teca TLC-700 Manual de usuario

ProductInformationPacket
ModelTLC-700HC
Heat/CoolSolidStateLiquidChiller
withIntegralTC-4300TemperatureControl
Part#6-A0E0-1-0B0
Thankyouforyourpurchase.Informationhasbeenenclosedregardingthe
installation,specifications,andwiringofyoursolidstateassembly.
Pleasereadandfollowallinstructionscarefullybeforeinstallation.Only
qualifiedtechniciansshouldinstallthisequipment.
Ifyouhaveanyquestionswithyourequipment,pleasedonothesitatetocall
ustollfreeat(888)TECA-USA(832-2872),wewillbehappytoassist.We
areopenfrom8:00amto4:30pmCentralTime.
Includedinthispacketyouwillfind:
GettingStarted
ProductLiteratureandSpecifications
WiringDrawing#SK100706
WarrantyInformation
PrintedEasyLogManual
TC-4300CD

Positionthistubingupwards
whilefillingthelines
Loadtobecooled
GETTINGSTARTED:
(Readentireinstructionsbeforeoperating)
Thisunitshouldoperatewiththebottomfeetrestingonaflatsurface.Theinternalheatexchangeriscooledby
atubeaxialfan.Itisnecessarytokeeptheinlet/outletairpathfreefromanyrestrictionsthatmayimpedeyourcooling
performance.A6"minimumspacingfromtherearoftheunittoanyobstructionisrequired.Externaltubingwithinsulationhas
beenprovidedforatotalof12'plumbingline.Trimthetubingandinsulationasnecessarytominimizetheambientthermal
load.4clampshavebeenprovidedtoattachthetubing(2tothequickconnectorsprovidedand2foryourload
connectors).Thetubinglinesarea3/8"innerdiameter.Connecttheexternalplumbinglinestothedevice(s)beingcooled.
Lowfluidandlowflowindicatorshavebeenprovidedonthefrontpanel.Itisnecessarytofilltheinternal
reservoirbeforeyouapplypower.Theinternalreservoirholds
approximately500mloffluid.The“addfluid”lightwillcomeonwhenthereservoirisapproximately½full.Thereisavisual
indicatorofthewaterlevelonthesideoftheunit.Distilledwateristherecommendedfluidfortemperaturesto5C.For
temperaturesbelow5C,a30%glycol70%distilledwatermixissuggested.Removethereservoircaplocatedatthetopleft
corneroftheunitandfillthereservoir.Keepthereservoircapoffuntiltheexternalplumbingisfilledandthereservoiris
toppedoff.
Connectthepowercordtoanappropriateoutlet.Thepowercordmustbeconnectedtoareceptacle
protectedbyacircuitprotectedperlocalandornationalcodes.Whileyouarefillingtheexternallines,positionthesupply
quickconnectupwards.(SeeFigureA)Thiswillassistinremovingairtrappedinthelines.Atthispoint,depressthe power
switchonthefrontpaneltoturnthesystemon.Fora12'plumbingline,itshouldtakeabout30secondsbeforethe“add
fluid”lightilluminates.Atthispoint,turnthepoweroffandaddadditionalfluid.Re-applypower.Another30secondsorso
shouldbeenoughtimetocompletelyfillthelines.Turnoffthepowerswitchandtopoffthereservoir.Reattachthereservoir
capsecurely.
PleaseNote:Itmaybenecessarytoaddfluidtothereservoirfromtimetotime.The“addfluid”indicatorwillilluminateifthe
reservoirrequiresarefill.Ifthe“lowflow”indicatorlightappears,checktosee ifthereareanyobstructionsorleakswithinthe
plumbinglines.
The“lowflow”indicatorappearswhentheflowisapproximately0.3liter/minorless.
Adigitaltemperaturecontrollerhasbeenprovided.Holdthe*buttonandadjusttoadjustthesetpoint.
Moredetailedtemperaturecontrolinformationhasbeenincludedwithyourproductinformationpacket.Wesuggest
changingthetemperaturecontrollersprogrammingtoaPIDcontrolmethodandthenperforminganautotuneforbetter
temperaturecontrol.
WehopeyouenjoyyournewAmeritemp™seriesliquidchiller.Ifyouhaveanyquestions,pleasedonothesitatetocallour
technicaldepartment@888-TECA-USA(888-832-2872).
STEP#1
STEP#2
STEP#3
STEP#4
FAILURETODOSOMAYRESULTINDAMAGETOTHEPUMP
E
E
?>

