SMA MULTICLUSTER-BOX 6 Manual de usuario

MC-BOX-6-3-BE-en-30 | Version 3.0ENGLISH
Operating manual
MULTICLUSTER-BOX 6

Legal Provisions SMA Solar Technology AG
Operating manualMC-BOX-6-3-BE-en-302
Legal Provisions
The information contained in these documents is the property of SMA Solar Technology AG. No
part of this document may be reproduced, stored in a retrieval system, or transmitted, in any form or
by any means, be it electronic, mechanical, photographic, magnetic or otherwise, without the prior
written permission of SMA Solar Technology AG. Internal reproduction used solely for the purpose
of product evaluation or other proper use is allowed and does not require prior approval.
SMA Solar Technology AG makes no representations or warranties, express or implied, with
respect to this documentation or any of the equipment and/or software it may describe, including
(with no limitation) any implied warranties of utility, merchantability, or fitness for any particular
purpose. All such representations or warranties are expressly disclaimed. Neither SMA Solar
Technology AG nor its distributors or dealers shall be liable for any indirect, incidental, or
consequential damages under any circumstances.
The exclusion of implied warranties may not apply in all cases under some statutes, and thus the
above exclusion may not apply.
Specifications are subject to change without notice. Every attempt has been made to make this
document complete, accurate and up-to-date. Readers are cautioned, however, that product
improvements and field usage experience may cause SMA Solar Technology AG to make changes
to these specifications without advance notice or per contract provisions. SMA Solar Technology
AG shall not be responsible for any damages, including indirect, incidental or consequential
damages, caused by reliance on the material presented, including, but not limited to, omissions,
typographical errors, arithmetical errors or listing errors in the content material.
SMA Warranty
You can download the current warranty conditions from the Internet at www.SMA-Solar.com.
Trademarks
All trademarks are recognized, even if not explicitly identified as such. Missing designations do not
mean that a product or brand is not a registered trademark.
SMA Solar Technology AG
Sonnenallee 1
34266 Niestetal
Germany
Tel. +49 561 9522-0
Fax +49 561 9522-100
www.SMA.de
Email: [email protected]
As of: 2/23/2021
Copyright © 2021 SMA Solar Technology AG. All rights reserved.

Table of Contents
SMA Solar Technology AG
Operating manual MC-BOX-6-3-BE-en-30 3
Table of Contents
1 Information on this Document................................................. 5
1.1 Validity........................................................................................................................ 5
1.2 Target Group.............................................................................................................. 5
1.3 Levels of Warning Messages.................................................................................... 5
1.4 Symbols in the Document .......................................................................................... 5
1.5 Typographical Elements in the Document ................................................................ 6
1.6 Designations in the Document................................................................................... 6
1.7 Additional Information............................................................................................... 6
2 Safety ........................................................................................ 7
2.1 Intended Use .............................................................................................................. 7
2.2 IMPORTANT SAFETY INSTRUCTIONS.................................................................... 7
3 Scope of Delivery ..................................................................... 9
4 Product Overview .................................................................... 10
4.1 Product Description.................................................................................................... 10
4.2 Symbols on the Product ............................................................................................. 11
4.3 System Structure......................................................................................................... 12
5 Mounting................................................................................... 13
5.1 Requirements for Mounting ....................................................................................... 13
5.2 Mounting the product ................................................................................................ 15
6 Electrical Connection ................................................................ 16
6.1 Overview of the Connection Area ............................................................................ 16
6.1.1 Interior View............................................................................................ 16
6.1.2 View from Below..................................................................................... 17
6.2 Connecting the Generator......................................................................................... 17
6.3 Connecting the Loads ................................................................................................ 18
6.4 Connecting the PV System......................................................................................... 19
6.5 Connecting the Sunny Island..................................................................................... 19
6.6 Grounding the Multicluster System........................................................................... 20
6.7 Connecting the Data Cable....................................................................................... 21
7 Preparing for Commissioning ................................................. 22
8 Disconnect from voltage sources ............................................ 23
9 Periodic Actions ........................................................................ 24

Table of Contents SMA Solar Technology AG
Operating manualMC-BOX-6-3-BE-en-304
9.1 Inserting Power Cables.............................................................................................. 24
9.2 Inserting Data Cables ................................................................................................ 25
10 General Maintenance Work ................................................... 27
11 Decommissioning the Product ................................................. 29
12 Technical Data .......................................................................... 30
13 Multicluster Technology Terms................................................ 34
14 Contact ...................................................................................... 36
15 EU Declaration of Conformity ................................................. 39

