SMA Solar Technology MFR01-10 Manual de usuario

MFR-NR-IA-en-20 | 98-1000220 | Version 2.0
EN
Multi-Function Interface
MULTI-FUNCTION RELAY
Installation Manual


SMA Solar Technology AG Table of Contents
Installation Manual MFR-NR-IA-en-20 3
Table of Contents
1 Information on this Document. . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2 Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
2.1 Intended Use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
2.2 Qualification of Skilled Persons . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2.3 Safety Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
3 Scope of Delivery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
4 Product Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
5 Electrical Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
5.1 Safety during Electrical Connection. . . . . . . . . . . . . . . . . . . . . . . . . . 12
5.2 Mounting Position and Cable Routing . . . . . . . . . . . . . . . . . . . . . . . . 12
5.3 Installing the Multi-Function Relay in the Inverter . . . . . . . . . . . . . . . . 13
5.4 Multi-Function Relay Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
5.4.1 Connection Options for the Multi-Function Relay. . . . . . . . . . . . . . . 15
5.4.2 Connection to the Multi-Function Relay . . . . . . . . . . . . . . . . . . . . . . 19
6 Setting the Operating Mode of the Multi-function Relay . . . . 22
7 Technical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
8 Contact . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24

Table of Contents SMA Solar Technology AG
4 MFR-NR-IA-en-20 Installation Manual

SMA Solar Technology AG 1 Information on this Document
Installation Manual MFR-NR-IA-en-20 5
1 Information on this Document
Validity
This document is valid for device type "MFR01-10".
Target Group
This document is for skilled persons. Only qualified personnel with the appropriate skills are allowed
to perform the tasks described in this manual (see Section2.2 "Qualification of Skilled Persons",
page8).
Additional Information
Links to additional information can be found at www.SMA-Solar.com:
Symbols
Document title Document type
Measured Values and Parameters Technical description
Temperature Derating Technical information
Symbol Explanation
Indicates a hazardous situation which, if not avoided, will result in death
or serious injury
Indicates a hazardous situation which, if not avoided, could result in death
or serious injury
Indicates a hazardous situation which, if not avoided, could result in minor
or moderate injury
Indicates a situation which, if not avoided, could result in property damage
Information that is important for a specific topic or goal, but is not
safety-relevant
☐ Indicates an essential requirement for achieving a specific goal
☑ Desired result
✖ A problem that might occur

1 Information on this Document SMA Solar Technology AG
6 MFR-NR-IA-en-20 Installation Manual
Typography
Nomenclature
Display of Parameters
Depending on the type of communication, RS485, Bluetooth or Speedwire, the parameters are
displayed differently in the communication products. This document contains both display types.
Typography Usage Example
bold • Parameter
• Elements to be selected
• Elements to be entered
• Select the parameter
Operating mode of
multifunction relay or
Mlt.OpMode and set the
desired operating mode .
Full designation Designation in this document
Sunny Boy, Windy Boy, Sunny Tripower Inverter
Operating parameter Parameter
Example: Display of the operating mode parameter of the multi-function relay
• With communication via RS485: parameter Mlt.OpMode
• With communication via Bluetooth or Speedwire: parameter Operating mode of
multi-function relay