94 TECA 1-888-TECA-USA (832-2872) www.teca-usa.com
TLC-700 Air Cooled Liquid Chiller
Air Cooled 120 VDC, 240 VAC and 24 VDC Input
SPECIFICATIONS
PERFORMANCE VOLTAGE CURRENT WEIGHT MAX HEATING OPTION TEMP. FLUID AGENCY
MODEL PART NUMBER RATING VAC AMPS. LBS. (KG) OPERATING (HC SUFFIX) CONTROL TEMP APPROVALS
BTU/HR 50/60 HZ AMBIENT RANGE °C (ETL)
TLC-700 6-A0D0-0-000 730-800 120 VAC 4.2 32(14.5) 50 °C(+122 F) TC-3300 -5/65 UL3101-1/CSA22.2, CE
TLC-700HC 6-A0D0-1-000 730-800 120 VAC 4.2 32(14.5) 50 °C(+122 F) 200 Watt TC-3300 -5/65 UL3101-1/CSA22.2, CE
TLC-702 6-A0D2-0-000 730-800 240 VAC 2.9 42(19) 50 °C(+122 F) TC-3300 -5/65 UL3101-1/CSA22.2, CE
TLC-702HC 6-A0D2-1-000 730-800 240 VAC 2.9 42(19) 50 °C(+122 F) 200 Watt TC-3300 -5/65 UL3101-1/CSA22.2, CE
TLC-700 6-A0E0-0-0B0 730-800 120 VAC 4.2 32(14.5) 50 °C(+122 F) TC-4300 -5/65 PENDING
TLC-700HC 6-A0E0-1-0B0 730-800 120 VAC 4.2 32(14.5) 50 °C(+122 F) 200 Watt TC-4300 -5/65 PENDING
TLC-702 6-A0E2-0-0B0 730-800 240 VAC 2.9 42(19) 50 °C(+122 F) TC-4300 -5/65 PENDING
TLC-702HC 6-A0E2-1-0B0 730-800 240 VAC 2.9 42(19) 50 °C(+122 F) 200 Watt TC-4300 -5/65 PENDING
TLC-700 6-A0E5-0-0B0 730-800 24 VDC 10.0 32(14.5) 50 °C(+122 F) TC-4300 -5/65 PENDING
TLC-700HC 6-A0E5-1-0B0 730-800 24 VDC 10.0 32(14.5) 50 °C(+122 F) 200 Watt TC-4300 -5/65 PENDING
FEATURES
• Compact (only 15.5" X 7.6" bench top footprint)
• Easy prime pump design
• Integral PID "tunable" temperature control (two styles)
• No compressor, fluorocarbons or filters
• Remote Sensibility™ remote temperature sensing
• Un-cooled, 500mL reservoir
• Front to back air-flow system
• Stainless steel exterior housing
• Ergonomic sloping front design
• Low fluid level and low flow warning
• Integral power supply
• Self priming pump/reservoir
• Low pressure drop fluid quick connects
TC-4300 FEATURES
• Heating and Cooling
• Integral PID "tunable" temperature control
• One shot smart PID control tuning or Adaptive Smart
Continuous Tuning
• Multi-segment ramp and soak programs
• RS-232 communications standard, includes EzLog®software
for easy programming and control logging
• Process fluid "out of temperature range" warning
• Variable fan speed for quietest operation
• Easy prime/pump reset feature
• No flow system shut down
• Optional software iTools® and OPC Server
TC-3300 FEATURES
• Cool and Heat/Cool versions
• RS-232 communications (optional)
• Communications Software (optional)
TLC-700 with TC-4300
TLC-700 with TC-3300

95www.teca-eu.com 1-888-TECA-USA (832-2872) TECA
DIMENSIONS
PERFORMANCE CURVE
Equation of line: y=⌬T(°C) x=Capacity (Watts)
Ambient Temp 25°C 50°C
Fluid Supply y=.14x-30.2 y=.14x-33.2
ENVIRONMENTS
Bench top
Laboratory
Industrial
COOLING CAPACITY
215 Watts @ 0 °C ⌬T
TLC-700
Liquid Chiller - Air Cooled
Ambient Air Path
PUMP CURVE


LIMITEDWARRANTY
Intheeventadefectinmaterialorworkmanshipisdiscoveredinanyof
TECA’sproductswithinoneyearafterthedatetheyaredeliveredtoBuyer,
:(a)TECAisnotifiedofthedefectinwritingbycertifiedmailwithin14
daysofthedateofdiscovery;(b)TECAmaytheneither,atitssolediscretion,
inspecttheproductatBuyer’slocation,orrequirethattheproductbemade
availableatBuyer’sexpenseatTECA’spremisesforTECA’sinspection
within14daysofthedateofnotification;and(c)theproductsaredefective
andthedefectsresultfromfaultymaterialsand/orworkmanshipandnotin
anywayfromaccident,misuse,misapplication,mishandling,modification,or
alterationbytheBuyerortheshipper,TECAshall,atitssoleoption,
repairorexchangedefectiveproductsfreeofchargetoBuyer,orcreditto
buyerthepriceofthedefectiveproducts.ALLOTHERWARRANTIES,
EXPRESSORIMPLIED,AREEXCLUDED,INCLUDINGBUTNOTLIMITED
TOTHEIMPLIEDWARRANTIESOFMERCHANTABILITYANDFITNESS
FORAPARTICULARPURPOSE.INNOEVENTSHALLTECABELIABLE
FORANYCLAIMBASEDUPONBREACHOFEXPRESSORIMPLIED
WARRANTYORANYOTHERDAMAGESWHETHERSPECIAL,INDIRECT,
INCIDENTAL,CONSEQUENTIAL,LOSTPROFITS,BUSINESS
INTERRUPTION,ORLOSSOFBUSINESSORCUSTOMER
RELATIONSHIPS.
Inordertoreturnmerchandiseforanyreason(repair,replacement,orcredit)
areturnauthorizationnumbermustbeissuedbyTECA.Newmerchandise
maynotbereturnedforcreditbeyond60daysfromshipment.Chargesfor
incidentalorotherdamagesmayalsobemade.Allreturnedgoodsmustbe
sentfreightprepaid.Arestockingchargeof15%willapply.Onspecial
equipmentandcustommodifiedequipmentorders,additionalincremental
cancellationchargesmaybemade.
andif
then
RETURNEDGOODS,RESTOCKINGCHARGES
Otros manuales para TLC-700
1
Este manual sirve para los siguientes modelos
13
Tabla de contenidos
Otros manuales de Enfriador de teca