. Locate an unused rack position and mount the panel
using the four, 12-24 thread-cutting screws and lock-
washers provided, as shown on the right.
5. Tighten the screws to 35 in.-lb (4.29 N•m).
6. Before connecting any conductor, use a multimeter to
measure the resistance between the input terminal of
each side (+A and -A for Side A; +B and -B for Side
B) at the rear corner of the panel. Expect 500Ωor
more for both Side A and Side B.
WARNING! Failure to properly ground this equipment can create hazardous conditions to
installation personnel and to the equipment.
ALERT! Only use components and crimping tools approved by agencies or certifying
bodies recognized in your country or region such as Underwriter’s Laboratories (UL),
TUV, etc.
7. For ground wiring, use a listed (approved) crimping tool to attach a listed (approved), single-
hole compression lug suitable for a #10 (~5 mm) screw onto a suitable ground wire.
Bracket for a
19-in. Rack
Bracket for a
23-in. Rack
(Flush Mount) (Flush Mount)
Bracket for a
19-in. Rack
(Extended 2 in.)
Clover-Leaf Pattern Points Downward
on Right Side of Panel.
Figure 6 - Bracket Installation (Examples)
Figure 7 - Mounting the Panel
Figure 6 - Bracket Installation (Examples)
4. Locate an unused rack position and mount the panel
using the four, 12-24 thread-cutting screws and
lock washers provided, as shown on the right.
5. Tighten the screws to 35 in.-lb (4.29 N•m).
6. Before connecting any conductor, use a multimeter to
measure the resistance between the input terminal of
each side (+A and -A for Side A; +B and -B for Side B)
at the rear corner of the panel. Expect 500Ω or more for
both Side A and Side B.
Telect, Inc. • USA +1.509.926.6000 • Mexico +52.33.3836.37.52
www.telect.com • © 2010 Telect, Inc., All Rights Reserved, 130358-2 A0.1
Page 6
2. Select the proper pair of brackets and discard the other two.
3. Mount the brackets to sides of the panel, as shown in the following examples. Tighten screws
to about 29 in.-lb (~3.3 N•m).
The panel can be mounted so that the panel’s face is flush or extended in 0.5-in. (12.7 mm)
increments from the rack. (The clover-leaf pattern on the face of the bracket points downward
on the right side of the panel and upward on the left.)
4. Locate an unused rack position and mount the panel
using the four, 12-24 thread-cutting screws and lock-
washers provided, as shown on the right.
5. Tighten the screws to 35 in.-lb (4.29 N•m).
6. Before connecting any conductor, use a multimeter to
measure the resistance between the input terminal of
each side (+A and -A for Side A; +B and -B for Side
B) at the rear corner of the panel. Expect 500Ωor
more for both Side A and Side B.
WARNING! Failure to properly ground this equipment can create hazardous conditions to
installation personnel and to the equipment.
ALERT! Only use components and crimping tools approved by agencies or certifying
bodies recognized in your country or region such as Underwriter’s Laboratories (UL),
TUV, etc.
7. For ground wiring, use a listed (approved) crimping tool to attach a listed (approved), single-
hole compression lug suitable for a #10 (~5 mm) screw onto a suitable ground wire.
Bracket for a
19-in. Rack
Bracket for a
23-in. Rack
(Flush Mount) (Flush Mount)
Bracket for a
19-in. Rack
(Extended 2 in.)
Clover-Leaf Pattern Points Downward
on Right Side of Panel.
Figure 6 - Bracket Installation (Examples)
Figure 7 - Mounting the Panel
Figure 7 - Mounting the Panel
WARNING
WARNING! Failure to properly ground this equipment can create hazardous conditions to installation
personnel and to the equipment.
ALERT
ALERT! Only use components and crimping tools approved by agencies or certifying bodies
recognized in your country or region such as Underwriter’s Laboratories (UL), TUV, etc.
7. For ground wiring, use a listed (approved) crimping tool to attach a listed (approved), single-hole compression lug
suitable for a #10 (~5 mm) screw onto a suitable ground wire.
Ground wire should be same gauge as the input wiring. Input wiring size depends solely on input interruption device
at the primary power distribution unit.