1 Information on this Document
SMA Solar Technology AG
Operating manual MC-BOX-6-3-BE-en-30 5
1 Information on this Document
1.1 Validity
This document is valid for:
• MC-BOX-6.3-11 (Multicluster-Box 6)
1.2 Target Group
The tasks described in this document must only be performed by qualified persons. Qualified
persons must have the following skills:
• Training in how to deal with the dangers and risks associated with installing, repairing and
using electrical devices, batteries and installations
• Training in the installation and commissioning of electrical devices and installations
• Knowledge of all applicable laws, standards and directives
• Knowledge of and compliance with this document and all safety information
1.3 Levels of Warning Messages
The following levels of warning messages may occur when handling the product.
DANGER
Indicates a hazardous situation which, if not avoided, will result in death or serious injury.
WARNING
Indicates a hazardous situation which, if not avoided, could result in death or serious injury.
CAUTION
Indicates a hazardous situation which, if not avoided, could result in minor or moderate injury.
NOTICE
Indicates a situation which, if not avoided, can result in property damage.
1.4 Symbols in the Document
Symbol Explanation
Information that is important for a specific topic or goal, but is not safety-rele-
vant
☐
Indicates a requirement for meeting a specific goal
☑
Desired result

1 Information on this Document SMA Solar Technology AG
Operating manualMC-BOX-6-3-BE-en-306
Symbol Explanation
✖
A problem that might occur
Example
1.5 Typographical Elements in the Document
Typography Use Example
bold • Messages
• Terminals
• Elements on a user interface
• Elements to be selected
• Elements to be entered
• Connect the insulated
conductors to the terminals
X703:1 to X703:6.
• Enter 10 in the field
Minutes.
>• Connects several elements to be
selected
• Select Settings > Date.
[Button]
[Key]
• Button or key to be selected or
pressed
• Select [Enter].
# • Placeholder for variable
components (e.g., parameter
names)
• Parameter WCtlHz.Hz#
1.6 Designations in the Document
Complete designation Designation in this document
Multicluster-Box 6.3 Multicluster-Box
SunnyIsland 6.0H / 8.0H Sunny Island, battery inverter
1.7 Additional Information
For more information, please go to www.SMA-Solar.com.
Title and information content Type of information
SUNNYISLAND 4.0M / 6.0H / 8.0H Operating manual

2 Safety
SMA Solar Technology AG
Operating manual MC-BOX-6-3-BE-en-30 7
2 Safety
2.1 Intended Use
The Multicluster-Box is the main AC distribution board in a multicluster system. The multicluster
system forms an AC grid and is made up of a maximum of 2 clusters (each three-phase).
Do not exceed the maximum AC connection power of the Multicluster-Box. Cables with copper
conductors must be used for the installation.
The Multicluster-Box is designed for connection to TN-S- systems.
The Multicluster-Box must only be operated in conjunction with Sunny Island 6.0H (SI6.0H-13 /
SI6.0H-12) or Sunny Island 8.0H (SI8.0H-13 / SI8.0H-12). Always take the maximum AC
connection power and the permitted inverter combinations into account.
In terms of interference immunity, the product is suitable for EMC environment A, and in terms of
EMC emissions, it is suitable for EMC environment B (as per IEC 61439-1:2011).
The product is designed for indoor use only.
Only operate the product at temperatures between −-25°C and +60°C.
The Multicluster-Box is designed for use at altitudes of up to 2000 m above Mean Sea Level. If you
would like to use the Multicluster-Box at altitudes above 2000 m, contact Service (see Section14,
page36).
Use SMA products only in accordance with the information provided in the enclosed
documentation and with the locally applicable laws, regulations, standards and directives. Any
other application may cause personal injury or property damage.
Alterations to the SMA products, e.g., changes or modifications, are only permitted with the express
written permission of SMA Solar Technology AG. Unauthorized alterations will void guarantee and
warranty claims and in most cases terminate the operating license. SMA Solar Technology AG
shall not be held liable for any damage caused by such changes.
Any use of the product other than that described in the Intended Use section does not qualify as the
intended use.
The enclosed documentation is an integral part of this product. Keep the documentation in a
convenient, dry place for future reference and observe all instructions contained therein.
This document does not replace and is not intended to replace any local, state, provincial, federal
or national laws, regulations or codes applicable to the installation, electrical safety and use of the
product. SMA Solar Technology AG assumes no responsibility for the compliance or non-
compliance with such laws or codes in connection with the installation of the product.
The type label must remain permanently attached to the product.
2.2 IMPORTANT SAFETY INSTRUCTIONS
Keep the manual for future reference.
This section contains safety information that must be observed at all times when working.
The product has been designed and tested in accordance with international safety requirements. As
with all electrical or electronical devices, there are residual risks despite careful construction. To
prevent personal injury and property damage and to ensure long-term operation of the product,
read this section carefully and observe all safety information at all times.