SMA Solar Technology AG 2 Safety
Installation Manual MFR-NR-IA-en-20 7
2Safety
2.1 Intended Use
You can use the multi-function relay for various purposes:
The multi-function relay is suitable for use in the following SMA inverters:
• SB 3000TL-21, SB 3600TL-21, SB 4000TL-21, SB 5000TL-21
• WB 3000TL-21, WB 3600TL-21, WB 4000TL-21, WB 5000TL-21
• SB 2500TLST-21, SB 3000TLST-21
• STP 8000TL-10, STP 10000TL-10, STP 12000TL-10, STP 15000TL-10, STP 17000TL-10
• STP 15000TLHE-10, STP 20000TLHE-10, STP 15000TLEE-10, STP 20000TLEE-10
Use the multi-function relay only for one of the indicated purposes. Any other use may result in
personal injury or property damage.
For safety reasons, it is not permitted to modify the product or install components that are not explicitly
recommended or distributed by SMA Solar Technology AG for this product.
The enclosed documentation is part of this product.
• Read and adhere to the documentation.
• Keep the documentation in a convenient place for future reference.
Application
(operating mode)
Description
Fault indication/FltInd The multi-function relay controls a display device which, depending on
the type of connection, either reports an error or the undisturbed
operation of the inverter.
Self-consumption/
SelfCsmp
The multi-function relay switches loads on or off, depending on the
power supply status of the plant.
Control via communication/
ComCtl
The multi-function relay switches the loads on and off via a
communication product.
Battery bank/BatCha The multi-function relay controls battery charging, depending on the
power supply situation of the plant.
Fan control/FanCtl The multi-function relay controls an external fan depending on the
temperature of the inverter.
Switching status grid relay/
GriSwCpy
The local network operator may require that a signal is transmitted as
soon as the inverter connects to the electricity grid.
The multi-function relay simulates the switching status of the grid relay
and trips a signal to the network operator.

2 Safety SMA Solar Technology AG
8 MFR-NR-IA-en-20 Installation Manual
2.2 Qualification of Skilled Persons
The work described in this document must be performed by skilled persons only. Skilled persons must
have the following qualifications:
• Knowledge of how an inverter works and is operated
• Training in how to deal with the dangers and risks associated with installing and using electrical
devices and plants
• Training in the installation and commissioning of electrical devices and plants
• Knowledge of the applicable standards and directives
• Knowledge of and adherence to this document and all safety precautions
2.3 Safety Precautions
Electric Shock
High voltages which may cause electric shocks are present in the conductive parts of the inverter.
• Prior to performing any work on the inverter, always disconnect the inverter as described in the
corresponding installation manual from any voltage sources on the AC and DC sides
(see inverter installation manual).
Burn Hazards
Some parts of the enclosure may get hot during operation.
• Do not touch any parts other than the lower enclosure lid of the inverter during operation.
Electrostatic Discharge
Touching electronic components can cause damage to or destroy the inverter through electrostatic
discharge.
• Earth yourself before touching any components.
• Avoid contact with components or plug contacts inside the inverter.

SMA Solar Technology AG 3 Scope of Delivery
Installation Manual MFR-NR-IA-en-20 9
3Scope of Delivery
Check the scope of delivery for completeness and any externally visible damage. Contact your
specialist dealer if the scope of delivery is incomplete or damaged.
Figure1: Components included in scope of delivery
Item Quantity Description
A 1 Multi-function relay*
B 1 M20x1.5 cable gland*
* If the multi-function relay has already been installed at the factory, this component is not included.
C 1 Installation manual
D 1 M4x8 cheese-head screw*
E1Washer M4*

4 Product Description SMA Solar Technology AG
10 MFR-NR-IA-en-20 Installation Manual
4Product Description
You can use the multi-function relay for various purposes:
The multi-function relay can be retrofitted, or installed in the inverter at the factory if specified in the
order.
Application (operating
mode)
Description
Fault indication/FltInd The multi-function relay controls a display device which, depending on
the type of connection, either reports an error or the undisturbed
operation of the inverter.
Self-consumption/
SelfCsmp
The multi-function relay switches loads on or off, depending on the
power supply status of the plant.
Control via communication/
ComCtl
The multi-function relay switches the loads on and off via a
communication product.
Battery bank/BatCha The multi-function relay controls battery charging, depending on the
power supply situation of the plant.
Fan control/FanCtl The multi-function relay controls an external fan depending on the
temperature of the inverter.
If the temperature of the inverter is 5°C higher than a specific
threshold set in the inverter, the fan starts automatically. If the
temperature of the inverter is 10°C lower than the threshold, the fan
stops automatically.
Switching status grid relay/
GriSwCpy
The multi-function relay switches simultaneously with the grid relay of
the inverter.