THERMORACK 800 THERMOELECTRIC CHILLER 52-13007-1
SOLID STATE COOLING SYSTEMS,167 MYERS CORNERS ROAD,WAPPINGERS FALLS,NY 12590 6
TELEPHONE:(845) 296-1300 FAX:(845) 296-1303 WEB:WWW.SSCOOLING.COM VERSION M8
SECTION 2
SPECIFICATIONS _________________________________________________
Operating Range (Set Point): 5°C to 50°C standard
Ambient Temperature Range: 10°C to 40°C non-condensing
Stability / Repeatability: ±0.05°C with constant load (even near ambient)
Cooling Capacity (typical1): 700 Watts @ 20°C in 20°C ambient air with 100 to 240 VAC 1Phase
800 Watts @ 20°C in 20°C ambient air with 200 to 240 VAC 1Phase
900 Watts @ 20°C in 20°C ambient air with 200 to 240 VAC 1Phase
+ high speed fan
Noise Level (at 1 meter)2: <63 dBA (50% load), <75 dBA (with full load)
Coolant / Process Fluid: Koolance (27% propylene glycol / water mix)
or 27-50% ethylene glycol / water mix
(contact SSCS for advice on other fluids)
Note: Do not use water alone in copper systems with centrifugal
pumps as water absorbs CO2from the air, causing its pH to become
acidic. Acidic water dissolves copper which then plates out inside
the magnetic drive of the centrifugal pump, causing the pump to
seize after a few months of operation.
Process Fluid Fittings: 3/8” NPT female. Brass for units with copper wetted parts and stainless
steel for units with aluminum wetted parts.
Pumps: 3.5 lpm (0.9 gpm) @ 30 psig smooth flow centrifugal
Tank Volume: 0.8 liter with level sensor
Wetted Materials: Aluminum, stainless steel and polymers,
or Copper, stainless steel, brass and polymers (option)
Dimensions (W x D x H): 19” x 20” x 11” 6U (48cm x 51 cm x 27 cm)
Weight: 55 lbs (25.5 kg)
Power Input: 200-240 VAC 1 phase, 50/60 Hz, 8 amps max
100-240 VAC, 50/60 Hz, 16-8 amps max (700W model only)
Controls: Digital PID controller for heating and cooling
Communications: Keypad or USB interface
Alarms Temperature, fluid level, system or component failure (display and USB)
Standards TUV listed to UL, CAN/CSA and EN 61010-1,
CE 61010-1, RoHS compliant
Warranty 2 years
Notes:
1) Cooling capacity will vary with configuration.
2) Typical configuration.