2 Safety SMA Solar Technology AG
Operating manualMC-BOX-6-3-BE-en-308
DANGER
Danger to life due to electric shock when live components or cables are
touched
High voltages are present in the conductive components or cables of the product. Touching live
parts and cables results in death or lethal injuries due to electric shock.
• Do not touch non-insulated parts or cables.
• Disconnect the product from voltage sources and make sure it cannot be reconnected
before working on the device.
• Wear suitable personal protective equipment for all work on the product.
CAUTION
Risk of burns due to hot components
Some components and terminals inside the product can become hot during operation. Touching
hot components or terminals can result in burn injuries.
• Wear suitable personal protective equipment for all work on the product.
• After opening the product, wait until the components have cooled down.
NOTICE
Damage to the product due to sand, dust and moisture ingress
Sand, dust and moisture penetration can damage the product and impair its functionality.
• Do not open the product during a dust storm or precipitation.
• Close the product in case of interruption of work or after finishing work.
• Only operate the product when it is closed.
• Store the closed product in a dry and covered location. Observe storage conditions.
Effects of an emergency disconnection
Emergency disconnection on the battery inverter triggers the uncontrolled shutdown of the
system and unsaved data is lost.
• Only trip the emergency disconnection to avoid danger or consequential damage.
• In the event of an emergency disconnection, always check whether any fuse elements in
the product, such as circuit breakers, have tripped.
• If any fuse elements have tripped, reactivate these fuse elements.

3 Scope of Delivery
SMA Solar Technology AG
Operating manual MC-BOX-6-3-BE-en-30 9
3 Scope of Delivery
Check the scope of delivery for completeness and any externally visible damage. Contact your
distributor if the scope of delivery is incomplete or damaged.
D
B
AC
G
E F
Figure 1: Components included in scope of delivery
Position Quantity Designation
A 1 Multicluster-Box
B 1 Switch cabinet key
C 1 Data cable for communication (5m, black)
D 3 Data cable for measurement and control signals (5m, red)
E 4 Sealing ring with washer (diameter: 6mm)
F 4 Sealing ring with washer (diameter: 8mm)
G 1 Operating manual and circuitry overview

4 Product Overview SMA Solar Technology AG
Operating manualMC-BOX-6-3-BE-en-3010
4 Product Overview
4.1 Product Description
The Multicluster-Box is an SMA multicluster technology device for off-grid systems, battery-backup
systems, and systems for increased self-consumption. The Multicluster-Box is a main AC distribution
board to which you can connect up to 2 clusters. Each cluster is three-phase and made up of 3 DC-
side, parallel-switched SunnyIsland 6.0H / 8.0H inverters with firmware version 3.5 or higher.
Functions of the Multicluster-Box include:
• Main AC distribution board for Sunny Island inverters, one generator, one load, and one PV
system
• Load shedding
• Automatic bypass and reverse current monitoring for the generator
• Active anti-islanding
B
A
ComSyncTn ComSyncOut
Sl v2/L3
BackupVtgCur
Sl v1/L2
BackupVtgCur
Mstr/L1
BackupVtgCur
L1 L2 L3
F4.1 F4.2 F4.3
Main Cluster
L1 L2 L3
F4.4 F4.5 F4.6
Ext. Cluster 1
NL1 L2 L3
PE NPE
N N PE PE
L1 L2 L3
F2
Loads
N PE
X1
Generator
N PE
X4
All Clusters
PE
X5
Equipotential
Busbar
L1 L2 L3 N PE
X3
PV-System
N N PE
X2
Loads
2A 2A 2A
L1 L2 L3
F1
Generator
Figure 2: Multicluster-Box with cabinet door open
Position Designation
A Type label
The type label clearly identifies the product. The type label must remain per-
manently attached to the product. You will find the following information on
the type label:
• Device type (Model)
• Serial number (Serial No. or S/N)
• Date of manufacture
• Device-specific characteristics
B Circuit breaker